background image

10 18-CD34D1-5-EN

INSTALLER’S GUIDE

DUCT CONNECTIONS

NOTE:  The top flanges on the furnace must be bent 90 degrees 

upward to allow connection to the ducting.

Air duct systems should be installed in accordance with standards 

for air conditioning systems, National Fire Protection Association 

Pamphlet No. 90. They should be sized in accordance with ACCA 

Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling units, 

shall be installed in parallel or on the upstream side of the cooling 

units to avoid condensation in the heating element, unless 

the  furnace  has  been  specifically  approved  for  downstream 

installation.  With  a  parallel  flow  arrangement,  the  dampers 

or other means used to control flow of air shall be adequate to 

prevent chilled air from entering the furnace, and if manually 

operated, must be equipped with means to prevent operation of 

either unit unless the damper is in full heat or cool position.

On  any  job,  flexible  connections  of  nonflammable  material 

may be used for return air and discharge connections to prevent 

transmission of vibration. Though these units have been 

specifically designed for quiet, vibration free operation, air ducts 

can act as sounding boards and could, if poorly installed, amplify 

the slightest vibration to the annoyance level.

When  the  furnace  is  located  in  a  utility  room  adjacent  to  the 

living area, the system should be carefully designed with returns 

which minimize noise transmission through the return air grille. 

Although these winter air conditioners are designed with large 

blowers operating at moderate speeds, any blower moving a 

high volume of air will produce audible noise which could be 

objectionable when the unit is located very close to a living area. 

It is often advisable to route the return air ducts under the floor 

or through the attic. Such design permits the installation of air 

return remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry air 

circulated by the furnace to areas outside the space containing the 

furnace, the return air shall also be handled by a duct(s) sealed 

to the furnace and terminating outside the space containing the 

furnace.

Minimum return air/“air entering” temperature for the 

furnace is 55° F.

Where there is no complete return duct system, the return 

connection must be run full size from the furnace to a location 

outside the utility room, basement, attic, or crawl space.

Do  not  install  return  air  through  the  back  of  the  furnace 

cabinet.

Return Air Duct Connection

All  return  air  duct  systems  should  provide  for  installation  of 

return air filters.

NOTE:  For  Upflow  5  ton  airflow  models,  if  the  airflow 

requirement exceeds 1800 CFM, these models will require 

return air openings and filters on both sides; or 1 side and 

the bottom; or just the bottom.

1.  Set the furnace in place.
2. 

For side return installations on upflow models, remove 

the insulation around the opening in the blower 

compartment.

3. 

The  side  panels  on  upflow  furnaces  include  locating 

notches which may be used as guides for cutting an 

opening for return air. Refer to Figure 11 and the outline 

drawing in this document for duct connection dimensions 

for various furnaces.

4. 

If a 3/4" flange is to be used for attaching the air inlet duct, 

add to cut where indicated by solid lines in Figure 11. Cut 

corners diagonally and bend outward to form flange.

5. 

If flanges are not required, and a filter frame is installed, 

cut along knockout guidelines.

6. 

Upflow  Furnaces:  Filter  brackets  are  available  for 

filter  use  within  the  furnace  cabints.  Order  RTR00133 

and  CLP00359.  If  bottom  return  opening  is  not  used, 

fabricate and install a sheet metal plate in the bottom of 

the furnace cabinet

UPFLOW FURNACE ONLY

*

SEE OUTLINE

DRAWING

FURNACE 

FRONT

LOCATING 
NOTCHES 
PROVIDED 
FOR SIDE 
RETURN 
CUTOUT

q

CUT 

OUT 

FOR 

SIDE 

FILTER

*

*

*

*

Downflow Furnaces: Brackets must be field supplied. Order 

BAYBRCKFLT10. Also 2 FLR01185 for 14.5" models, or 

2  FLR01186  for  17.5",  21.0"  and  24.5"  models  must  be 

ordered.

When the upflow furnace is installed in the horizontal right 

or left application and a return duct is attached to the top 

side as shown in Figure 12, the filter must be installed in a 

remote location.

Do not install the filter in the return duct directly above the 

furnace in horizontal applications.

