background image

18-CD34D1-5-EN 17

 

INSTALLER’S GUIDE

that the pressure switch contacts are open and the limit switch(es) 

contacts are closed, the draft blower will be energized.

As  the  induced  draft  blower  comes  up  to  speed,  the  pressure 

switch contacts will close and the ignitor warm up period will 

begin. The ignitor will heat for approx. 17 seconds, then the gas 

valve is energized to permit gas flow to the burners. The flame 

sensor  confirms  that  ignition  has  been  achieved  within  the  6 

second ignition trial period.

After the flame sensor confirms that ignition has been achieved, 

the  delay  fan  ON  period  (fixed  at  45  seconds)  begins  timing. 

After the delay of 45 seconds, the indoor blower motor will be 

energized and will continue to run during the heating cycle.

When the thermostat is satisfied, R and W thermostat contacts 

open, the gas valve will close, the flames will extinguish, and the 

induced draft blower will be de-energized. The indoor blower 

motor will continue to run for the fan off period (fixed at 100 

seconds), then will be de-energized by the control module.

WARNING

!

FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could 
result in serious injury, death or property damage. 
Never test for gas leaks with an open flame. Use a 
commercially available soap solution made specifically 
for the detection of leaks to check all connections. A 
fire or explosion may result causing property damage, 
personal injury, or loss of life

START-UP AND ADJUSTMENT

Preliminary Inspections

With gas and electrical power “OFF”

1. 

Duct connections are properly sealed

2. 

Filters are in place

3.  Venting is properly assembled
4. 

Blower door is in place

Turn  knob  on  main  gas  valve  within  the  unit  to  the  “

OFF

” 

position. Turn the external gas valve to “ON”. Purge the air from 

the gas lines. After purging, check all gas connections for leaks 

with a soapy solution – 

DO NOT CHECK WITH AN OPEN 

FLAME

. Allow 5 minutes for any gas that might have escaped 

to dissipate. LP Gas, being heavier than air, may require forced 

ventilation. Turn the knob on the gas valve in the unit to the 

“ON” position.

COMBUSTION AND INPUT CHECK

1. 

Make sure all gas appliances are off except furnace.

2. 

Clock the gas meter with the furnace operating (determine 

the dial rating of the meter) for one revolution.

3. 

Match the “Sec” column in the gas flow (in cfh) Table 12 

with the time clocked.

4. 

Read  “Flow”  column  opposite  number  of  seconds 

clocked.

GAS PIPING

WARNING

!

FIRE - EXPLOSION HAZARD

DO  NOT RUN FLEXIBLE GAS LINE THROUGH THE 

FURNACE CABINET WALL. FAILURE TO FOLLOW 

THIS WARNING COULD RESULT IN PROPERTY 

DAMAGE, SERIOUS PERSONAL INJURY, OR DEATH.

This unit is shipped standard for left side installation of gas 

piping. A piping cutout is also provided in the right side for an 

alternate piping arrangement. The installation of piping shall 

be in accordance with piping codes and the regulations of the 

local gas company. Pipe joint compound must be resistant to the 

chemical reaction with liquefied petroleum gases. Refer to piping 

Table 9 for delivery sizes. 

NOTE: Refer to local codes and the National Fuel Gas Code, 

current edition, for gas pipe requirements. 

The furnace and its individual shut-off valve must be disconnected 

from the gas supply piping system during any pressure testing of 

that system at test pressures in excess of 1/2 psig.

The furnace must be isolated from the gas supply piping by 

closing its individual manual shut-off valve during any pressure 

testing of the gas supply piping system at test pressures equal to 

or less than 1/2 psig.

CAUTION

!

Use a backup wrench on the gas valve when 

installing gas piping to prevent damage to the gas 

valve and manifold assembly.

NOTE: Maximum pressure to the gas valve for natural gas 

is  13.8"  W.C.  Minimum  pressure  is  5.0"  W.C.  Maximum 

pressure to the gas valve for propane is 13.8" W.C. Minimum 

pressure is 11.0" W.C. 
All  gas  fittings  must  be  checked  for  leaks  using  a  soapy 

solution before lighting the furnace.
DO NOT CHECK WITH AN OPEN FLAME!

The following warning complies with the State of California law, Proposition 65.

WARNING

!

HAZARDOUS GASES!
EXPOSURE TO FUEL SUBSTANCES OR BY 

PRODUCTS OF INCOMPLETE FUEL COMBUSTION 

IS BELIEVED BY THE STATE OF CALIFORNIA TO 

CAUSE CANCER, BIRTH DEFECTS, OR OTHER 

REPRODUCTIVE HARM.

SEQUENCE OF OPERATION

Thermostat call for heat

R and W thermostat contacts close signaling the control module 

to run its self-check routine. After the control module has verified 

Summary of Contents for M801P040AU24AA

Page 1: ...els only BAYFLTR200 External side filter rack BAYFLTR203 Filter kit horizontal for 17 5 cabinet BAYFLTR204 Filter kit horizontal for 21 cabinet BAYFLTR205 Filter kit horizontal for 24 5 cabinet BAYFLT...

Page 2: ...d components upon substantial completion of the construction process and verify furnace operating conditions including ignition input rate temperature rise and venting according to the manufacturer s...

Page 3: ...and bathroom exhausts so they are operating at maximum speed Do not operate a summer exhaust fan 5 Follow the lighting instructions Place the appliance be ing inspected into operation Adjust the therm...

Page 4: ...above the floor and the furnace must be located or protected to avoid physical damage from vehicles CAUTION To prevent shortening its service life the furnace should not be used as a Construction Heat...

Page 5: ...E DRAWINGS UPFLOW HORIZONTAL For the M801P Series Furnaces MODEL DIM A DIM B DIM C DIM D M801P040AU24AA M801P060AU24AA M801P060AU36AA 14 1 2 9 5 8 13 1 4 13 M801P080BU36AA M801P080BU48AA M801P100BU36A...

Page 6: ...NECTION 1 5 8 HOLE WITH PLUG 1 5 8 HOLE WITH PLUG 3 7 8 HOLE WITH PLUG ELECTRICAL CONNECTION ALTERNATE MODEL DIM A DIM B DIM C DIM D M801P060AD24AA M801P060AD36AA 14 1 2 9 5 8 13 1 4 13 M801P080BD45AA...

Page 7: ...with downflow furnaces for installation to stabilize and secure the furnace and cased coil in the horizontal position See Figure 4 IMPORTANT The cased coil must be placed downstream of the furnace In...

Page 8: ...ance with latest edition of Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 or Sections 7 2 7 3 or 7 4 of CAN CGA B149 Installation Codes and applicable provis...

Page 9: ...installations will require use of OUT DOOR AIR for combustion due to chemical exposures Commercial buildings Buildings with indoor pools Furnaces installed in commercial laundry rooms Furnaces install...

Page 10: ...taining the furnace the return air shall also be handled by a duct s sealed to the furnace and terminating outside the space containing the furnace Minimum return air air entering temperature for the...

Page 11: ...rnaceisaccessible itisrecommended that both supply and return air plenums are removable 8 When replacing a furnace old duct work should be cleaned out Thin cloths should be placed over the registers a...

Page 12: ...end tab in the slot Replace screws Remove brackets Screw locations Flanges upward TABLE 6 CABINET WIDTH RETURN DUCT WIDTH FILTER ACCESS OPENING DIMENSION A FILTER ACCESS OPENING DIMENSION B 14 1 2 13...

Page 13: ...ructions with the kit must be followed WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operatio...

Page 14: ...nder positive pressure 11 Horizontal pipe runs must be supported by hangers straps or other suitable material in intervals at a minimum of every 3 feet of pipe 12 A furnace shall not be connected to a...

Page 15: ...GRAM FOR 1 STAGE FURNACE 1 STAGE HEATING 1 STAGE COOLING USING A 1 STAGE HEATING 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER SEE NOTE 5 From drawing B342026 Rv 0 FURNACE SEE NOTE 6...

Page 16: ...l Electrical Code ANSI NFPA 70 latest edition or Canadian Electrical Code CSA C22 1 if an external electrical source is utilized All field supplied wiring must conform with the temperature limitation...

Page 17: ...ECK 1 Make sure all gas appliances are off except furnace 2 Clock the gas meter with the furnace operating determine the dial rating of the meter for one revolution 3 Match the Sec column in the gas f...

Page 18: ...screw 9 Using a leak detection solution or soap suds check for leaks at the pressure outlet boss and pressure tap test screw 10 Turn on system power and check operation of unit CAUTION Replace and or...

Page 19: ...rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude Installations above 4 000 feet may require a pressure switch change If required us...

Page 20: ...es to make sure they are within the ranges specified on the furnace rating nameplate If the airflow needs to be increased or decreased see the wiring diagram for information on changing the speed of t...

Page 21: ...or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not t...

Page 22: ...R S GUIDE The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Ingersoll Rand 11819 N Pennsylva...

Reviews: