2-3. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and the
following instructions executed by qualified personnel.
1)
Make sure the mains wire and breakers in the building are in compliance with the standard of rated
capacity of the UPS to avoid hazard of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less
than the UPS’s
maximum input current. Otherwise the receptacle may be burned and destroyed.
2)
Switch off the mains switch in the building before installation.
3)
Turn off all the connected devices before connecting to the UPS.
4)
Prepare wires based on the following table (use flexible cables):
HV Model
Wiring spec (mm²/AWG)
Input(Ph) Bypass(Ph) Output(Ph)
Neutral
Battery
Ground
M5T 10K 3/3
6 /
14
6 /
14
6 /
14
6 /
10
6 /
8
M5T 10K WOB 3/3
6 /
14
6 /
14
6 /
14
6 /
10
6 /
8
6 /
8
M5T 10K 3/1
6 /
14
6 /
8
6 /
8
6 /
8
6 /
8
M5T 10K WOB 3/1
6 /
14
6 /
8
6 /
8
6 /
8
6 /
8
6 /
8
M5T 15K 3/3
6 /
12
6 /
12
6 /
12
6 /
10
6 /
8
M5T 15K WOB 3/3
6 /
12
6 /
12
6 /
12
6 /
10
6 /
8
6 /
8
M5T 15K 3/1
6 /
12
6 /
6
6 /
6
6 /
6
6 /
6
M5T 15K WOB 3/1
6 /
12
6 /
6
6 /
6
6 /
6
6 /
8
6 /
6
M5T 20K 3/3
10 /
10
10 /
10
10 /
10
10 /
6
10 /
6
M5T 20K WOB 3/3
10 /
10
10 /
10
10 /
10
10 /
6
10 /
8
10 /
6
M5T 20K 3/1
10 /
10
10 /
4
10 /
4
10 /
4
10 /
4
M5T 20K WOB 3/1
10 /
10
10 /
4
10 /
4
10 /
4
10 /
8
10 /
4
M5T 30K
16 /
8
16 /
8
16 /
4
16 /
4
16 /
4
16 /
4
M5T 30K WOB
16 /
8
16 /
8
16 /
4
16 /
4
16 /
4
16 /
4
M5T 40K
16 /
6
16 /
6
16 /
4
16 /
4
16 /
4
16 /
4
M5T 40K WOB
16 /
6
16 /
6
16 /
4
16 /
4
16 /
4
16 /
4
M5T 60K S
25 / 4
25 / 4
25 / 4
-
-
LV Model
Wiring spec (mm²/AWG)
Input(Ph) Bypass(Ph) Output(Ph)
Neutral
Battery
Ground
M5T 10K 3/3
10 /
10
10 /
10
10 /
10
10 /
6
10 /
6
M5T 10K WOB 3/3
10 /
10
10 /
10
10 /
10
10 /
6
8
10 /
6
M5T 10K 3/1
10 /
10
10 /
4
10 /
4
10 /
4
10 /
4
M5T 10K tri/ WOB 3/1
10 /
10
10 /
4
10 /
4
10 /
4
10 /
8
10 /
4
M5T 15K
16 /
8
16 /
8
16 /
4
16 /
4
16 /
4
16 /
4
M5T 15K WOB
16 /
8
16 /
8
16 /
4
16 /
4
16 /
4
16 /
4
M5T 20K
16 /
6
16 /
6
16 /
4
16 /
4
16 /
4
16 /
4
M5T 20K WOB
16 /
6
16 /
6
16 /
4
16 /
4
16 /
4
16 /
4
M5T 30K S
25 / 4
25 / 4
25 / 4
-
-
NOTE 1:
The cable for
M5T 10k (SB) HV
should be able to withstand over 20A current. It is recommended
to use
6mm²/14 AWG
or thicker wire for Phase