background image

 

 

 13  

 

R

e

v

is

n

: 0

5

   

  R

e

f.:

 M

A

N

U

_

V

B

Z

   

 1

6

/0

2

/2

0

1

7

 

PROBLEM 

POSSIBLE SOLUTION 

Compressors start, but starting 

remains in circuit. 

1.- Low voltage. 

2.- Unit wired incorrectly. 

3.- Starting capacitor seal. 

4.- Running capacitor defective. 

5.- Starting relay defective. 

6.- High head pressure. 

7.- Bearings of pistons tight-low oil charge. 

Compressor  starts  and  runs, 

but cycles on overload 

1.- Low voltage. 

2.- Running capacitor defective. 

3.- Overload protector defective. 

4.- High head pressure. 

5.- Fan motor, pump, etc… , wire to wrong of overload protector. 

Compressor tries to start when 

thermostat closes but cuts out 

on overload, start after several 

attempts. 

1.- Low voltage. 

2.- Start capacitor defective. 

3.- Overload protector defective. 

4.- High head pressure. 

5.- Fan motor, pump, etc… , wire to wrong of overload protector. 

Compressor 

starts 

but 

immediately 

cuts 

out 

on 

overload 

1.- Starting relay contacts points welded together. 

2.- Starting capacitor defective. 

3.- Compressor short cycles. 

Starting relay burns out. 

1.- Low voltage. 

2.- High voltage. 

3.- Compressors short cycles. 

4.- Incorrect running capacitor. 

5.- Incorrect relay. 

Running capacitors burn out. 

1.- Line voltage too high. 

Head pressure to low 

1.- Insufficient refrigerant charge. 

2.- Leak in the system. 

3.- Cold location. 

Head pressure to high 

1.- Unit overcharged. 

2.- Air or other non-condensable gases in system. 

3.- Clogged condenser (air-cooled) 

4.- Defective condenser fan motor. 

5.- Unit location too hot. 

6.- Restriction in expansion valve, strainer or drier. 

7.- Discharge valve partially closed. 

8.- Restriction in discharge line. 

Summary of Contents for VBZ Ibiza

Page 1: ...VBZ Ibiza Cases GELATO DISPLAY CASES Service Installation Manual...

Page 2: ...CEDURE 7 8 OPERATION 7 8 1 Temperature control adjustment 7 8 2 Defrost control 8 8 3 Loading product 10 9 MAINTENANCE CARE AND CLEANING 10 9 1 Cleaning procedure 10 9 2 Parts and Service Error Marcad...

Page 3: ...cluding the following This refrigerator must be properly installed and located in accordance with this manual before it is used Do not allow children to climb stand or hang on the shelves in the refri...

Page 4: ...nt This unit is intended for indoor use only Be sure the location chosen for your unit must be able to provide good air circulation for most efficient refrigeration Avoid locations near heat sources s...

Page 5: ...front side or back However you must be certain to allow the unit to remain in an upright position afterwards for at least 24 hours before plugging it in so that the compressor oil and refrigerant may...

Page 6: ...e should be checked before connection to assure that proper voltage for the cabinet wiring is available To determine correct unit voltage please refer to the serial data plate located on an inner wall...

Page 7: ...ercial standards If any unusual noises are heard turn the unit off immediately and check for any obstructions of the fans All cabinets must be given enough time to reach normal operating temperature b...

Page 8: ...Menu mode it is used to look through the parameter codes or decrease the value of the variable in use This turns the light on and off Note while in the OFF status the light button is active VBZ ice c...

Page 9: ...wo defrost cycles To adjust this parameter you may follow the next instruction 1 Enter the Programming mode by pressing the SET DOWN keys for 3s the C or F LED starts blinking 2 Select the required pa...

Page 10: ...binet Do not leave food inside the unit when it is going to remain shut down either from a power outage or fault in the equipment If the cabinet is going to remain shut down for prolonged periods try...

Page 11: ...st be able to freely circulate through the condenser so the surface of the condenser must be kept free of dirt and grease for proper system operation Dirty condensers result in compressor failure and...

Page 12: ...to back up and overflow the drain pans Many operating problems are derived from causes that can be easily eliminated without the need to contact the Technical Department The following page shows a ta...

Page 13: ...ective 3 Overload protector defective 4 High head pressure 5 Fan motor pump etc wire to wrong of overload protector Compressor starts but immediately cuts out on overload 1 Starting relay contacts poi...

Page 14: ...Fixture doors left open too long 8 Insufficient defective or water logged insulation 9 Evaporated oil logged Noisy unit 1 Compressor oil charge low 2 Fan cable on condenser or evaporator bent causing...

Page 15: ...r authorization by Infrico In addition to the warranty set above Infrico warrants the hermetically and semi hermetically sealed compressor part only for an additional four 4 years based on the install...

Page 16: ...pparatus is not functioning correctly users must make the checks indicated in the manual and if the problem persists contact their distributor This certificate must be presented if it is necessary for...

Page 17: ...improper or non compliant installation of the apparatus connection voltage power supply fluctuations electrical connection not conforming to instructions etc or from manipulation of the nameplate or o...

Page 18: ...___________ Compressor No __________________________ Vendor Signature Purchaser Signature R E T U R N T O T H E M A N U F A C T U R E R User ___________________________________________________________...

Page 19: ...Infrico SL CR CO 762 Los Piedros Las Navas s n 14900 Lucena C rdoba Espa a 00 34 957 59 51 16 office 00 34 957 59 51 06 fax asistenciatecnica infrico com info infrico com www infrico com...

Reviews: