background image

 

 

 

ITC-308 User Manual

 

Inkbird Tech. Co., Ltd.                                                                        www.ink-bird.com

 

 

3. Keys Instruction 

 

  PV:  Process  Value.

 under running mode, display current temperature; under setting 

mode, display menu code. 
 

  SV:  Setting  Value. 

under  running  mode,  display  setting  temperature;  under  setting 

mode, display setting value. 

 

  Cooling  indicator  Lamp:

  when  the  light  is  on,  start  refrigeration;  when  the  light  is 

flickering, the compressor is under delay protection. 

 

  Heating Indicator Lamp:

 when the light is on, start heating. 

 

  SET  key: 

press SET key for 3 seconds to enter menu for function setting. During the 

setting process, press SET key for 3 seconds to quit and save setting changes. 

 

  DECRESE  key:

  under  running  mode,  press  DECRESE  key  to  inquiry  CD  value;  under 

setting mode, press DECRESE key to decrease value. 
 

  INCREASE  key:

 under running mode, press INCREASE key to inquiry HD value; under 

setting mode, press INCREASE key to increase value. 

 

  Heating Device Socket:

 this socket is for heating output. 

 

Summary of Contents for ITC-308

Page 1: ... No part of this document may be reproduced without prior written permission Disclaimer Inkbird has made every effort to ensure that the information contained in this document is accurate and complete however the contents of this document are subject to revision without notice Please contact Inkbird to ensure you have the latest version of this document ...

Page 2: ... to Set Parameters 6 4 3 Setup Flow Chart 7 5 Menu Instruction 7 5 1 Temperature Control Range Setting TS HD CD 8 5 2 Alarm High Low Limit Setting AH AL 8 5 3 Compressor Delay PT 9 5 4 Temperature Calibration CA 9 5 5 Display in Fahrenheit or Centigrade unit CF 9 6 Error Description 10 Sensor Fault Alarm 10 Over temperature Alarm 10 7 Technical Assistance and Warranty 11 7 1 Technical Assistance 1...

Page 3: ...th large output power 1200W 110V 2200W 220V it s suitable for most applications ITC 308 is designed with compressor delay protection for refrigeration high and low temperature alarm and sensor fault alarm which makes the temperature controller more safe and reliable Functions such as temperature calibration separately set differential for refrigeration and heating enable more accurate temperature ...

Page 4: ...zzer Alarm High and Low Temperature Alarm Sensor Type NTC sensor Including Sensor Length 2m 6 56ft Relay Contact Capacity Cooling 10A 100 240VAC Heating 10A 100 240VAC Input Power Cable Length 1 5m 5ft Output Power Cable Length 30cm 1ft Dimension Main Body 140x68x33mm 5 5x2 7x1 3 inch Socket US Version 85x42x24mm 3 3x1 7x1 0 inch Socket EU Version 135x54x40mm 5 3x2 1x1 6 inch Socket UK Version 140...

Page 5: ...kering the compressor is under delay protection Heating Indicator Lamp when the light is on start heating SET key press SET key for 3 seconds to enter menu for function setting During the setting process press SET key for 3 seconds to quit and save setting changes DECRESE key under running mode press DECRESE key to inquiry CD value under setting mode press DECRESE key to decrease value INCREASE ke...

Page 6: ...meters When the controller is working normally press SET key for over 3 seconds to enter parameters set up mode SET indicator lamp will on PV window displays the first menu code TS while SV window displays according setting value Press SET key to go to next menu and display according menu code press key or key to set current parameter value After setting done press SET key for 3 seconds at any tim...

Page 7: ...ction Setting range Default setting Remarks TS Temperature Set Value 50 99 9 25 5 1 HD Heating Differential Value 0 3 15 2 0 CD Cooling Differential Value 0 3 15 2 0 AH Alarm High Limit 50 99 9 90 5 2 AL Alarm Low Limit 50 99 9 40 PT Compressor Delay 0 10 minutes 3 minutes 5 3 CA Temperature Calibration 15 15 0 5 4 CF Display in Fahrenheit or Centigrade C 5 5 ...

Page 8: ...ion equipment is under compressor delay protection status When the measured temperature PV TS temperature set value the cool indicator lamp will off and the refrigeration relay stops working When the measured temperature PV TS temperature set value HD heating differential value system enter heating status the heat indicator lamp will on and heating relay starts to work when the measured temperatur...

Page 9: ...than preset delay the equipment won t start refrigeration until preset delay is satisfied Delay time will be calculated right after the moment refrigeration stops 5 4 Temperature Calibration CA When there is deviation between measured temperature and actual temperature use temperature calibration function to align the measured temperature and actual temperature The corrected temperature is equal t...

Page 10: ... be dismissed by pressing any key After faults solved the system will return to normal working mode Over temperature Alarm when measured temperature exceeds the measuring range less than 50 C 58 F or higher than 99 C 210 F the controller will initiate over temperature alarm mode and cancel all the actions The buzzer will alarm LED displays HL Buzzer alarm could be dismissed by pressing any key Whe...

Page 11: ...ondition by the original purchaser not transferable against defects caused by INKBIRD s workmanship or materials This warranty is limited to the repair or replacement at INKBIRD s discretion of all or part of the thermostat The original receipt is required for warranty purposes INKBIRD is not responsible for injury property damage or other consequential damages or damages of third parties arising ...

Reviews: