background image

www.austin-hughes.com

UM-PPS-03-S-Q320V1

P.22

< 1.10 >   SNMP Setup

Step 5

. Select the 

SNMP

 from the left navigation pane

Step 6

. The 

SNMP

 Settings window appears as below:

Step 7. 

Click 

“ Enable “ 

in

 “ SNMP agent “ 

to start the SNMP agent service

Step 8. 

Select 

“ v1/v2 “ 

in 

“ SNMP version “

Step 9. 

Input 

“ SNMP port “. 

 Default is 161

Step 10. 

Input “ 

sysContact

 “. Default is human.being<nobody@but.you>

Step 11. 

Input “ 

sysLocation

 “. Default is Earth

Step 12.

 Input “ 

sysName

 “. Default is A320D

Step 13. 

Inpu

t “ Read Community “.  

Default is public

Step 14. 

Input 

“ Write Community “. 

 Default is private

Step 15. 

Click

 “ Activate “

 in Station 1 to enable the trap service

Step 16.

 Input

 “ Trap Station IP “ , “ Trap Port “ 

“ Trap Community “ 

of Station 1

Step 17. 

Repeat Step 14 & 15 for Station 2 & 3

Step 18. 

Click 

“ Apply “ 

to 

fi

 nish the SNMP v1 / v2 settings

Summary of Contents for PPS-03-S

Page 1: ...stin hughes com UM PPS 03 S Q320V1 PPS 03 S IP dongle GUI SNMP InfraPower Intelligent PDU Inspired by Your Data Center User Manual Designed and manufactured by Austin Hughes 1 Phase 1 Phase Dual Feed 3 Phase ...

Page 2: ...rvice personnel should open the chassis Opening it yourself could damage the equipment and invali date its warranty If any part of the equipment becomes damaged or stops functioning have it checked by qualified service personnel What the warranty does not cover Any product on which the serial number has been defaced modified or removed Damage deterioration or malfunction resulting from Accident mi...

Page 3: ...Meter PDU Level Setting P 4 1 4 IP Dongle Configuration P 5 1 5 Remote PDU Level ID Setting P 6 1 6 PPS 03 S IP Dongle GUI P 10 1 7 System P 15 1 8 Network P 16 1 9 Login P 17 1 10 SNMP Setup P 21 1 11 Notification P 26 1 12 Syslog P 27 1 13 IP Dongle Firmware Upgrade P 28 1 14 DHCP Setting P 30 1 15 Command Line Interface Access P 33 ...

Page 4: ...moke Sensor Monitoring Remote Access via Web Graphic User Interface PDU Series Support All Single Three Phase iPDU All Single Three Phase Dual Feed iPDU All Single Three Phase inline meter All Single Three Phase Dual Feed inline meter IP Dongle Access to 32 PDU Levels Patented IP Dongle provides IP remote access to the PDUs by a true network IP address chain Only 1 x IP dongle allows access to max...

Page 5: ...database Strong passwords and granular user user group permissions Remote Management Significantly reduce the number of Ethernet ports used in deployment by cascading a single network connection across multiple iPDUs up to 32 Simultaneous access via free management software IPM 04 web GUI SNMP V2 V3 Remote level ID setting for cascaded iPDU s Alerts Alarms Receive alerts via SNMP email SMTP and sy...

Page 6: ... Phase 3 Phase InfraPower PDU IP dongle installation steps slide the IP dongle on the plate above the meter plug the RJ 45 connector of IP dongle into the LINK port of the 1st level PDU meter use the CAT 5e 6 cable to connect IP dongle to network device To LINK port of 1st PDU 1st level PDU meter 3rd level PDU meter 2nd level PDU meter Cat 5e 6 cable Up to 20M Cat 5e 6 cable Up to 20M To LINK port...

Page 7: ...press to confirm Step 2 Press the button to PDU ID and press to confirm II For 2 8 LCD Meter With touchscreen function I For 1 8 LCD Meter No touchscreen function III For 2 8 LCD Meter With touchscreen function Level 16 0 Cancel Enter 8 7 9 5 4 6 2 1 3 Level 29 0 Cancel Enter 8 7 9 5 4 6 2 1 3 PDU Level 050 29 Group Level A M B Setup Level Buzzer Sensor Screen Outlet ON M I For PDU with firmware v...

Page 8: ... dongle Step 5 Enter device name in Name min 4 char max 16 char Default is Name Step 6 Enter device location in Location min 4 char max 16 char Default is Rack_001 Step 7 Enter password in Password for authentication min 8 char max 16 char Default is 00000000 Step 8 Enter new password in New password min 8 char max 16 char Step 9 Re enter new password in Confirm new password Step 10 Change the des...

Page 9: ...irmware version V37 or above supports this functions You MUST have the PDU serial number onhand and know which rack the PDU is installed Step 1 Open Internet Explorer I E version 11 Step 2 Enter the configured IP Dongle address into the I E address bar Default IP address of LAN 1 is 192 168 11 1 Default IP address of LAN 2 is 192 168 0 1 Step 3 Enter the Login name and Password Click Login Step 4 ...

Page 10: ...www austin hughes com UM PPS 03 S Q320V1 P 7 Step 5 After the searching is completed the following screen will display 1 5 Remote PDU Level ID Setting ...

Page 11: ...www austin hughes com UM PPS 03 S Q320V1 P 8 Step 6 Assign a unique Level Name and Location to each PDU and ensure to check the register box Then Click Apply 1 5 Remote PDU Level ID Setting ...

Page 12: ...www austin hughes com UM PPS 03 S Q320V1 P 9 Step 7 After the PDU level setting is complete Status page will display the PDU with proper level 1 5 Remote PDU Level ID Setting ...

Page 13: ...rer I E version 11 0 Step 2 Enter the configured IP dongle address into the I E address bar Please refer to 1 4 IP dongle configuration Default IP address of LAN 1 is 192 168 11 1 Default IP address of LAN 2 is 192 168 0 1 Step 3 Enter Login name Password Click Login Please refer to 1 4 IP dongle configuration In Status Click Search to search all new installed PDUs View all installed PDUs status V...

Page 14: ...uits Click Apply Click Reset to reset peak amp or kWh of PDU s circuits Click ON OFF to swich ON OFF outlet Switched PDU only View On Off status of each PDU s outlet View aggregated current on the PDU View latest loading energy consumption of each PDU s outlet Outlet Measurement PDU only Click Time Sync update PDU s real time clock from the computer logged in the IP Dongle ...

Page 15: ...e PDU s outlet name Change Power up sequence delay of PDU s outlet Switched PDU only Change Alarm amp Rising Alert amp Low alert amp of PDU s outlet Outlet Measurement PDU only Click Apply to finish the above settings Click Reset to reset peak amp or kWh of PDU s outlet Outlet Measurement PDU only ...

Page 16: ...3 In Sensor Status View status location latest reading alarm setting of Temp Humid sensors View status location of Door sensor Smoke sensor The GUI will not show the status reading if sensors are NOT installed activated 1 6 PPS 03 S IP Dongle GUI ...

Page 17: ...ngle GUI In Sensor Setting Default Sensor setting Deactivate Activate sensors ONLY when they are connected Change Location Rising alert Setting Alarm Setting of Temp Humid sensors Change Location of Door sensor Smoke sensor If no any sensor connected NEVER activate ...

Page 18: ...le name location Change temperature unit displayed in UI Set the Date Time of the IP dongle by Manually or NTP server Default is Manually Tick Force HTTPS to provide data transmission security Default Web Access is HTTP Click Apply to finish the above settings 1 7 System ...

Page 19: ...bnet mask Gateway For static IP setting only Enter the IP address of Primary DNS Default is 8 8 8 8 Enter the IP address of Secondary DNS Default is 0 0 0 0 Click Apply to finish the above settings Failover mode Tick Enable automatic failover to operate the failover mode Enter IPv4 address IPv6 address Subnet mask Gateway For static IP setting only Enter the IP address of Primary DNS Default is 8 ...

Page 20: ...ssword in Confirm password Click Apply and OK on the pop up window to make changes effective Domain LDAP Default Join Domain is Disable Enable Join Domain only when you want to login the IP dongle WEBUI by AD server Enter AD Server Account Login Password Click Apply and OK on the pop up window to make changes effective You can now go to Domain Users to assign access right to the Domain Users or the ...

Page 21: ...access Allow Deny to Domain Users and click Apply The Domain User assigned Allow access right can login the IP dongle WEBUI In Domain Users Setting Click Update domain data to update domain group list Assign access right No access Allow to Domain Group and click Apply The Users of the Domain Group assigned Allow access right can login the IP dongle WEBUI ...

Page 22: ...in the IP dongle WEBUI by LDAP server Enter LDAP Server Select Protocol LDAP LDAPS Default is LDAP Enter Port Default is 389 Select Encrytion None SSL Default is None Enter Base DN Enter Account Login Password Click Apply and OK on the pop up window to make changes effective You can now go to LDAP Users to assign access right to the LDAP User or the LDAP Group ...

Page 23: ...right No access Allow Deny to LDAP User and click Apply The LDAP User assigned Allow access right can login the IP dongle WEBUI In LDAP Access Setting Click Update domain data to update domain user list Assign access right No access Allow Deny to LDAP Group and click Apply The LDAP Group assigned Allow access right can login the IP dongle WEBUI ...

Page 24: ...esources infrapower software Step 2 Select the appropriate MIB file of the PDU series II Enabling SNMP Support i The following steps summarize how to enable the IP Dongle for SNMP v1 v2 support Step 1 Connect the IP Dongle to a computer Please refer to 1 4 IP dongle configuration Step 2 Open the Internet Explorer I E version 11 0 Step 3 Enter the configured IP Dongle address into the I E address b...

Page 25: ...ort Default is 161 Step 10 Input sysContact Default is human being nobody but you Step 11 Input sysLocation Default is Earth Step 12 Input sysName Default is A320D Step 13 Input Read Community Default is public Step 14 Input Write Community Default is private Step 15 Click Activate in Station 1 to enable the trap service Step 16 Input Trap Station IP Trap Port Trap Community of Station 1 Step 17 R...

Page 26: ...le to a computer Please refer to 1 4 IP dongle configuration Step 2 Open Internet Explorer I E version 11 0 Step 3 Enter the configured IP Dongle address into the I E address bar Default IP address of LAN 1 is 192 168 11 1 Default IP address of LAN 2 is 192 168 0 1 Step 4 Enter Login name Password Default login name password are 00000000 Step 5 Select SNMP from the left navigation pane 1 10 SNMP S...

Page 27: ...Write in User role Step 15 Input the name of USM user Default is usm_user1 Step 16 Select None MD5 SHA in Auth algorithm If you select Read Write in User role you MUST select MD5 SHA in Auth algorithm Step 17 Input the Auth password Default is 00000000 Step 18 Select None DES AES AES192 AES256 in Privacy algorithm If the Auth algorithm is NONE NO privacy algorithm can be selected Step 19 Input the...

Page 28: ...25 III SNMP Traps Setting After enable SNMP you can click SNMP Traps to go to the SNMP Traps Setting page Below is the default setting for each PDU SNMP trap You can set the SNMP trap option and Click Apply to finish the settings 1 10 SNMP Setup ...

Page 29: ...is Port 25 Step 3 Enable or Disable the SMTP authentication Default is Disable Step 4 Enter User name and Password when SNMP authentication is enabled Step 5 Select the secure connection None SSL TLS STARTTLS Default is None Step 6 Enter the Sender Name and Sender Email Step 7 Enter the Alarm Interval Min 10 Max 60 mins Step 8 Enter the alarm recipient email account in Recipient 01 Step 9 Repeat s...

Page 30: ...www austin hughes com UM PPS 03 S Q320V1 P 27 In Syslog you can view the latest 2000 device and system log 1 12 Syslog ...

Page 31: ...urces infrapower software Step 2 Select the appropriate IP Dongle firmware file of the PDU series Step 3 Connect the IP Dongle to the computer Please refer to 1 4 IP dongle configuration Step 4 Open the Internet Explorer I E version 11 0 Step 5 Enter the configured IP Dongle address into the I E address bar Default IP address of LAN 1 is 192 168 11 1 Default IP address of LAN 2 is 192 168 0 1 Step...

Page 32: ...mware upgrade window appears as below Step 9 Click Browse and select the firmware file xxx zip from the specific path in the pop up window and Click Open Step 10 Click Upgrade to start the upgrade process It takes a few minutes to complete Step 11 Once complete UI will return to the login page ...

Page 33: ...E version 11 0 Step 3 Enter the configured IP Dongle address into the I E address bar Default IP address of LAN 1 is 192 168 11 1 Default IP address of LAN 2 is 192 168 0 1 Step 4 Enter the Login name Password Default login name password are 00000000 Step 5 Select Network from the left navigation pane Step 6 Dual Lan Mode Select ON from DHCP of LAN 1 LAN 2 Click Apply to save the settings ...

Page 34: ...UM PPS 03 S Q320V1 P 31 1 14 DHCP Setting Step 7 Select Firmware from the left navigation pane Step 8 Record the MAC address of LAN 1 LAN 2 Step 9 Assign an IP addressof LAN 1 LAN 2 of to the IP Dongle from your DHCP server ...

Page 35: ...4 DHCP Setting Complete Step 10 Failover Mode Select ON from DHCP Click Apply to save the settings Step 11 Select Firmware from the left navigation pane Step 12 Record the MAC address Step 13 Assign an IP address to the IP Dongle from your DHCP server ...

Page 36: ...ollowing settings via CLI access i System settings Change temperature display unit change the temp unit to be displayed in the WEBUI Change system RTC date time set the system time of the IP Dongle Change network settings change the IP settings of the IP Dongle Change features services a Enable disable management software support b Enable disable SNMP agent c Enable disable FTP server d Enable dis...

Reviews: