Stop by Battery
Voltage
Set stop battery voltage in battery test (11~12V) x
(battery Number)
11V x Battery Number (Default)
Stop by Battery
Capacity
Set battery capacity to stop battery-testing. (20~50%)
20% (Default)
Battery Age
Alert
Battery Age Alert
(Months)
Set battery age for replacement. (Disable,12~60Months)
Disable (Default)
If this feature is enabled and the battery has been
installed over this period, there is a warning “Battery Age
Alert” to indicate it.
Temperature
Compensation
--
Set battery temperature compensation. (0~-5 (mV/
℃
/cl))
0(mV/
℃
/cl) (Default)
Charging
Voltage
--
Set battery charging voltage. (2.30~2.35V)
2.35V (Default)
Set battery float voltage. (2.23~2.35V)
2.29V (Default)
4.2.6.4 Pre-Alarm Screen
Use UP and DOWN buttons to switch different sub-menus. Press ENTER button to go into the
Pre-Alarm setting screen, as shown in Figure 4-26.
Figure 4-26 Setup-Pre-Alarm screen
Pre-Alarm setting can be set in any operation mode. See Setup-Pre-Alarm setting list in Table
4-10.
Table 4-10: Setup-Pre-Alarm setting list
Setting Item Sub Item
Explanation
Line Voltage
Range
--
Set line voltage range:
Upper limit
+5%
+10%
+15%
+20% (Default)