CONFIGURATION TABLE 

Parameter  Description 

Length 

(Bytes) 

R/W 

Default 

Value 

Valid Values 

Time between Battery Reports (hours) 

R/W 

Range: 1

–127 hours 

0 = Do not send periodically 

Send BASIC SET ON above this temperature  
(See #20) 

R/W 

121 

Range: 15° 

– 120° F 

121 = Disabled 

Send BASIC SET ON below this temperature  
(See #20) 

R/W 

121 

Range: 15° 

– 120° F 

121 = Disabled 

Send BASIC SET OFF above this temperature  
(See #20) 

R/W 

121 

Range: 15° 

– 120° F 

121 = Disabled 

Send BASIC SET OFF below this temperature  
(See #20) 

R/W 

121 

Range: 15° 

– 120° F 

121 = Disabled 

Send multiple attempts for all BASIC SET 
commands 

R/W 

1-5 = Number of extra attempts sent 
every minute after first send 
0 = Disabled 

Temperature Units 

R/W 

1 = Fahrenheit 
0 = Celsius 

Association Group1 

– Temperature delta auto 

send threshold 

R/W 

10 

Range: 1 - 200 
Parameter is in tenths of degrees.  

Association Group1 

– Periodic temperature 

send interval  

R/W 

Range: 1-120 minutes 
0 = Disabled 

10 

Association Group2 

– Temperature delta auto 

send threshold  

R/W 

10 

Range: 1 - 50  
0 = Disabled 
Parameter is in tenths of degrees. 

11 

Association Group2 

– Periodic temperature 

send interval  

R/W 

Range: 1-120 minutes 
0 = Disabled 

12 

Send BASIC SET ON above this humidity   
(See #20) 

R/W 

Range: 1

–100% 

0 = Disabled 

13 

Send BASIC SET ON below this  humidity  
(See #20) 

R/W 

Range: 1-100% 
0 = Disabled 

14 

Send BASIC SET OFF above this  humidity  
(See #20) 

R/W 

Range: 1-100% 
0 = Disabled 

15 

Send BASIC SET OFF below this  humidity  
(See #20) 

R/W 

Range: 1-100% 
0 = Disabled 

16 

Association Group1 

– Humidity delta auto send 

threshold 

R/W 

1-50% 

17 

Association Group1 

– Periodic humidity send 

interval 

R/W 

Range: 1-120 minutes 
0 = Disabled 

18 

Association Group3 

– Humidity delta auto send 

threshold 

R/W 

Range: 1-30% 
0 = Disabled 

19 

Association Group3 

– Periodic humidity send 

interval 

R/W 

Range: 1-120 minutes 
0 = Disabled 

20 

BASIC SET options for temperature and 
humidity 

R/W 

Configuration Register Combinations: 
1 = Enable Registers 2, 5, 12 15 
2 = Enable Registers 2, 5, 13, 14 
3 = Enable Registers 3, 4, 12, 15 
4 = Enable Registers 3, 4, 13, 14 

21 

Temperature Offset 

R/W 

Range: -7° to 7° F 

22 

Humidity Offset 

R/W 

Range: -7% to 7% 

23 

Humidity Filter Time Constant 

R/W 

30 

Range: 1 

– 60 minutes 

 

© 2017 Ingersoll Rand 
Rev. 20170629 

These instructions are ONLY for connecting a Z-Wave wireless temper-
ature sensor to a new or existing Z-Wave network.  This sensor 
CANNOT be used as a remote temperature sensor for an 824, 850 or 
1050 comfort control.

 

 