Booster Parameters
I 13
Booster Parameters
Display Name
Unit
Range
Description
Factory setting
220V
240V
B 00
Set pressure
Bar
0.3 ~ 6.0
The pressure value to be kept
constant.
2
2
B 01
Differential
Pressure
Bar
-0.3 ~ -0.2
To correct variation between
suction and discharge of the
pressure value
-0.3
-0.5
B 02
Sensor
Range
Bar
1.0 ~ 20.0
Selection of the sensor range
denpend on the pressure required.
10
6
B 03
Sensor
Adjustment
Bar
-9.9 ~ 9.9
If the value indicated at the
pressure gauge differs from the
pressure sensor, please adjust the
sensor value with this paremeter.
0
0
B 04
Low
Pressure
setting
Bar
0.2 ~ 2.0
To set the lowest pressure.
Note : Once the default set
pressure is adjusted, the
Low Pressure setting will be
automatically adjusted to 20% of
the set pressure
0.3
0.5
B 05
Low Pressure
Stop
Sec
0 or 1
- 0 : OFF
- 1 : 1~999
20
20
B 06
Low Current
Amp
0.5 ~ 5.0
Note : This value automatically
changes depend on P10
(Pump capacity).
1HP : 1.8A
1.5HP : 2.5A
2HP : 3.3A
2.5HP : 4.0A
3HP : 4.6A
3.3
3.3
B 07
Low Current
Stop
Sec
0 or 1
- 0 : OFF
- 1 : 1~999
10
10
B 08
Motor
Direction
0 or 1
- 0 : CW
- 1 : CCW
0
0
To set the parameter, please press the ‘
’ and
‘
’ button for 3 seconds.