Summary of Contents for M801P040AU24AA

Page 1: ...els only BAYFLTR200 External side filter rack BAYFLTR203 Filter kit horizontal for 17 5 cabinet BAYFLTR204 Filter kit horizontal for 21 cabinet BAYFLTR205 Filter kit horizontal for 24 5 cabinet BAYFLT...

Page 2: ...d components upon substantial completion of the construction process and verify furnace operating conditions including ignition input rate temperature rise and venting according to the manufacturer s...

Page 3: ...and bathroom exhausts so they are operating at maximum speed Do not operate a summer exhaust fan 5 Follow the lighting instructions Place the appliance be ing inspected into operation Adjust the therm...

Page 4: ...above the floor and the furnace must be located or protected to avoid physical damage from vehicles CAUTION To prevent shortening its service life the furnace should not be used as a Construction Heat...

Page 5: ...E DRAWINGS UPFLOW HORIZONTAL For the M801P Series Furnaces MODEL DIM A DIM B DIM C DIM D M801P040AU24AA M801P060AU24AA M801P060AU36AA 14 1 2 9 5 8 13 1 4 13 M801P080BU36AA M801P080BU48AA M801P100BU36A...

Page 6: ...NECTION 1 5 8 HOLE WITH PLUG 1 5 8 HOLE WITH PLUG 3 7 8 HOLE WITH PLUG ELECTRICAL CONNECTION ALTERNATE MODEL DIM A DIM B DIM C DIM D M801P060AD24AA M801P060AD36AA 14 1 2 9 5 8 13 1 4 13 M801P080BD45AA...

Page 7: ...with downflow furnaces for installation to stabilize and secure the furnace and cased coil in the horizontal position See Figure 4 IMPORTANT The cased coil must be placed downstream of the furnace In...

Page 8: ...ance with latest edition of Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 or Sections 7 2 7 3 or 7 4 of CAN CGA B149 Installation Codes and applicable provis...

Page 9: ...installations will require use of OUT DOOR AIR for combustion due to chemical exposures Commercial buildings Buildings with indoor pools Furnaces installed in commercial laundry rooms Furnaces install...

Page 10: ...taining the furnace the return air shall also be handled by a duct s sealed to the furnace and terminating outside the space containing the furnace Minimum return air air entering temperature for the...

Page 11: ...rnaceisaccessible itisrecommended that both supply and return air plenums are removable 8 When replacing a furnace old duct work should be cleaned out Thin cloths should be placed over the registers a...

Page 12: ...end tab in the slot Replace screws Remove brackets Screw locations Flanges upward TABLE 6 CABINET WIDTH RETURN DUCT WIDTH FILTER ACCESS OPENING DIMENSION A FILTER ACCESS OPENING DIMENSION B 14 1 2 13...

Page 13: ...ructions with the kit must be followed WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operatio...

Page 14: ...nder positive pressure 11 Horizontal pipe runs must be supported by hangers straps or other suitable material in intervals at a minimum of every 3 feet of pipe 12 A furnace shall not be connected to a...

Page 15: ...GRAM FOR 1 STAGE FURNACE 1 STAGE HEATING 1 STAGE COOLING USING A 1 STAGE HEATING 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER SEE NOTE 5 From drawing B342026 Rv 0 FURNACE SEE NOTE 6...

Page 16: ...l Electrical Code ANSI NFPA 70 latest edition or Canadian Electrical Code CSA C22 1 if an external electrical source is utilized All field supplied wiring must conform with the temperature limitation...

Page 17: ...ECK 1 Make sure all gas appliances are off except furnace 2 Clock the gas meter with the furnace operating determine the dial rating of the meter for one revolution 3 Match the Sec column in the gas f...

Page 18: ...screw 9 Using a leak detection solution or soap suds check for leaks at the pressure outlet boss and pressure tap test screw 10 Turn on system power and check operation of unit CAUTION Replace and or...

Page 19: ...rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude Installations above 4 000 feet may require a pressure switch change If required us...

Page 20: ...es to make sure they are within the ranges specified on the furnace rating nameplate If the airflow needs to be increased or decreased see the wiring diagram for information on changing the speed of t...

Page 21: ...or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not t...

Page 22: ...R S GUIDE The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Ingersoll Rand 11819 N Pennsylva...

Reviews: