58
S9V2-SF-2A-EN
11 Fault Code
Defini"on
The IFC has detected that internal gas valve relays have failed
OR 24 VAC is being sensed at 2
nd
stage gas valve
Is 24 VAC nominal voltage present
between Brown lead at gas valve
connec"on to chassis ground?
Remove any hea"ng
call
Correct wiring
Check opera"on
YES
Replace IFC
NO
12 Fault Code
Defini"on:
The onboard 5 amp fuse is open or missing.
Apply power to the
unit
Is 24 VAC
measured across
the fuse terminals?
Replace fuse
YES
Is fuse fully
seated into
connector?
NO
Properly seat the
fuse
NO
Replace IFC
YES
Start unit and measure amp
draw on transformer 24VAC red
wire (accessories turned OFF)
Is amp draw less
than 5 amps?
Correct low voltage wiring
Possible Causes
Field wiring shorted
Unit wiring shorted
Turn on each accessory (if
installed) and measure amp
draw. If amp draw exceeds
fuse ra"ng, correct wiring
associated with that accessory
NO
YES