Installation
17
Installation and programming manual
Chapter 4
INSTALLATION
4-1
Wall-mounting
The SmartLink should be located in a hidden place that cannot be
accessed by unauthorized persons.
ATTENTION!
Verify that the GSM network signal of the selected provider is
adequate.
Do not install the device near metal objects.
Ensure that there are at least two metres between the SmartLink
and other electrical devices.
1.
Using the metal backbox (
table 3, L
), mark the anchor screw
locations on the wall. Be sure not to drill in the vicinity of elec-
trical wiring or plumbing/gas pipes, etc.
2.
Insert the screw anchors (recommended size 6mm).
3.
Pull the wires through the wire entry.
4.
Using the screws, attach the backbox to the wall.
Note
The cable gland must be flame class rating V-1 or higher.
4-2
Connecting to the mains
power supply
The SmartLink must be powered from the mains and must also be
connected to a backup battery.
MAINS POWER
SUPPLY 230VAC 50HZ
The mains supply requires the use of a power supply (
Appendix A,
Events
) and therefore a separate line from the mains box. The line
must be protected by a safety-standards compliant circuit breaker
(trip switch).
The protective earthing system must be compliant with all safety
standards and laws in force.
ATTENTION!
Ensure that the Mains is switched Off during the mains connection
phase. Danger of electric shock.
Connect the power supply (already connected to the mains), to
terminals “
+ 14 -
” on the PCB (
table 4 "Terminals on the terminal
board"
), taking care to respect the correct polarity of the wires. The
power supply will provide power to the SmartLink and the devices
connected to its outputs and also recharge the backup battery.