background image

18-CD37D1-2-EN  

43

Installer’s Guide

INSTRUCTIONS TO THE OWNERS

WARNING

!

EXPLOSION HAZARD

IN THE EVENT THAT ELECTRICAL, FUEL OR 
MECHANICAL FAILURES OCCUR, SHUT OFF THE 
GAS SUPPLY AT THE MANUAL GAS SHUT OFF VALVE, 
LOCATED ON THE SUPPLY GAS PIPING COMING 
INTO THE FURNACE, BEFORE TURNING OFF THE 
ELECTRICAL POWER TO THE FURNACE. CONTACT 
SERVICER.
FAILURE TO FOLLOW THIS WARNING COULD RESULT 
IN PROPERTY DAMAGE, PERSONAL INJURY OR 
DEATH.

BURNER BOX TEMPERATURE LIMIT DEVICE

All models are equipped with a manual reset temperature limit 

located on the Burner Box. In case of excessive temperature, 

the limit will open and cause the circuit to open which shuts off 

all flow of gas.

CONDITIONS THAT AFFECT SYSTEM 
OPERATION

  1.  EXCESSIVE COMBUSTION PRESSURE (WIND IN 

EXCESS OF 40 M.P.H.) VENT OR FLUE BLOCKAGE

    On a call for heat, the Variable Speed Draft Inducer must 

first ramp up to speed and close the Pressure Switch 
before the ignition sequence is allowed to begin. If the 
Pressure Switch does not close, the motor will ramp up to 
maximum speed and continue to operate there for about 
1 minute.

    After one minute, the Integrated Furnace Control will turn 

the motor off for about 30 seconds and then back on in 
an attempt to reestablish proper operation. This condition 
is indicative of a highly restricted or blocked inlet or outlet 
vent pipe or a failed Pressure Switch.

    If pressure against induced draft blower outlet becomes 

excessive, the Pressure Switch will open. If the Pressure 
Switch is open for more than 3.5 seconds, the variable 
speed draft inducer will speed up and attempt to close 
the Pressure Switch. If the Pressure Switch is not closed 
within 12 seconds or if the maximum speed of the motor 
is reached, the draft inducer sends a Fault signal to the 
Integrated Furnace Control. If the unit is operating in 
Second Stage, an Inducer Fault will cause the Furnace 
Control to transition the system to First Stage and it will 
operate there for 10 minutes before attempting to run 
again in Second Stage. If the unit is operating in First 
Stage, an Inducer Fault will cause the Furnace Control 
to shut the system down and wait 30 seconds before 
attempting to reestablish operation in First Stage.

  2.  LOSS OF FLAME
    If loss of flame occurs during a heating cycle, or flame is 

not present at the sensor, the flame control module will 
close the Gas Valve. The Integrated Furnace Control will 
then recycle the ignition sequence, then if ignition is not 
achieved, it will shut off the Gas Valve and lock out the 
system.

  3.  POWER FAILURE
    If there is a power failure during a heating cycle, the 

system will restart the ignition sequence automatically 
when power is restored, if the Comfort Control still calls 

for heat.

  4.  GAS SUPPLY FAILURE
    If loss of flame occurs during a heating cycle, the 

system Integrated Control Module will recycle the ignition 
sequence, then if ignition is not achieved, the Integrated 
Control Module will shut off the Gas Valve and lock out the 
system.

  5.  INDUCED DRAFT BLOWER FAILURE
    Please refer to the Variable Speed Draft Inducer 

troubleshooting manual for diagnostic assistance.

  6.  CONDENSATE DRAIN BLOCKAGE
    If the condensate drain is blocked, either by debris, 

improper draining, or by freezing condensate, the 
pressure switch will receive a signal warning of the 
accumulation of condensate in the heat exchanger 
assembly. The pressure switch contacts will open and 
remain open, not allowing unit operation. The unit will not 
operate until the condensate drain has been cleared, and 
the condensate flows freely.

  7.  RESET AFTER LOCKOUT
    When the Integrated Furnace Control has shut the system 

down and gone into lockout, the system must be manually 
reset before the unit will restart. The system can be reset 
by turning the system power off for more than 1 second, 
or by removing 24VAC from the control for more than 1 
second, or by removing the Comfort Control call for heat 
for more than 1 second but less than 20 seconds.

  8.  RESET AFTER BURNER BOX LIMIT SHUTDOWN
    If the furnace shuts down, one thing that can be checked 

is the burner box temperature limit switch. It is located on 
the bottom of the burner box. The vent and combustion 
air inlet terminations should be checked for blockage. 
If blockage exists, clear the problem and then the reset 
button may be depressed. 

If there is no blockage of 

the terminations, the limit switch must be reset by a 
qualified servicer.

INDOOR MOTOR MAINTENANCE 

Direct drive motors have bearings which are permanently 
lubricated and under normal use, lubrication is not 
recommended.

Summary of Contents for M952V060BD36AA

Page 1: ...ble filter for 17 5 cabinet upflow only BAYFLTR321 Cleanable filter for 21 cabinet upflow only BAYFLTR324 Cleanable filter for 24 5 cabinet upflow only BAYLPKT210B Propane conversion kit BAYLPSS210B L...

Page 2: ...llow safety warnings exactly could result in a fire or explosion causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicin...

Page 3: ...rritation PRECAUTIONARY MEASURES Avoid breathing fiberglass dust Use a NIOSH approved dust mist respirator Avoid contact with the skin or eyes Wear long sleeved loose fitting clothing gloves and eye p...

Page 4: ...to check all connections as specified in the Gas Piping section of these instructions on page 31 6 Always install the Furnace to operate within the Furnace s intended temperature rise range with a duc...

Page 5: ...STALL THE FURNACE DI RECTLY ON CARPETING TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING CAUTION Do NOT install the Furnace in a corrosive or contaminated atmosphere Failure to follow this...

Page 6: ...7 1 2 2 M952V100CU48A 21 2 1 2 19 3 4 19 1 2 9 3 M952V120DU60A 24 1 2 2 15 16 23 1 4 23 10 3 SUFFIX LETTER MAY BE A Z NOTES 1 M952V120DU60AA REQUIRES 3 DIAMETER PIPE M952V100CU48AA REQUIRES 2 1 2 OR...

Page 7: ...de Figure 3 Downflow Outline Drawing MODEL SEE NOTE 1 2 DIM A DIM B DIM C DIM D M952V060BD36A M952V080BD36A 17 1 2 2 1 4 16 1 4 16 M952V100CD48A 21 2 1 2 19 3 4 19 1 2 M952V120DD60A 24 1 2 2 15 16 23...

Page 8: ...e in the horizontal position by placing the Furnace on the left side as viewed from the front in the vertical position The horizontal Furnace installation in an attic should be on a service platform l...

Page 9: ...meets the criteria for an unconfined space The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination Refer to Table 4 for minimu...

Page 10: ...high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area It is often advisable to route the return air ducts under the floor or t...

Page 11: ...furnace must be removed for bottom return air After removing the filter lay the fur nace on its back Remove the two 5 16 hex screws secur ing the front of the bottom channel to the cabinet Rotate the...

Page 12: ...17 e Reinstall the furnace filter in the bottom position by inserting the chamfer end first into the filter rack ALTERNATE FILTER RACK INSTALLATION FOR SIDE RETURN AIR ON UPFLOW FURNACES Left or Right...

Page 13: ...or Return Filter Rack Installation With Side Furnace Cabinet Side Figure 19 CHAMFER END OF FILTER GOES INTO FILTER RACK FIRST Airflow Figure 22 Typical Horizontal Filter Installation Figure 23 BOTTOM...

Page 14: ...ples for location of the furnace clips Side return only Pre drill clearance holes with a 3 16 drill Bottom return holes are pre drilled 2 Install the clips in front and rear of the desired location us...

Page 15: ...obtain maximum efficiency from a condensing Furnace Proper installation of the vent system is necessary to assure drainage of the condensate and prevent deterioration of the vent system American Gas A...

Page 16: ...le pressure zone applications see Figure 30 The following are EXAMPLES ONLY EX 1 Example 1 shows that the vent may go vertical while the inlet air may be on any side of the structure The vent pipe wou...

Page 17: ...e the pipes to be removed later without cutting Be sure to properly support these joints Commercially available solvent cement for PVC must be used to join PVC pipe fittings Follow instructions on con...

Page 18: ...ULAR CORE 3 180 ASTM F628 DuraVent PolyPro 45 ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING NA NA 230 ULC S636 1 Allowable temperatures based on classifications covered in ASTM D4396 Deflectio...

Page 19: ...LENGTHS 2 Minimum vent length for all models 3 horizontal or 3 vertical 3 DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET Except adapters at the top of the furnace If...

Page 20: ...g NOTE Vent termination kit BAYAIR30AVENTA or BAYVENT200B may be used in addition to the horizontal and vertical termination options shown in the following figures For Canadian applications venting sy...

Page 21: ...licensed professionals for the installation of hard wired carbon monoxide detectors HORIZONTAL VENTING THROUGH WALL These Furnaces may be installed as direct vent as shipped or as nondirect vent Inst...

Page 22: ...hall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be ins...

Page 23: ...RTV SILICONE SEALANT CLEARANCE 0 ACCEPTABLE FOR PVC VENT PIPE 1 ACCEPTABLE FOR TYPE 29 4C STAINLESS STEEL VENT PIPE Figure 39 MAINTAIN 12 IN 18 IN FOR CANADA MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPAT...

Page 24: ...o the building Figure 40 TYPE 29 4C STAINLESS STEEL VENTING THROUGH UNUSED CHIMNEY Figure 41 VENTING ROUTED THROUGH A MASONRY CHIMNEY PVC PLASTIC VENTING THROUGH UNUSED CHIMNEY SUPPORT THE SINGLE WALL...

Page 25: ...a height 15 feet 4 5 m above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm J Clearance to nonmechanical air supply inlet to build ing or the combustion air inl...

Page 26: ...6 feet 1 83m 3 feet 91 cm above if within 10 feet 3m horizontally L Clearance above a paved sidewalk or paved driveway located on public property 7 feet 2 13 m M Clearance under veranda porch deck or...

Page 27: ...onnections by turning the trap and extending the tubing to the lower right front corner of the Furnace Trim all excess tubing to avoid kinking The connecting tubing for left or right side condensate d...

Page 28: ...ain tube at the header Evaporator and Furnace condensate drain piping may be manifolded together as shown in Figure 46 A primary drain vent stack must be installed and terminated below the outlet of t...

Page 29: ...from the trap to the side of the unit and trim all excess tubing to avoid kinks Downflow furnace Use RTV silicon sealant to connect the fitting to the trap for ease of removal when cleaning the trap F...

Page 30: ...causing slippery conditions that could lead to personal injury Excessive draining of conden sate may cause saturated ground conditions that may result in damage to plants NOTE Use 1 2 or larger PVC or...

Page 31: ...UTOMATIC GAS VALVE WITH MANUAL SHUT OFF GROUND UNION JOINT DRIP LEG Figure 55 THE DOWNFLOW VERTICAL MAY BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING GROUND UNION JOINT AUTOMATIC GAS VALVE WITH MANU AL S...

Page 32: ...und joint union and a manual shut off valve as shown in Figures 43 44 National codes require a condensation drip leg to be installed ahead of the controls as shown in Figures 55 56 The furnace and its...

Page 33: ...unit is derated for high altitude d Replace and tighten the regulator cover screw securely 7 Cycle the valve several times to verify regulator setting a Repeat steps 5 7 if needed 8 Turn off all elec...

Page 34: ...he burner box The burner box pressure tap equalizes the gas valve pressure regulator Manifold pressure is checked by installing a tee field supplied in the tubing between the tee coming from the burne...

Page 35: ...r leaks with a soapy solution DO NOT CHECK WITH AN OPEN FLAME Allow 5 minutes for any gas that might have escaped to dissipate LP Gas being heavier than air may require forced ventilation Turn the tog...

Page 36: ...h 6 When a single stage heating thermostat without fan switch is used no wiring on G terminal is used 7 W1 and W2 must be jumpered together for proper operation Second stage heat will begin based on I...

Page 37: ...off delays 9 Optional humidistat is to be connected between R and BK Factory installed jumper R to BK on the circuit board must be cut if optional humidistat is used The jumper must also be cut when...

Page 38: ...B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SEE NOTE 5 FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE 1 STAGE HEATING 1 STAGE COOLING USING A 1 STAGE HEATING 1 ST...

Page 39: ...JUMPER SEE NOTE 9 From Dwg B342020 Rev 0 B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SEE NOTE 5 FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE 2 STAGE HEATING...

Page 40: ...nd multi zone system controller On single speed cooling only non heat pump systems jumper Y to O for proper operation of the delay profiles and the Humidistat For two compressor or two speed systems j...

Page 41: ...stment Preliminary Inspections WARNING ELECTRIC SHOCK HAZARD DISCONNECT POWER TO THE UNIT BEFORE REMOV ING THE BLOWER DOOR ALLOW A MINIMUM OF 10 SECONDS FOR IFC POWER SUPPLY TO DISCHARGE TO 0 VOLTS FA...

Page 42: ...et at 60 100 140 or 180 seconds The factory setting is 100 seconds See unit wiring diagram Cooling The fan delay off period is set by dip switches on the Integrated Furnace Control The options for coo...

Page 43: ...tablish operation in First Stage 2 LOSS OF FLAME If loss of flame occurs during a heating cycle or flame is not present at the sensor the flame control module will close the Gas Valve The Integrated F...

Page 44: ...o call for Heat Flashing Fast Normal Call for Heat Fault Code Reset The last 4 fault codes can be erased from memory by powering up the control with G energized and then applying R to the W1 terminal...

Reviews: