931229_00(0)_B Page 2 of 2

Figure 3

With keeper in closed position, install

new double switch (Figure 3).

New double

switch

3

Keeper (in closed position)

Figure 4-1

Snap new strain relief around DS wires

(Figure 4-1) and slide into box slot with

flat part facing out as shown (Figure 4-2).

Flat part facing out

4

Figure 4-2

New strain relief

Place keeper spring as far left as possible

and verify that spring’s hook is seated in

keeper’s spring slot (Figure 5).

5

Spring hook (seated in

keeper’s spring slot)

Figure 5

Keeper spring

Secure box top on box and while ensuring

that the keeper spring does not move out

of position, and that the wire strain relief

is secure (Figure 6).

6

Figure 6

Keeper spring

secure

Strain relief

secure

Reattach the box to the faceplate and

reinstall strike. See Figure 1.

7

NOTES:

If the current being sent through the switch is less than 100mA

a Gold contact switch (100mA) must be used.

If the current is greater than 100mA use the standard switch

(standard switches are rated for a maximum of 2A).

Type B switches are required for 6211WF and 6212WF units.

A non DS unit can not be upgraded to a DS unit with this kit

because the kit does not contain a tripper.

Hold keeper in closed position while

installing  switch and after switch is installed

or switch actuator can be damaged