INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Flashing Slow
Normal - No call for Heat
Flashing Fast
Normal - Call for Heat
Continuous ON
Replace IFC
Continuous OFF
Check Power
2 Flashes
System Lockout (Retries or Recycles
exceeded)
3 Flashes
Draft Pressure Error - Possible problems
a) Venting problem
b) Pressure switch problem
c) Inducer problem
4 Flashes
Open High Limit Device
5 Flashes
Flame sensed when no flame should be
present
6 Flashes
115 Volt AC power reversed or Poor
Grounding
7 Flashes
Gas valve circuit error
8 Flashes
Low flame sense signal
9 Flashes
Check Ignitor circuit and Line "N" to
24VAC "Common" voltage (< 2volts)
(possible grounding problem)
ABNORMAL CONDITIONS
IFC ERROR FLASH CODE