User Manual V1.3 | XtracontrolDC2, XtracontrolET2, XtracontrolEC21
XtracontrolDC2.04
XtracontrolDC2.07
polarity
Voltage failure switching
10 ms at < 20.4 V DC
Ethernet interfaces
No. / type of interface
1x 10/100 Base T
Connection system
RJ45
Protocols
TCP/IP, Modbus TCP, BACnet, Profinet
EtherCAT interfaces
No. / type of interface
1x EtherCAT (EtherCAT master)
Connection system
RJ45
USB interfaces
No. / type of interface
1x host USB 2.0 / USB plug port A
No. plugging/unplugging cycles
max. 1,000
CAN bus interfaces
No. / type of interface
1x CAN bus
Protocols
CAN-Bus and/or CANopen master
Serial interfaces
No. / type of interface
1x RS-232;
1 x RS-485
Protocols
Modbus RTU
Additional functions
Real-time clock
yes, with battery back-up
microSD card slot
1x microSD card
I/O
Digital IN
4x
Digital OUT
4x (0.5 A)
Analogue IN
2x (–10…+10 V, PT100/PT1000 with 2-wire)
2x (–10…+10 V, or return lead for 3-wire)
Battery
Type
Panasonic VL2020 or similar
Lifespan
10 years (depends on operating temperature)
Storage
1 year without voltage (any longer and RTC data can be lost)
Front membrane display (Autoflex)
Ambient temperature
(rel. atmospheric humidity 10…
95 %)
–40…+60 °C
Ambient temperature
(rel. atmospheric humidity
< 10 %)
–40…+85 °C
(without loss of functionality after 0.5 million activations at –40 °C)
Use outdoors
Like all polyester-based membranes, Autoflex is unsuitable for long-
term exposure to direct sunlight.