8.0 GENERAL INFORMATION
TS1A–13A
http://air.irco.com
22
TS–9A 50/60Hz
KEY
A.
Electrical conduit connection
B.
Compressed air inlet
50Hz: 4” PN16–DN
380v / 3 / 60Hz: 4” PN16–DN
All other 60Hz: 4” ANSI
C.
Compressed air discharge
50Hz: 4” PN16–DN
380v / 3 / 60Hz: 4” PN16–DN
All other 60Hz: 4” ANSI
D.
Condensate drain
50Hz: 1/4” BSP female
380v / 3 / 60Hz: 1/4” BSP female
All other 60Hz: 1/4” NPT female
TS–9A
“X”
Fan Qty
380v / 3 / 60Hz
1666 mm
3
400v / 3 / 50Hz
1670 mm
2
460v / 3 / 60Hz
1668 mm
2
NOTES:
1.
Weight (approximate):
TS–9A: 595 kg (1309 lb)
2.
Refrigerant: R–404A
3.
Tolerance on dimensions:
13mm (0.5”) unless otherwise
stated.
4.
305mm (12”) minimum electrical cable length allowance is
required between the electrical cable entry (A) and the mains
terminal block.
5.
Recommended clearance on all sides 1m(3ft) front panel with
starter door may require more as defined by local and national
electrical codes.
6.
External piping shall not exert any unresolved moments or
forces on it.
7.
There should be no plastic piping, not approved by IR, attached
to this unit or used for any lines downstream.
8.
Field installed ducting to and from the dryer can not add more
than 1.0mm (0.04) water air resistance.
Summary of Contents for TS10A
Page 2: ......
Page 10: ...5 0 SAFETY TS1A 13A http air irco com 8 5 3 TEXT DECALS NORTH AMERICA ...
Page 50: ......
Page 52: ......
Page 60: ...5 0 SECURITE TS1A 13A http air irco com 8 5 3 DÉCALCOMANIES DES TEXTES AMÉRIQUE DU NORD ...
Page 101: ......
Page 102: ......
Page 104: ......
Page 112: ...5 0 SEGURANÇA TS1A 13A http air irco com 8 5 3 AUTOCOLANTES DE TEXTO AMÉRICA DO NORTE ...
Page 152: ......
Page 161: ...5 0 SEGURIDAD TS1A 13A http air irco com 8 5 3 CALCOMANÍAS DE TEXTO AMÉRICA DEL NORTE ...
Page 203: ......
Page 204: ......