51 / 92
ALARM CLEAN xx-
xx
Delete xx-xx alarm
SUCCESS
Delete the historical records
within the a range.
WHITELIST ON|OFF WHITELIST ON|OFF
Start or stop using a white
list.
ADD 13812345678
ADD 13812345678 OK
Add users to the alarm list.
DELETE
13812345678
DELETE 13812345678
OK
Delete users on an alarm list.
3.4.7.2 Alarm User List
Up to ten alarm recipients can be added to the “alarm user list.”
Mobile phone numbers are filled in the first column, and may range from 1 to 16 bytes long. This
column must be filled; otherwise users cannot be added.
User names are filled in the second column, and may range from 0 to 16 bytes long. This column
may be left empty.
Telephone numbers cannot be repeated.
3.4.7.3 Alarm Rule List
In this section of interface, the technician will create an "alarm rule list.” Each line defines an alarm
rule and a maximum of one-hundred alarm rules can be configured. The technician will match
mathematical expressions and compare values to a variable in each rule. To set an alarm rule follow
these steps:
Select a PLC in the first column. Any PLC previously setup in the “Modbus to SMS” chapter of
this manual will appear in a drop-down menu.
Select a variable name in the second column, and the corresponding variable of the PLC will
appear above it. The technician will compare values to this variable.
Compare the variable to a value by selecting an operator in the third column. The available options
are: NONE, >, >=, <, <=, = and !=.
Define the first value in the fourth column. This value will be compared to the main variable. For