11
HB Series Desiccant Dryer Models 150-8000
ingersollrandproducts.com
9.0 TECHNICIAN MODE
Depress the SELECT DISPLAY button until the HEATER
TEMPERATURE SET POINT screen is displayed.
HEATER TEMP
375
SELECT
DISPLAY
Depressing ENTER saves the selected set point.
SET
Pressing the SET button permits the value of the HEATER
TEMPERATURE SETPOINT to be changed
HEATER TEMP
___
ENTER
Use the numbers on the keypad to enter the desired value
for the HEATER TEMPERATURE setpoint.
3
HEATER TEMP
3__
8
HEATER TEMP
38_
HEATER TEMP
380
Use the numbers on the keypad to enter the desired value
for the HEATER TEMPERATURE setpoint.
0
HEATER TEMP
380
Use the numbers on the keypad to enter the desired value
for the HEATER TEMPERATURE setpoint.
A
NOTICE
New desiccant has a moisture holding capacity higher than the dryer’s
design regeneration capacity. The desiccant ages in a three- to six-
month time period at which point it stabilizes to an "aged" state. During
this aging process at initial start-up or after desiccant replacement, the
Energy Management System feature should be deactivated.
9.5.1
ENABLING / DISABLING ENERGY MANAGEMENT
SYSTEM
The following illustrates the method of accessing and
adjusting the Energy Management System feature:
Depress the +/- button until the desired set point is displayed.
Pressing SELECT DISPLAY saves the current selection.
Depress the SELECT DISPLAY button until the ENERGY
MANAGEMENT SYSTEM screen is displayed.
EMS:
OFF
SELECT
DISPLAY
+
-
EMS:
ON
9.5.2
SETPOINT ADJUSTMENT
On dryers equipped with the optional Energy Management
System the setpoint can be adjusted to match the dryers
operation to the desired pressure dew point.
The following illustrates the method of adjusting the setpoint
for the Energy Management System feature:
The following illustrates the method of adjusting the setpoint for the
heater temperature:
9.5 ENERGY MANAGEMENT SYSTEM (OPTIONAL)
The Energy Management System option includes a dew point sensor
that transmits the outlet pressure dew point to the Microprocessor
Controller. The Microprocessor Controller displays the outlet pressure
dew point in real-time. This option package also includes Energy
Management System, an energy savings feature that matches moisture
loading and regeneration energy usage. The Energy Management
System feature utilizes the data communicated from the dew point
sensor and extends the normal timed switching sequence in proportion
to the moisture loading on the dryer.
When the Energy Management System feature is turned off, all
switching sequences occur as described in Section 7.7. When the
Energy Management System feature is activated, the drying sequence
is governed by the outlet pressure dew point as measured by the dew
point sensor. When the sampled outlet dew point registers below the
customer set point (-43°F default for -40°F dryers), an immediate
change in dryer operation will not be noticeable. The dryer will continue
its normal regeneration process through tower re-pressurization. Once
the tower is re-pressurized, both towers will be at line pressure but air
will only flow through the tower indicated by the status panel. Tower
switch over sequence is delayed until the dew point elevates above the
Energy Management System setpoint, at which point tower switch over
will occur.
To enter a negative number, depress the +/- button.
Otherwise, proceed to the next step.
Depress the SELECT DISPLAY button until the EMS SET
POINT screen is displayed.
EMS SET POINT
-43
SELECT
DISPLAY
+
-
EMS SET POINT
-___
SET
Pressing the SET button permits the value of the EMS
SETPOINT to be changed
EMS SET POINT
___
Use the numbers on the keypad to enter the desired
pressure dew point temperature for the EMS setpoint.
4
EMS SET POINT
-4__
Use the numbers on the keypad to enter the desired
pressure dew point temperature for the EMS setpoint.
1
EMS SET POINT
-41_
120.26 Dryer - Operation, Installation, Maintenance Manual, and Parts