Second method:
6) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off
the load and shut down the system.
7) Make sure the bypass setting is enabled in each UPS and then turn off the system. All UPSs
will transfer to Bypass mode. Remove all the maintenance bypass covers and set the
maintenance switches
from “UPS” to “BPS” position. Turn off all the
input breakers and battery
breakers in parallel system.
8) Turn off the output breaker and remove the parallel cable and share current cable of the UPS
which you want to remove. Now, you can remove the UPS from parallel system.
9) Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode.
Set the m
aintenance switches from “BPS” to “UPS position and put
the maintenance bypass
covers back on.
10) Turn on the remaining UPS according to the previous section.
Warning: (Only for the parallel system)
●
Before turning on the parallel system to activate inverter, make sure that all
unit’s
maintenance
switch at the same position.
●
When parallel system is turned on, please do not operate the maintenance switch of any unit.
●
The parallel system DOES NOT support ECO mode. Therefore, please DO NOT
“enable”
ECO mode in any unit.
3-6. Fault Code
Fault code
Fault event
Fault code Fault event
01
Bus start failure
46
Incorrect UPS setting
02
Bus over
47
MCU communication failure
03
Bus under
49
Phase error on input and output
04
Bus unbalance
61
Bypass SCR short circuited
06
Converter over current
62
Bypass SCR open circuited
11
Inverter soft start failure
63
Voltage waveform abnormal in L1
phase
12
High inverter voltage
64
Voltage waveform abnormal in L2
phase
13
Low inverter voltage
65
Voltage waveform abnormal in L3
phase
14
Inverter L1 output(line to
neutral) short circuited
67
Bypass O/P short circuited
15
Inverter L2 output(line to
neutral) short circuited
68
Bypass O/P line to line short
circuited
16
Inverter L3 output(line to
neutral) short circuited
69
Inverter SCR short circuited
17
Inverter L1-L2 output (line to
line) short circuited
6C
BUS voltage drops too fast
18
Inverter L2-L3 output (line to
line) short circuited
6D
Current sampling error value
19
Inverter L3-L1 output (line to
line) short circuited
6E
SPS power error
1A
Inverter L1 negative power
fault
6F
Battery polarity reverse
1B
Inverter L2 negative power
fault
71
PFC IGBT over-current in L1
phase
1C
Inverter L3 negative power
fault
72
PFC IGBT over-current in L2
phase