Installation and Programming manual
Programming and maintenance from the panel
27
10.1.3 Addressing the power supply station on the RS485 BUS
From station:
Ok, Programming, Ok, Address RS485,
Ok
This programming section will allow you to assign addresses to all the power-supply stations on the RS485
BUS of the INIM fire detection panel.
Select an address from 01 a 16 (the default address is 01). If more than one SmartLevel power supply
station is connected to the RS485 BUS, each must have a different address.
Press
Ok
to assign the desired address. Press
Esc
to save the setting and exit.
10.1.4 Reset default (factory settings)
From station:
Ok, Programming, Ok, Default data,
Ok
If you select this option, you will be asked to confirm the operation. If you press
OK
, all the settings will
reset to default (factory settings).
10.2
Direct Maintenance
From station:
Ok, Maintenance, Ok
This section will allow you to carry out software maintenance using the power supply station interface.
10.2.1 Time and Date
From station:
Ok, Maintenance, Ok, Time and date, Ok
Using keys
S
and
T
, select the desired field then press
Ok
to modify the value.
Press
Esc
to save the setting and exit.
10.2.2 Booster ON/OFF
From station:
Ok, Maintenance, Ok, Booster ON/OFF, Ok
This section will allow you to modify the output channels directly and view the status of the circuit
breakers. Using keys
S
and
T
, select the desired output then adjust it to requirements using the
Ok
key.
If the selected output is set as
ON
, it will have a value of 24V. If the selected output is set as
OFF
it will
have a value 0V.
If the
In prot.
string appears, it means that the corresponding protection circuit has switched the output
Off due to either short-circuit or overload (a charge that exceeds specifications). Under these
circumstances, follow the procedure described in paragraph
11.2 “Output protection” fault
.
10.3
Closing a Programming/Maintenance session
Once all operations are complete, remove the PROG. jumper to end the programming session.
The power supply station will be fully operative and the display will show the presentation screen.
Parameter
Default value
Mains failure delay
2 minutes
Output activation time (ON Time)
Undefined
Standby status of the outputs
24V
Power Supply unit address on the RS485 BUS
01
Language
You must select the language at
first startup