background image

 

23

 

Input/Output and Alarm Information for 

Intellisys S3 Controller 

 

1.0 

Hardware Input / Output Information

 

Each I/O and software function is labeled as 

STD

 where the function is available in the standard 

controller (

R

apidly 

D

eveloping 

E

conomies) and 

ENH

 where the function is available in the enhanced 

controller (

RDE

 – Options and Developed Markets). 

           

1.1   

Analog Inputs

 - 10 bit resolution. .5% Full scale accuracy. Pressure Transducer, 2 Wire, 4-

20 ma, Loop Powered. 
 

Sensor        Range              Description                                   Control        Term 

STD

    4APT          0-232 Psi          Package Discharge                     X05               1-2 

ENH

   3APT          0-232 Psi          Sump, Wet Side                           X05               5-6

 

  

Temperature, 2 Wire, 10 K ohm Thermistor, see appendix 1 for Resistance table! 

 

Sensor          Range             Description                                    Control         Term 

STD

  2ATT           -34 to 124 °C  (255 F)  Air end Discharge                X05               3-4

 

 
1.2  

Analog Output

 - 0-20ma, 24Vdc, max load 500 Ohms, .020ma resolution, 

 

Output              Description                                                        Control         Term 

STD

 #1                     PORO Horn (Using Solid State Relay)                 X06                1-2

 

 

 
 
Analog Inputs Comments

 

STD

 Pressure Input Calibration - Initiates an automatic

 

calibration routine for reading and 

correcting the pressure

 

transducer inputs with a known zero Psi input.

 

A zero offset calibration should 

be performed by first the user verifying the pressure applied to the pressure transducer is in fact 0 
PSI. Initiating this calibration routine will read and store a new zero offset value for the analog inputs. 
This value is used as an offset for all future pressure readings. The display (UI) should indicate to the 
user that a zero Psi reading has been successfully made and stored for the new zero PSI offset value 
by displaying a successful message or icon. If when reading the analog input for the 0 PSI value, the 
actual reading is greater than +/- 10% of the scale, the calibration will not be performed for that 
particular sensor and the previous pressure offset value will be retained. A Sensor Calibration Failure 
will be displayed indicating which input has failed and also adding an entry into the Alarm Log. If the 
Developed Markets features are enabled, the Sump Pressure transducer will be present and should 
be calibrated along with the Package Discharge Pressure transducer. Span calibration is not 
accessible by the customer. The calibration is done through the advanced set up menu as shown in 
the flow chart on page 6.  

 

 
 
 
 
 

Summary of Contents for R110IU-10

Page 1: ...Fault Finding Guide for the R90 160 IU More than Air Answers Online answers http www air irco com PHONE 1 800 820 0308 WSV June 07...

Page 2: ...system Close and lock all access doors when the compressor is left unattended Do not use extinguishers intended for Class A or Class B fires on electrical fires Use only extinguishers suitable for cl...

Page 3: ...e Intellisys S3 Controller 23 25 Analog Inputs Outputs Information and Comments Digital Inputs Outputs 12 S3 Intellisys Controller Serial Communications Information 26 13 Eiger Maintenance Intervals 2...

Page 4: ...vices This controller is different than other Intellisys controllers in that the relay outputs are not solid state triacs they are relays that are turned on an off by an internal 24 VDC power supply c...

Page 5: ...5 S3 Intellisys Controller Operating Instructions...

Page 6: ...6 Software Navigation...

Page 7: ...7 Eiger Controller Fault Indicators 020 Tr Motor PTC Open High Motor Temperature...

Page 8: ...Controller has no power to relay outputs This controller has no provision to detect a power loss to the relay outputs Reset controller Insufficient Coolant Circulation insufficient cooling Compressor...

Page 9: ...and check that the air end and motor rotate freely Check the separator element for excessive pressure drop Set the motor overload on star delta at 67 FLA SF of motor name plate data tag Measure curre...

Page 10: ...MPV stuck open Strip the MPV examine and repair if necessary Compressor will not load Inlet valve not opening Check that the valve is free to open Check the operation of the load solenoid valve 1SV C...

Page 11: ...Stop Fault T 2 Incoming power wired to package incorrectly Clear fault hazard twist emergency stop button to reset Compressor will not start below 2 deg C 28 deg F unless fitted with low ambient opti...

Page 12: ...valve and make sure it operates freely Check load solenoid valve and controller operation P1 Sensor calibration failure Fault T 10 Check sensor connection and calibrate or replace if necessary P1 Sens...

Page 13: ...wiring Maintenance due immediately Fault W 15 Maintenance timer has reached 2000 hrs of runtime or 8760 hours clock time Reset time in factory set up menu using access code 1954 Change oil filter Faul...

Page 14: ...14 Star Delta Wiring Diagram...

Page 15: ...15...

Page 16: ...16 Soft Start Wiring Diagram...

Page 17: ...17...

Page 18: ...18 Line Start Schematic...

Page 19: ...19...

Page 20: ...20 Process and Instrumentation Diagram...

Page 21: ...21...

Page 22: ...the discharge air and passing it through the separator much of the water vapor which is naturally present in the air can be removed The coolant system consists of a sump cooler thermostatic valve and...

Page 23: ...he pressure transducer inputs with a known zero Psi input A zero offset calibration should be performed by first the user verifying the pressure applied to the pressure transducer is in fact 0 PSI Ini...

Page 24: ...ck KM3 2 from the 1S KM3 contactor keeps the 2M KM2 contactor from energizing anytime the 1S KM3 contactor is energized Electrical interlocks are wired such that when the 1S KM3 output is de energized...

Page 25: ...c Condensate Interval Time Default 180 Sec Minimum 90 Sec Maximum 300 Sec ENH Modulation The modulation output is used to turn on the modulation solenoid valve anytime the modulation set point is turn...

Page 26: ...e of servicing communications at least twice per second Any serial communications intended for this slave device must be responded to within 500 milliseconds ENH Serial Control Starting the compressor...

Page 27: ...set STD Maintenance Indicator How to display time to maintenance the maintenance timer will display the maintenance timer value in hours and in percentage 2000 or 8760 closest to reaching its respecti...

Page 28: ...28 Maintenance...

Page 29: ...29 Maintenance...

Page 30: ...30 Maintenance...

Page 31: ...31 S3 Controller Input Output Overview AI Analog Input DI Digital Input DO Digital Output...

Page 32: ...less than 2 C The compressor will be in an alarm state and not start if the temperature is below 2 C The compressor will start if the temperature is above 2 C This is only active if Low Ambient LA op...

Page 33: ...er Interface Buttons The 8 buttons located on the controller are to be a raised membrane button used to activate the membrane switch The icon and button oval are not raised Fault Symbols LED Indicator...

Page 34: ...eft on all the time as long as this does not significantly reduce the life of the backlight Icons in the standard LCD display Shutdown in Auto Restart Pressure Control Power Out Restart Active PORO Sc...

Page 35: ...machine operational or fault status will be continuously displayed for all Status displays Compressor Running Unloaded Manual Unloaded Compressor Running and Loaded Flash Icon when the compressor is U...

Page 36: ...etup displays Satus screen Data in Yellow will only be displayed is ENH Default Ae 0 0 0 0 C Airend Discharge Temp 1 Ip 0 0 0 0 PSI Sump Pressure 2 DL 0 0 0 0 PSI Delta pressure DL will not be display...

Page 37: ...0 Pass Code If no buttons are pressed within 30 seconds the display will revert back to the default Status display item Un 0 0 0 0 PSI Unload Pressure Ld 0 0 0 0 PSI Load Pressure As 0 0 0 0 SEC Unloa...

Page 38: ...h for each Trip Fc _ 0 0 1 _ _ _ Fault Code Pd _ _ 6 5 PSI Package Discharge Pressure Ae 2 2 1 0 F Airend Discharge Temperature Rn _ _ _ _ 1 2 3 Run Hours Sp _ _ 6 9PSI Sump Pressure Dt 1 0 3 0 _06 Da...

Page 39: ...Stop Time Po off PORO on off Pt 0 0 1 0 SEC PORO Time Lt 0 0 2 0 SEC Low Ambient Load Delay Time RC 0 0 0 0 _ Remote Control Selection Is _ _ _ _ OFF Integral sequencing Cn 0 0 0 1 Multi 485 Compresso...

Page 40: ...Trips Red Trip LED on solid green LED off When a trip or warning is detected by the controller the following codes and icons should be displayed on the bottom line of the LCD display T Indicates Trip...

Page 41: ...al Requirements All units shall be designed such that the package can operate continuously in ambient temperatures between 35 F 2 C and 115 F 46 C with non condensing humidity from 0 95 from the front...

Page 42: ...nit was running or stopped in auto start stop when power was lost If it is determined this was the case it will start the PORO sequence The control will energize the PORO horn and start a count down o...

Page 43: ...nts which have relatively high constant air demand relative to the compressor capacity the recommended control mode is modulation The modulation control system retains the features of the on line off...

Page 44: ...e main power disconnect switch in the ON position 5 Open the isolation valve and start the compressor 6 Adjust the isolation valve to bring the discharge air pressure to the rated discharge pressure 1...

Page 45: ...45 Standard S3 Menu Structure and Parameters Table 12...

Page 46: ...46 Standard S3 Menu Structure and Parameters Table 12...

Page 47: ...47 Standard S3 Menu Structure and Parameters Table 12...

Page 48: ...48 Standard S3 Menu Structure and Parameters Td Air Temp High Level Trip Fixed Value 109 C 109 C 109 109 Table 13...

Page 49: ...49 Modbus Register Listing...

Page 50: ...50 Table 13 Modbus Register Listing...

Page 51: ...51 Here is a list of trip codes that are very handy to carry with you on a service call Motor PTC Open High Motor Temperature...

Page 52: ...52 Appendix 1 Thermistor 2ATT 34 to 124 C 255 F Air end Discharge...

Page 53: ...53...

Page 54: ...54...

Page 55: ...55...

Page 56: ...56...

Page 57: ...57...

Page 58: ...58 General Specifications for Eiger Packages...

Page 59: ...59...

Page 60: ...60...

Page 61: ...61...

Page 62: ...62...

Page 63: ...63...

Page 64: ...64...

Page 65: ...65...

Page 66: ...66...

Page 67: ...67...

Page 68: ...68...

Page 69: ...69...

Page 70: ...70...

Page 71: ...71...

Page 72: ...72...

Page 73: ...73...

Page 74: ...74...

Page 75: ...75...

Page 76: ...76...

Page 77: ...77...

Page 78: ...78...

Page 79: ...79...

Reviews: