IHC-230 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
9
5.1 Control Range Setting
MD: Mode Setting
MD=H, being in Humidity Setting Mode, user can set humidity parameters in the following
menu;
MD=T, being in Temperature Setting Mode, user can set temperature parameters in the
following menu;
5.2 Humidity/Temperature Control (HD, HS, DS/ HC,TS,DS)
In Humidifying/Heating Control Mode (HD=H, HC=H)
When the measured humidity (temperature) drops down to
HS–DS (or TS-DS)
, the
output will be on and the indicator lamp will light up; When the measured
humidity/temperature reaches the set value
HS (TS)
, the output will be off and the
indicator lamp will be off too.
In Dehumidifying/Cooling Control Mode (HD=D, HC=C)
When the measured humidity (temperature) rises to
HS+DS (or TS+DS)
, the output will
be on and the indicator lamp will light up; when the measured humidity/temperature
reaches the set value
HS (TS)
, the output will be off and the indicator lamp will be also off.
5.3 Alarm Limit Setting (AH, AL)
When the measured humidity (temperature)
higher than AH
, the humidity (temperature)
high alarm will be on; when the measured humidity (temperature)
lower than AL
, the
humidity (temperature) low alarm will be on.
When alarm is on, the display will be flashing between the measured value and alarm code
with the “BI-BI-BIII” sound. The alarm sound can be stopped by pressing any key but the
status of alarm will be not change until the value of measured humidity/temperature
return to the normal range.
5.4 Compressor Delay (PT)
Under dehumidifying (cooling) control mode, after power on, if the measured humidity
(temperature) higher than
HS+DS
(TS+DS)
, the equipment won’t start
dehumidifying/cooling control immediately, but waiting for a delay time.
When the time interval between two dehumidifying (cooling) operation (or the time from
power on to dehumidify (refrigeration) is larger than preset delay, the equipment will start
dehumidifying (cooling) control immediately; when the time interval between two
dehumidifying (cooling) (or the time from power on to dehumidifying/cooling) is less than
preset delay, the equipment won’t start dehumidifying (cooling) until preset delay is
satisfied.
Delay time will be calculated once dehumidifying (cooling) stops.