SMT-BD2
3.2
-
M
OTOR
H
ALL
E
FFECT
S
ENSORS ADJUSTMENT
If the motor is using Hall Effect Sensors, check that the COM jumpers setting is correct according to the motor
HES type (60° or 120°).
Check that the ENABLE input is disabled and the amplifier turned on.
If the “ HES ” error is displayed, turn off the amplifier and check the following points before turning it on again:
♦
The HES are correctly wired on the amplifier X1 connector (if 60° type HES are used, check the different
HES signals wiring combinations to find the right wiring order).
♦
The commutation signal jumpers COM are correctly set according to the HES type.
♦
The HES supply voltage value is correct.
Move the motor manually over one revolution, or one pole pitch for a linear motor.
If the “ HES ” error is displayed turn off the amplifier and check the following points before turning it on again:
♦
The HES are correctly wired on the amplifier X1 connector (if 60° type HES are used, check the different
HES signals wiring combinations to find the right wiring order).
♦
The commutation signal jumpers COM are correctly set according to the HES type.
♦
The HES supply voltage value is correct.
♦
The
Motor encoder resolution
parameter value is correct.
If the motor HES are not working correctly, select the following COM jumpers setting to run the motor without the
HES devices.
B5
B4
COM
B3
In this case a motor phasing procedure must be executed at each amplifier power up.
3.3
-
A
BSOLUTE SINGLE TURN
S
IN
/C
OS ENCODER ADJUSTMENT
If the motor is using an absolute single turn Sin/Cos encoder (Heidenhain ERN 1085 or compatible), check that
the COD and COM jumpers setting are correct.
Check that the ENABLE input is disabled and the amplifier turned on, and move the motor manually over one
revolution.
If the “ HES ” error is displayed, turn off the amplifier and check the following points before turning it on again:
♦
The Sin/Cos encoder commutation channels are correctly wired on the amplifier X1 connector.
♦
The commutation signal jumpers COM are correctly set.
♦
The Sin/Cos encoder supply voltage value is correct.
♦
The
Motor encoder resolution
parameter value is correct.
39
Chapter 6 - Commissioning