TAM7-SF-2E-EN
17
TAM7B0C60
AIRFLOW
PERFORMANCE
CONSTANT
CFM
MODE
/
CONSTANT
TORQUE
MODE
OUTDOOR
MUL
TIPLIER
(T
ONS)
COOLING
AIRFLOW
SET
TING
AIRFLOW
POWER
EXTERNAL
ST
A
TIC
PRESSURE
(Constant
CFM
/
Constant
T
orque)
HEA
TING
AIRFLOW
SET
TING
AIRFLOW
POWER
EXTERNAL
ST
A
TIC
PRESSURE
0.1
0.3
0.5
0.7
0.9
0.1
0.3
0.5
0.7
0.9
3.5
tons
370
CFM/ton
CFM
W
atts
1316
/
1404
194
/
201
1328
/
1330
258
/
234
1328
/
1244
314
/
260
1320
/
1146
364
/
276
1308
/
1033
406
/
280
400
CFM/ton
CFM
W
atts
1404
205
1424
275
1426
337
1419
391
1410
440
380
CFM/ton
CFM
W
atts
1349
/
1435
207
/
213
1360
/
1362
272
/
247
1359
/
1278
329
/
273
1352
/
1183
380
/
290
1338
/
1074
422
/
295
410
CFM/ton
CFM
W
atts
1437
218
1455
289
1457
351
1451
407
1441
456
390
CFM/ton
CFM
W
atts
1381
/
1466
220
/
225
1391
/
1394
286
/
260
1390
/
1312
344
/
287
1383
/
1220
396
/
304
1370
/
1115
439
/
310
420
CFM/ton
CFM
W
atts
1467
230
1487
303
1489
367
1482
423
1474
474
400
CFM/ton
CFM
W
atts
1413
/
1496
234
/
238
1422
/
1426
300
/
273
1421
/
1346
360
/
301
1415
/
1256
412
/
319
1402
/
1154
456
/
325
430
CFM/ton
CFM
W
atts
1500
244
1516
317
1519
382
1515
441
1505
491
4
tons
370
CFM/ton
CFM
W
atts
1485
/
1583
269
/
278
1493
/
1516
337
/
314
1493
/
1441
398
/
342
1486
/
1357
452
/
362
1475
/
1263
498
/
370
400
CFM/ton
CFM
W
atts
1586
285
1600
360
1604
428
1601
490
1592
543
380
CFM/ton
CFM
W
atts
1521
/
1618
287
/
295
1529
/
1552
356
/
331
1528
/
1479
418
/
360
1522
/
1396
474
/
380
1511
/
1305
520
/
389
410
CFM/ton
CFM
W
atts
1622
303
1636
379
1640
449
1638
512
1629
566
390
CFM/ton
CFM
W
atts
1557
/
1654
306
/
313
1564
/
1589
376
/
350
1564
/
1516
440
/
379
1559
/
1436
496
/
400
1548
/
1347
544
/
409
420
CFM/ton
CFM
W
atts
1659
322
1672
399
1677
471
1675
535
1667
591
400
CFM/ton
CFM
W
atts
1593
/
1689
326
/
332
1600
/
1625
397
/
369
1600
/
1554
462
/
399
1595
/
1475
519
/
420
1585
/
1389
568
/
430
430
CFM/ton
CFM
W
atts
1695
342
1708
421
1713
493
1712
559
1705
616
4.5
tons
**†
370
†
CFM/ton
CFM
W
atts
1652
/
1748
360
/
365
1659
/
1685
433
/
403
1660
/
1616
500
/
433
1655
/
1540
559
/
454
1646
/
1456
610
/
465
400
CFM/ton
CFM
W
atts
1769
385
1782
467
1789
543
1788
611
1783
671
380
CFM/ton
CFM
W
atts
1694
/
1789
386
/
390
1701
/
1727
460
/
427
1701
/
1659
528
/
458
1697
/
1548
589
/
480
1688
/
1503
641
/
491
410
CFM/ton
CFM
W
atts
1811
411
1826
495
1831
572
1832
643
1827
704
390
CFM/ton
CFM
W
atts
1736
/
1831
413
/
416
1742
/
1770
489
/
454
1744
/
1703
558
/
484
1740
/
1629
620
/
506
1732
/
1549
673
/
518
420
CFM/ton
CFM
W
atts
1854
439
1869
525
1875
604
1877
676
1872
739
400
CFM/ton
CFM
W
atts
1778
/
1873
442
/
443
1784
/
1813
519
/
481
1786
/
1747
590
/
512
1783
/
1675
653
/
534
1776
/
1597
707
/
546
430
CFM/ton
CFM
W
atts
1898
468
1913
556
1919
637
1921
711
1918
777
5
tons
370
CFM/ton
CFM
W
atts
1826
/
1921
475
/
476
1833
/
1862
555
/
515
1835
/
1797
627
/
545
1832
/
1726
692
/
568
1826
/
1650
748
/
580
400
CFM/ton
CFM
W
atts
1963
515
1978
606
1985
689
1988
766
1985
833
380
CFM/ton
CFM
W
atts
1875
/
1971
512
/
512
1882
/
1912
593
/
550
1884
/
1848
667
/
581
1882
/
1778
733
/
603
1876
/
1703
791
/
616
410
CFM/ton
CFM
W
atts
2014
554
2029
647
2037
733
2040
811
2038
880
390
CFM/ton
CFM
W
atts
1924
/
2021
551
/
550
1932
/
1963
634
/
588
1935
/
1900
710
/
619
1933
/
1832
777
/
641
1927
/
1758
836
/
654
420
CFM/ton
CFM
W
atts
2066
595
2082
691
2090
779
2093
859
2090
928
400
CFM/ton
CFM
W
atts
1975
/
2073
593
/
590
1983
/
2015
678
/
629
1986
/
1953
755
/
660
1985
/
1886
824
/
682
1979
/
1814
884
/
695
430
CFM/ton
CFM
W
atts
2120
640
2136
738
2143
828
2147
909
2143
980
•
†
F
actory
Setting
•
**
Not
an
actual
OD
size
•
Status
LED
will
blink
once
per
100
CFM
requested.
In
torque
mode,
actual
airflow
may
be
lower
.
•
T
orque
mode
will
reduce
airflow
when
static
is
above
approximately
0.4”
water
column.
•
If
the
air
handler
is
applied
in
downflow
or
horizontal
configurations,
the
airflow
should
not
exceed
2000
CFM.
Airflow
above
2000
CFM
could
result
in
water
blow-off
.
•
All
heating
modes
default
to
Constant
CFM.
•
Cooling
airflow
values
are
with
wet
coil,
no
filter
MINIMUM
HEATING
AIRFLOW
CFM
—
HEATER
MATRIX
MODEL
NO.
BA
YEV
AC04BK1AA
BA
YEV
AC04LG1AA
BA
YEV
AC05BK1AA
BA
YEV
AC05LG1AA
BA
YEV
AC08BK1AA
BA
YEV
AC08LG1AA
BA
YEV
AC10B-
K1AA
BA
YEV
AC10L
-
G1AA
BA
YEV
AC10LG3AA
BA
YEVCB15LG3AA
BA
YEVBC15BK1AA
BA
YEVBC20BK1AA
BA
YEVCC25BK1AA
T
AM7B0C60
1063
/
1188
1063
/
1500
1125
/
1500
1000
/
1188
1125
/
1563
1250
/
1625
1500
/
1750
1625
(a)
/
1813
WITHOUT
HEA
T
PUMP
/
WITH
HP
—
SEE
AIR
HANDLER
NAMEPLA
TE
Note:
Minimum
auxiliary
heating
airflow
is
automatically
configured
by
the
air
handler
model
and
the
auxiliary
heater
model
number.
This
is
not
field
adjustable.
(a)
Heater
not
qualified
for
208V
when
installed
in
horizontal
left
pposition
without
Heat
Pump