16
3.8 Warning indicators
Warnings Icons
(flashing)
Alarms
Low battery
Sounding every second.
Overload
Sounding twice every
second.
Battery is not
connected
Sounding every second.
Overcharge
Sounding every second.
Site wiring fault
Sounding every second.
EPO enable
Sounding every second.
Fan failure
Sounding every second.
Over temperature
Sounding every second.
Charger failure
Sounding every second.
Battery fault
Sounding every second.
4 . T R O U B L E S H O O T I N G
If the UPS system does not operate correctly, please solve the problem by using the table
below.
Symptoms Possible
causes
Remedy
No indication and alarm even though
the main is normal.
The AC input power is not
correctly connected.
Check if input power
cord firmly connected to
the mains.
The AC input is connected to
the UPS output.
Plug AC input power
cord to AC input
correctly.
The icon
and the warning
code
flashing on LCD display
and alarm is sounding every second.
EPO function is activated.
Set the circuit in close
position to disable EPO
function.
The icon
and
flashing on
LCD display and alarm is sounding
every second.
Line and neutral conductors
of UPS input are reversed.
Rotate mains power
socket by 180° and then
connect to UPS system.
The icon
and
The external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.