3.3.2 Cold Start Startup
Step 1: Switch ON the battery Breaker.
Step 2: Press the “Battery Start” button on any one of Power Modules to start up the control
power of all Power modules and STS moodule as shown below.
Battery Start Button
Step 3: After pressing the “Battery Start” button, UPS will enter into Standby mode. Refer to the
diagram below for LCD display.
Step 4: Before UPS enters into shutdown mode, please press “Power On/Off” button for 2 second
immediately as shown in the diagram below.