16: Floating charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust floating
charger voltage.
Parameter 3:
the voltage range is from
0V to 6.4V
, the default
value is 0V.
17: Constant charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust constant
charger voltage.
Parameter 3:
the voltage range is from
0V to 3.2V
, the default
value is 0V.
18: Charger maximum current setting
(factory setting, do not modify)
Interface
Setting
Parameter 3:
E4 Value 4000 / 5000 models : The maximum charging current
could be adjusted as 1A or 2A. Default value is 1A.
E4 Value 5000 B+ / 6000 / 10k models : The maximum charging
current could be adjusted. Default value is 1A. The available
options are 1A, 2A, 4A and 6A. 6A is only available for 16 pieces of
batteries.
19: Battery capacity and parallel groups setting
(factory setting, do not modify)
Interface
Setting
Parameter 2:
Set the battery capacity at 7AH, 9AH, 10AH, 12AH, 17AH, 26AH,
40AH, 65AH, 100AH and so on.
The default value is 9AH.
Parameter 3:
Set the battery group range from 1 to 6. The default value is 1
group. These parameters are for the battery backup time
calculation.
20: Backup time calibration
(factory setting, do not modify)
Interface
Setting
Parameter 3:
Calibrate the displayed backup time by adjusting this multiplier
factor. The calculation is as below:
Displayed backup time=Original calculated backup time x
Multiplier factor
The default value of the multiplier factor is 1.0, and the range is
from 0.5 to 2.