8. Specifications
Mod5T
Mod5T
Mod5T S
GENERAL CHARACTERISTICS
Phase
3-Phase in / 3-Phase out
Power
from 30 to 300 kVA
Power factor
1*
Battery Bank
Integrated
External
Power module
30kVA/30kW
Cabinet
30U / 42U
INPUT
Nominal Voltage
3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Range
305 ~ 478 VAC at 100% load ; 208 ~ 304VAC at <70% load
Nominal frequency
50/60Hz (Auto sensing)
Frequency range
40Hz ~70Hz
Power factor
> 0.99 at 100% load, >0.98 at 50% load
Harmonic Distortion (THDi)
< 3% @ 100% load
OUTPUT
Nominal Voltage
3 x 380VAC/400VAC/415VAC (3Ph+N) (HV models)
Voltage Regulation (Steady state)
≦
± 1% Typical (balanced load)
≦
± 2% Typical (unbalanced load)
Voltage Regulation (Transient)
<=± 5% Typical
Nominal frequency
50/60Hz
Frequency Range (Synchronized
range)
46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability
1 hour for 110%, 10 mins for 120%, 1 min for 150%, 200ms for >150%
Harmonic Distortion (THDv)
≦
2% THD (Linear Load)
≦
4% THD (Non-linear Load)
Efficaciency
Up to 94.5%
BATTERY / CHARGER
Nominal Voltage
+/- 240V (12V x 40 Pcs)
Floating Charge Voltage
2.25V/element
Boost Charging Voltage
2.35V/element
Temperature Compensation
Yes
Maximum Charging Current
8A for each power module (ajustable)
MANAGEMENT / COMMUNICATION
Communication
USB & RS232 port (supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC)
Optional SNMP : Power management from SNMP manager (compatible VMware
©
)
and web browser
ENVIRONMENT
Operation Temperature
0 ~ 40°C
Relative Humidity
0 ~ 95% non-condensing
Altitude **
<1000m for Nominal power
IP Class
IP 20
NORMS
Standard
CE RoHS
EMC
EN62040-2:2006, EN61000-3-12:2011, EN61000-3-11:2000, EN55024:2010, IEC 61000-4-2:2008, IEC
61000-4-3:2006+A1:2007+A2:2010, IEC61000-4-4:2012, IEC 61000-4-5:2005, IEC 610004-6:2008, IEC
61000-4-8:2009, IEC 61000-2-2:2002
LVD
EN 62040 1 : 2008/A1:2013
Product specifications are subject to change without further notice.
*When temperature is above 30
℃
, the output power factor will be de-rated, 0.8 at 31
℃
~35
℃
and 0.7 at 36
℃
~40
℃
.
**If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.