background image

18-CD34D1-5-EN 13

 

INSTALLER’S GUIDE

VENTING INTO A MASONRY CHIMNEY

If  the  chimney  is  oversized,  the  liner  is  inadequate,  or  flue-

gas condensation is a problem in your area, consider using the 

chimney as a pathway or chase for type “B” vent or flexible vent 

liner. If flexible liner material is used, size the vent using the “B” 

vent tables, then reduce the maximum capacity by 20% (multiply 

0.80 times the maximum capacity).

Internal Masonry Chimneys

Venting of fan assisted appliances into a lined, internal masonry 

chimney is allowed only if it is common vented with at least one 

natural draft appliance; OR, if the chimney is lined with type “B”, 

double wall vent or suitable flexible liner material (See Table 7).

WARNING

!

The chimney liner must be thoroughly inspected 

to insure no cracks or other potential areas for 

flue gas leaks are present in the liner. Liner leaks 

will result in early deterioration of the chimney.
Failure to follow this warning could result in 

carbon  monoxide poisoning or death.

TABLE 7

MASONRY CHIMNEY VENTING

Tile Lined Chimney

Chimney Lining

Type Furnace

Internal

External

“B” Vent

Flexible  

Metal Liner

Single Fan  

Assist

No

No

Yes

Yes*

Fan Assist

+ Fan Assist

No

No

Yes

Yes*

Fan Assist 

+ Natural

Yes

No

Yes

Yes*

* Flexible chimney liner size is determined by using the type “B” vent size 

for the available BTUH input, then reducing the maximum capacity by 20% 

(multiply maximum capacity times 0.80). The minimum capacity is the same 

as shown in the “B” vent tables.

External Masonry Chimney

WARNING

!

CARBON MONOXIDE POISONING HAZARD
This masonry chimney kit shall NOT be installed 

on any furnaces with 40,000 BTU/H inputs or any 

downflow models. Failure to follow this warning 

could result in carbon monoxide poisoning, 

personal injury, or death.

NOTE: Masonry Chimney Kit BAYVENT800B may be used 

with  these  furnaces  (Upflow  model  furnaces  60,000  BTU/H 

and  above  only)  to  allow  venting  into  an  external  masonry 

chimney.  Refer  to  BAYVENT800B  Installer's  Guide  for 

application  requirements.  The  following  section  does  not 

apply if BAYVENT800B (Masonry Chimney Kit) is used. All 

instructions with the kit must be followed.

WARNING

!

CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for 

each appliance connected to the venting system 

being placed into operation could result in carbon 

monoxide poisoning or death.

The following steps shall be followed for each appliance 

connected to the venting system being placed into 

operation, while all other appliances connected to the 

venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and 

horizontal pitch, as required in the National Fuel Gas 

Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 

Installation Codes and these instructions.  Determine 

that there is no blockage or restriction, leakage, 

corrosion and other deficiencies which could cause 

an unsafe condition.
3. As far as practical, close all building doors and 

windows and all doors between the space in which 

the appliance(s) connected to the venting system are 

located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not 

connected to the venting system. Turn on any exhaust 

fans, such as range hoods and bathroom exhausts, 

so they are operating at maximum speed.  Do not 

operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance 

being inspected into operation. Adjust the thermostat 

so appliance is operating continuously.
7. If improper venting is observed during any of the 

above tests, the venting system must be corrected 

in accordance with the National Fuel Gas Code, 

ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 

Installation Codes.
8. After it has been determined that each appliance 

connected to the venting system properly vents where 

tested as outlined above, return doors, windows, 

exhaust fans, fireplace dampers and any other gas-

fired burning appliance to their previous conditions of 

use.

The furnace shall be connected to a factory built chimney or 

vent complying with a recognized standard, or a masonry or 

concrete chimney lined with a lining material acceptable to 

the authority having jurisdiction.

WARNING

!

Furnace venting into an unlined masonry chimney 

or concrete chimney is prohibited.
Failure to follow this warning could result in 

property damage, personal injury, or death.

