background image

18-GF74D1-1K-EN

7

Figure 2. Dip Switches

DIP SWITCHES (TYPICAL SETTINGS)

COOLING

HEATING

AIRFLOW

FAN OFF

DELAY

AUXILARY

HEAT SPEEDS

If the airflow needs to be increased or decreased,
see the Airflow Label on the air handler or Blower
Performance Table.

Be sure to set the correct airflow for cooling and
heating.

Switches 1–4 Cooling Airflow

Switches 5–6 Fan Off Delay Options

Switches 7–8 Auxiliary Heat

IIn

nd

do

oo

orr B

Bllo

ow

we

err T

Tiim

miin

ng

g

IIm

mp

po

orrtta

an

ntt:: Leave dip switches 5 and 6 in the “as-

shipped” positions during system start-
up and check out. Afterwards, adjust as
desired.

Table 3. Cooling Off — Delay Options

SWITCH SETTINGS

SELECTION

NOMINAL

AIRFLOW

5 — OFF

6 — OFF

NONE

SAME

5 — ON

6 — OFF

1.5 MINUTES

100%

(a)

5 — OFF

6 — ON

3 MINUTES

50%

5 — ON

6 — ON

ENHANCED

(b)

50–100%

(a)

Default setting

(b)

This ENHANCED MODE selection provides a ramping up and ramping
down of the blower speed to provide improved comfort, quietness,
and potential energy savings. The graph shows the ramping process.

Figure 3. Enhanced Mode

OFF

OFF

50%

80%

100% if necessary

50%

Dehumidify
Warm Air Heating

Fast Coil Cooling
Fast Coil Heating

Efficiency

7.5

minutes

3

minutes

1

minute

F

A

N

 O

P

E

R

A

T

IO

N

 (

C

F

M

)

as required

COMPRESSOR OPERATION          ON

OFF

9. W

Wiirriin

ng

g

Consult all schematic and pictorial wiring diagrams
of this unit and the outdoor equipment to
determine compatibility of wiring connections and
to determine specific requirements.

All field wiring to the air handler should be installed
in accordance with the latest edition of the National
Electric Code NFPA No. 70 and any local codes.
Check rating plates on unit for rated volts,
minimum circuit ampacity and maximum over
current protection. Supply circuit power wiring
must be 75 degree C (167 degree F) minimum
copper conductors only. Copper supply wires shall
be sized to the National Electric Code or local code
requirements, whichever is more stringent.

The unit is shipped wired for 230/240 Volt AC 60 HZ
1 Phase Operation. If the unit is to be operated at
208 VAC 60HZ, follow the instructions on the indoor
unit wiring diagram to change the low voltage
transformer to 208 VAC operation (Ensure unit is
properly grounded).

Class 2 low voltage control wiring should not be run
in conduit with power wiring and must be
separated from power wiring unless class 1 wire
with proper voltage rating is used.

Low voltage control wiring should be 18 Awg, color
coded (105 degree C minimum). For lengths longer
than 100ft., 16 Awg wire should be used. Make
certain that separation of control wiring and power
wiring has been maintained.

10. A

Aiirr F

Fiilltte

err

To protect the coil, blower and other internal parts
from excessive dirt and dust an air filter must be
installed before air enters the evaporator coil. A
remote filter must be installed. Consult the filter
manufacturer for proper sizing and maximum
velocity requirements.

IIm

mp

po

orrtta

an

ntt:: Air filters shall meet the test requirements

in UL 900.

11. T

Th

he

errm

mo

osstta

att

Select a thermostat that is commonly used with HP
or AC single stage heating/cooling with electric
heat. The thermostat will energize the fan on a
demand for heat or cool.

Install the thermostat on an inside wall, away from
drafts, lights or other heat sources in a location that
has sufficient air circulation from other rooms being
controlled by the thermostat.

12. S

Se

eq

qu

ue

en

ncce

e o

off O

Op

pe

erra

attiio

on

n

C

Co

oo

olliin

ng

g ((C

Co

oo

olliin

ng

g o

on

nlly

y))

When the thermostat calls for cooling, the circuit
from R to G is completed. The blower motor is
energized directly by the ECM fan control, which
receives the 24VAC signal from the thermostat.

The circuit from R to Y is also complete energizing
the compressor contactor of the outdoor unit. The

F

Fe

ea

attu

urre

ess

Summary of Contents for TEM6A0B24H21SB

Page 1: ...rature and on the tags stickers and labels that are attached to the equipment March 2018 1 18 8 G GF F7 74 4D D1 1 1 1K K E EN N Convertible Air Handlers 2 5 Ton TEM6A0B24H21SB TEM6A0B30H21SB TEM6A0C3...

Page 2: ...r rv vi ic ci in ng g a an nd d t tr ro ou ub bl le es sh ho oo ot ti in ng g o of f t th hi is s p pr ro od du uc ct t W WA AR RN NI IN NG G P PR RE ES SS SU UR RI IZ ZE ED D R RE EF FR RI IG GE ER R...

Page 3: ...AR RE EA A G GE EN NT TL LY Y W WI IT TH H S SO OA AP P A AN ND D W WA AR RM M W WA AT TE ER R A AF FT TE ER R H HA AN ND DL LI IN NG G T Th hi is s w wa ar rn ni in ng g c co om mp pl li ie es s w w...

Page 4: ...ta 11 Performance and Electrical Data 12 Minimum Airflow CFM 21 Outline Drawing 23 Heater Pressure Drop Table 24 Subcooling Adjustment 24 Subcooling Adjustment for TEM6A0C48H41 TEM6A0C60H51 24 Coil Co...

Page 5: ...onal 1 4 rise over the width or depth of the unit is allowed to create additional sloping towards the drain Unit must be positioned between level and rise sloping toward the drain connections When the...

Page 6: ...for air conditioning or heat pump operation Some outdoor models may require a start assist kit See outdoor unit for more information 7 B Bl lo ow we er r This unit is supplied with a variable speed m...

Page 7: ...y wires shall be sized to the National Electric Code or local code requirements whichever is more stringent The unit is shipped wired for 230 240 Volt AC 60 HZ 1 Phase Operation If the unit is to be o...

Page 8: ...the circuit from R to G is completed and the blower motor is energized directly by the ECM fan control which receives the 24VAC signal from the thermostat The circuit from R to W is completed energizi...

Page 9: ...for multiple stages of electric heat jumper W1 and W2 together if comfort control has only one stage of heat Single Stage HP Thermostat Air Handler Outdoor Unit R G B W1 W2 R B O Y X2 R G B O Y W1 Bl...

Page 10: ...lectric heat jumper W1 and W2 together if comfort control has only one stage of heat 2 Stage 2 Step HP Thermostat Air Handler Outdoor Unit R G B W1 W2 R B O Y1 X2 R G B O Y1 W1 Blue 24 VAC HOT FAN 24...

Page 11: ...18 GF74D1 1K EN 11 Electrical Data...

Page 12: ...211 830 242 727 268 HIGH 383 CFM ton ON OFF ON OFF CFM Watts 963 172 973 223 995 263 967 291 844 308 a Factory Default Setting Table 5 Air Flow Performance TEM6A0B24H21SB HEATING AIRFLOW PERFORMANCE N...

Page 13: ...138 1004 194 1022 258 1000 326 947 397 a Factory Default Setting Table 7 Air Flow Performance TEM6A0B30H21SB HEATING AIRFLOW PERFORMANCE NO FILTER NO HEATER OUTDOOR UNIT SIZE TONS SPEED SETTING AIRFLO...

Page 14: ...93 1528 436 1473 466 1406 483 1326 488 a Factory Default Setting Table 9 Air Flow Performance TEM6A0C36H31SB TEM6A0C42H41SB HEATING AIRFLOW PERFORMANCE NO FILTER NO HEATER OUTDOOR UNIT SIZE TONS SPEED...

Page 15: ...ed 1800 cfm in horizontal right horizontal left and downflow applications due to condensate blowoff The 5 ton high tap shall not be used in these applications Table 11 Air Flow Performance TEM6A0C48H4...

Page 16: ...476 1892 556 1900 635 1902 714 1760 650 a Factory Default Setting Table 13 Air Flow Performance TEM6A0D48H41SB TEM6A0D60H51SB HEATING AIRFLOW PERFORMANCE NO FILTER NO HEATER OUTDOOR UNIT SIZE TONS SP...

Page 17: ...45 Motor Amps a MCA and MOP for circuit 1 contains the motor amps Table 15 Electrical Data TEM6A0B30H21SB HEATER DATA Heater Model No No of Circuits Phases 240 Volt 208 Volt Capacity Heater Amps per C...

Page 18: ...YHTR1508BRK BAYHTR1508LUG 1 1 7 68 26200 32 0 45 45 5 76 19700 27 7 40 40 BAYHTR1510BRK BAYHTR1510LUG 1 1 9 60 32800 40 0 55 60 7 20 24600 34 6 49 50 BAYHTR1517BRK Circuit 1 a 2 1 9 60 32800 40 0 55 6...

Page 19: ...34 6 52 60 BAYHTR1517BRK Circuit 1 a 2 1 9 60 32800 40 0 59 60 7 20 24600 34 6 52 60 BAYHTR1517BRK Circuit 2 4 80 16400 20 0 25 25 3 60 12300 17 3 22 25 BAYHTR1523BRK Circuit 1 a 2 1 9 60 32800 40 0 5...

Page 20: ...34 6 52 60 BAYHTR1517BRK Circuit 1 a 2 1 9 60 32800 40 0 59 60 7 20 24600 34 6 52 60 BAYHTR1517BRK Circuit 2 4 80 16400 20 0 25 25 3 60 12300 17 3 22 25 BAYHTR1523BRK Circuit 1 a 2 1 9 60 32800 40 0 5...

Page 21: ...1000 820 BAYHTR3510LUG 875 820 BAYHTR3517LUG 1000 950 BAYHTR1523BRK 1300 1140 TEM6A0C48H41SB TEM6A0C60H51SB Heater Minimum Heater Airflow CFM With Heat Pump Without Heat Pump BAYHTR1504BRK BAYHTR1504L...

Page 22: ...7 Switch 8 Low ON ON 696 Med Lo OFF ON 825 Med Hi ON OFF 1150 High OFF OFF 1298 TEM6A0C48H41SB TEM6A0C60H51SB Airflow Performance with Auxiliary Heat Airflow Settings Dip Switch Settings Nominal Airfl...

Page 23: ...PRODUCT DIMENSIONS Air Handler Model A B C D E F H Flow Control Gas Line Braze TEM6A0B24 30 46 77 18 50 16 50 16 75 4 68 7 33 20 09 TXV 3 4 TEM6A0C36 42 51 27 23 50 21 50 21 75 7 01 9 66 24 59 TXV 7...

Page 24: ...1525 4 700 0 01 0 02 600 0 01 0 02 Subcooling Adjustment System Matched with Indoor Unit Model No Outdoor Model No Subcooling 16 SEER HP 2 ton TEM6A0C36H31 4TWR6024H1000A 4TWX6024H1000A 4A6H6024H1000A...

Page 25: ...The TEM6A0C48 and TEM6A0C60 will have a coil retaining bracket and a shipping bracket All other coils will have two coil retaining brackets 3 Remove the two screws holding the center horizontal brack...

Page 26: ...at hold the coil support brackets and retain for later use Seal the holes to prevent air leakage 7 Rotate and lift the two coil support brackets to remove from front slots in cabinet Figure 8 All mode...

Page 27: ...et removed in Step 3 Use the screws retained from Step 3 to attach 12 Place coil support brackets into the lower set of slots and rotate into place Push downward to lock into place 13 Secure each brac...

Page 28: ...l assembly back into the air handler cabinet as shown 16 Remove the appropriate knock out for the condensate piping Figure 12 TEM8A0C48 and TEM8A0C60 Only Figure 13 All other models 17 Replace all pan...

Page 29: ...ipping bracket All other coils will have two coil retaining brackets 3 Remove the two screws holding the center horizontal bracket and rotate out of place Retain parts Figure 16 TEM8A0C48 and TEM8A0C6...

Page 30: ...rtant The coil slabs are different and the mount hole locations will vary See the illustrations on the following pages that correspond to the unit tonnage to see the correct mounting position of the w...

Page 31: ...e on tube sheet TEM6A0B24 and TEM6A0B30 Front view Replace 2 screws and water diverter bracket Figure 23 TEM6A0B24 and TEM6A0B30 Rear view Remove 2 screws and water diverter bracket Figure 24 Screw is...

Page 32: ...Replace 3 screws and water diverter bracket TEM6A0C36 and TEM6A0C42 models Front view Figure 27 Remove 3 screws and water diverter bracket TEM6A0C36 and TEM6A0C42 models Rear view Figure 28 Screw is...

Page 33: ...Replace 3 screws and water diverter bracket Figure 31 TEM6A0D48 and TEM6A0D60 models Rear view Remove 3 screws and water diverter bracket Figure 32 TEM6A0D48 and TEM6A0D60 models Rear view Replace 3...

Page 34: ...s and the drain pan support bracket from the front of the drain pan and insert them in the drains at the rear of the drain pan Note For the TEM6A0C48 and TEM6A0C60 the drain pan support bracket should...

Page 35: ...nit in Step 12 Figure 36 All other models 12 Slide the coil assembly back into the air handler cabinet Important Make sure that the coil corner locks in place under the tab in the side left bracket to...

Page 36: ...in Step 3 15 Replace the two coil retaining brackets removed in a previous step Note The TEM6A0C48 and TEM6A0C60 will have only one coil retaining bracket 16 Replace all panels Figure 38 TEM6A0C48 an...

Page 37: ...ng shipment Adjust tubing if necessary so tubes do not rub against each other or any component when unit runs Ductwork is sealed and insulated All drain lines are clear with joints properly sealed Pou...

Page 38: ...38 18 GF74D1 1K EN N No ot te es s...

Page 39: ...18 GF74D1 1K EN 39 N No ot te es s...

Page 40: ...protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingersoll...

Reviews: