360o shield on the connectors
There must never be a shield interruption on the whole cable length.
Self-sticking copper ribbon if necessary for increasing the shield
diameter to get properly tightened under the clamp
Connector on MAVILOR
RBF RACK
motor for resolver and motor
The cable can be soldered on the shield
because the connector box is metalic
This solution does not correspond exactly
to the IEC requirements, but it is acceptable
Connector box on the MAVILOR motor
As short as possible
Ground
V
U
W
Metallic or metal plated plastic
SMTBM-20A
Sub-D pin package
360 degrees shield ensured by
the tightening clamp
The fastening screw must be tightened
in order to ensure the shield continuity
on the amplifier housing
Sub-D connector
Note
:
When the 360 degrees shield is made by means of a clamp, it is not necessary to connect a wire to the appropriate
pin on the Sub-D connector