Summary of Contents for M801P040AU24AA

Page 1: ...els only BAYFLTR200 External side filter rack BAYFLTR203 Filter kit horizontal for 17 5 cabinet BAYFLTR204 Filter kit horizontal for 21 cabinet BAYFLTR205 Filter kit horizontal for 24 5 cabinet BAYFLT...

Page 2: ...d components upon substantial completion of the construction process and verify furnace operating conditions including ignition input rate temperature rise and venting according to the manufacturer s...

Page 3: ...and bathroom exhausts so they are operating at maximum speed Do not operate a summer exhaust fan 5 Follow the lighting instructions Place the appliance be ing inspected into operation Adjust the therm...

Page 4: ...above the floor and the furnace must be located or protected to avoid physical damage from vehicles CAUTION To prevent shortening its service life the furnace should not be used as a Construction Heat...

Page 5: ...E DRAWINGS UPFLOW HORIZONTAL For the M801P Series Furnaces MODEL DIM A DIM B DIM C DIM D M801P040AU24AA M801P060AU24AA M801P060AU36AA 14 1 2 9 5 8 13 1 4 13 M801P080BU36AA M801P080BU48AA M801P100BU36A...

Page 6: ...NECTION 1 5 8 HOLE WITH PLUG 1 5 8 HOLE WITH PLUG 3 7 8 HOLE WITH PLUG ELECTRICAL CONNECTION ALTERNATE MODEL DIM A DIM B DIM C DIM D M801P060AD24AA M801P060AD36AA 14 1 2 9 5 8 13 1 4 13 M801P080BD45AA...

Page 7: ...with downflow furnaces for installation to stabilize and secure the furnace and cased coil in the horizontal position See Figure 4 IMPORTANT The cased coil must be placed downstream of the furnace In...

Page 8: ...ance with latest edition of Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 or Sections 7 2 7 3 or 7 4 of CAN CGA B149 Installation Codes and applicable provis...

Page 9: ...installations will require use of OUT DOOR AIR for combustion due to chemical exposures Commercial buildings Buildings with indoor pools Furnaces installed in commercial laundry rooms Furnaces install...

Page 10: ...taining the furnace the return air shall also be handled by a duct s sealed to the furnace and terminating outside the space containing the furnace Minimum return air air entering temperature for the...

Page 11: ...rnaceisaccessible itisrecommended that both supply and return air plenums are removable 8 When replacing a furnace old duct work should be cleaned out Thin cloths should be placed over the registers a...

Page 12: ...end tab in the slot Replace screws Remove brackets Screw locations Flanges upward TABLE 6 CABINET WIDTH RETURN DUCT WIDTH FILTER ACCESS OPENING DIMENSION A FILTER ACCESS OPENING DIMENSION B 14 1 2 13...

Page 13: ...ructions with the kit must be followed WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operatio...

Page 14: ...nder positive pressure 11 Horizontal pipe runs must be supported by hangers straps or other suitable material in intervals at a minimum of every 3 feet of pipe 12 A furnace shall not be connected to a...

Page 15: ...GRAM FOR 1 STAGE FURNACE 1 STAGE HEATING 1 STAGE COOLING USING A 1 STAGE HEATING 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER SEE NOTE 5 From drawing B342026 Rv 0 FURNACE SEE NOTE 6...

Page 16: ...l Electrical Code ANSI NFPA 70 latest edition or Canadian Electrical Code CSA C22 1 if an external electrical source is utilized All field supplied wiring must conform with the temperature limitation...

Page 17: ...ECK 1 Make sure all gas appliances are off except furnace 2 Clock the gas meter with the furnace operating determine the dial rating of the meter for one revolution 3 Match the Sec column in the gas f...

Page 18: ...screw 9 Using a leak detection solution or soap suds check for leaks at the pressure outlet boss and pressure tap test screw 10 Turn on system power and check operation of unit CAUTION Replace and or...

Page 19: ...rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude Installations above 4 000 feet may require a pressure switch change If required us...

Page 20: ...es to make sure they are within the ranges specified on the furnace rating nameplate If the airflow needs to be increased or decreased see the wiring diagram for information on changing the speed of t...

Page 21: ...or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not t...

Page 22: ...R S GUIDE The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Ingersoll Rand 11819 N Pennsylva...

Reviews: