background image

 

 

 12  

 

R

e

v

is

n

: 0

5

   

  R

e

f.:

 M

A

N

U

_

V

B

Z

   

 1

6

/0

2

/2

0

1

7

 

 

 

Drain Maintenance 

Each  unit  has  a  drain  located  inside  the  unit  which  removes  the  condensation  from  the 

evaporator  coil  and  evaporates  it  at  an  external  condensate  pan.  If  you  notice  excessive  water 

accumulation on the inside of the unit be sure the drain tube is connected from the evaporator housing 

to the condensate evaporator drain pan. 

 

If  water  is  collected  underneath  the  unit  you  may  want  to  check  the  condensate  evaporator 

drain tube to be sure it is still located inside the drain pan. 

 

Be  sure  all  drain  lines  are  free  of  obstructions;  typically,  food  product  is  found  blocking  drain 

lines causing water to back up and overflow the drain pans. 

 

 

 

 

Many  operating  problems  are  derived  from  causes  that  can  be  easily  eliminated  without  the 

need  to  contact  the  Technical  Department.  The  following  page  shows  a  table  with  types  of  problems 

that may come up, their cause, and how to resolve them. 

 

PROBLEM 

POSSIBLE SOLUTION 

Compressor  will  not  start-no 

hum. 

1.- Disconnect switch open. 

2.- Blown fuse. 

3.- Defective wiring. 

4.- Overload protector tripped. 

5.- Open control contacts (control may be defective, or unit location 

may be too cold). 

6.- Defective overload protector. 

7.- Low charge of freon-check for leaks. 

Compressor  will  not  start-no 

hums but cycles on overload. 

1.- Low voltage. 

2.- Unit wired incorrectly. 

3.- Starting capacitor defective. 

4.- Starting capacitor seal. 

5.- Compressor motor defective. 

6.- High head pressure. 

7.- Bearing of pistons tight-low oil charge. 

10

 

TROUBLE SHOOTING CHART 

Summary of Contents for VBZ Ibiza

Page 1: ...VBZ Ibiza Cases GELATO DISPLAY CASES Service Installation Manual...

Page 2: ...CEDURE 7 8 OPERATION 7 8 1 Temperature control adjustment 7 8 2 Defrost control 8 8 3 Loading product 10 9 MAINTENANCE CARE AND CLEANING 10 9 1 Cleaning procedure 10 9 2 Parts and Service Error Marcad...

Page 3: ...cluding the following This refrigerator must be properly installed and located in accordance with this manual before it is used Do not allow children to climb stand or hang on the shelves in the refri...

Page 4: ...nt This unit is intended for indoor use only Be sure the location chosen for your unit must be able to provide good air circulation for most efficient refrigeration Avoid locations near heat sources s...

Page 5: ...front side or back However you must be certain to allow the unit to remain in an upright position afterwards for at least 24 hours before plugging it in so that the compressor oil and refrigerant may...

Page 6: ...e should be checked before connection to assure that proper voltage for the cabinet wiring is available To determine correct unit voltage please refer to the serial data plate located on an inner wall...

Page 7: ...ercial standards If any unusual noises are heard turn the unit off immediately and check for any obstructions of the fans All cabinets must be given enough time to reach normal operating temperature b...

Page 8: ...Menu mode it is used to look through the parameter codes or decrease the value of the variable in use This turns the light on and off Note while in the OFF status the light button is active VBZ ice c...

Page 9: ...wo defrost cycles To adjust this parameter you may follow the next instruction 1 Enter the Programming mode by pressing the SET DOWN keys for 3s the C or F LED starts blinking 2 Select the required pa...

Page 10: ...binet Do not leave food inside the unit when it is going to remain shut down either from a power outage or fault in the equipment If the cabinet is going to remain shut down for prolonged periods try...

Page 11: ...st be able to freely circulate through the condenser so the surface of the condenser must be kept free of dirt and grease for proper system operation Dirty condensers result in compressor failure and...

Page 12: ...to back up and overflow the drain pans Many operating problems are derived from causes that can be easily eliminated without the need to contact the Technical Department The following page shows a ta...

Page 13: ...ective 3 Overload protector defective 4 High head pressure 5 Fan motor pump etc wire to wrong of overload protector Compressor starts but immediately cuts out on overload 1 Starting relay contacts poi...

Page 14: ...Fixture doors left open too long 8 Insufficient defective or water logged insulation 9 Evaporated oil logged Noisy unit 1 Compressor oil charge low 2 Fan cable on condenser or evaporator bent causing...

Page 15: ...r authorization by Infrico In addition to the warranty set above Infrico warrants the hermetically and semi hermetically sealed compressor part only for an additional four 4 years based on the install...

Page 16: ...pparatus is not functioning correctly users must make the checks indicated in the manual and if the problem persists contact their distributor This certificate must be presented if it is necessary for...

Page 17: ...improper or non compliant installation of the apparatus connection voltage power supply fluctuations electrical connection not conforming to instructions etc or from manipulation of the nameplate or o...

Page 18: ...___________ Compressor No __________________________ Vendor Signature Purchaser Signature R E T U R N T O T H E M A N U F A C T U R E R User ___________________________________________________________...

Page 19: ...Infrico SL CR CO 762 Los Piedros Las Navas s n 14900 Lucena C rdoba Espa a 00 34 957 59 51 16 office 00 34 957 59 51 06 fax asistenciatecnica infrico com info infrico com www infrico com...

Reviews: