24
stage will not enter the next time-temperature control until the
current stage is completed.
4.6.8 U01~U12
are the parameters for the user to determine
whether to alarm or not, setting to n=No Alarm; A= Alarm; C=
Confirm; S=Stop Program.
4.6.8.1 UX=n:
I
f the current stage is set to n, the next cycle
control is entered; if the execution of the cycle index MD is
completed, all output controls are turned off, PV shows the
current temperature, and SV shows End.
4.6.8.2 UX=A
:
If the current stage is set to A, when the
duration is completed, enter the next stage of control, PV
shows the previous stage UX (X = 01~12), SV shows A, and PV
shows the current temperature, SV shows the current stage of
setting temperature with 1Hz frequency alternate, buzzer
beeps every two seconds; if the cycle index MD is completed,
all output control is turned off, PV shows previous stage UX
(X=01~12), SV shows A and PV shows current temperature,
SV shows End with 1Hz frequency alternately . Press any
button at this time to cancel the buzzer alarm and return to
normal display. If the cycle index MD is completed, PV will
show the current temperature and SV will show End.
4.6.8.3 UX=C
:
If the current stage is set to C, when the
duration is completed, it still control according to the current
stage of the set temperature, PV shows the current stage UX
(X = 01 ~ 12), SV shows C, and PV shows the current
temperature, SV shows the current stage temperature setting
value with 1Hz frequency alternately . The buzzer beeps every
two seconds. Only when the user presses any button will turn
the alarm off and the control will be entered in the next stage.
If the execution of the cycle index MD is completed, PV shows
the current temperature and SV shows End.
4.6.8.4 UX=S
:
If the current stage is set to S, when the
duration is completed, all output controls are turned off, PV
shows the current stage UX (X=01~12), S shows down, and
PV shows the current temperature, SV shows the current
stage temperature setting value with 1Hz frequency
alternately, the buzzer beeps every two seconds. Only when
the user presses any button will turn the alarm off and the
Output(WORK1/WORK2) Instruction
WORK1:
The P1 heating/cooling output
WORK2:
The P2 heating/cooling output
Indicator LED:
●
Red LED is on WORK1 output is on.
●
Red LED is blinking WORK1 output is performing the
function of compressor delay.
●
Green LED is on WORK2 output is on.
●
Green LED is blinking WORK2 output is performing the
function of compressor delay.
●
Yellow LED is on The controller is in the setting mode.
Button Instruction
Please read the detail on
2.Button Operation Instructions
below
Probe interface
Two temperature probes can be insert into P1 and P2 interface.
Temperature probe
●
If the controller display Er, you may get a false temperature
probe, please try harder to insert the probe and rotate it to make
good contact. If the problem is still persists, it is likely the
internal probe wire has been damaged by the moisture or heat
temperature.
●
The probe and cable cannot be touched by the flame.
●
Do not exceed the probe temperature range to avoid
damaging.
2 Button Operation Instructions
2.1 Restore Default Settings
Press and hold the “ " button to power on, the buzzer will
make a short call, indicating that all parameters of the user's
temperature and humidity probe function return to the default
setting value.
2.2 “ ” and “ ”Button Function in Normal Operation
Mode
Press the “ ", PV shows the current temperature setting
value , SV shows current humidification value; press “ ", PV
shows current temperature value, SV the current humidification
setting value , and It will be back to the normal display if there is
no operation for 3 seconds orpressing the "
SET
" button.
2.3 “SET” Button Function in Normal Operation Mode
Short press the “
SET
” button to enter the quick setting
temperature and humidity value mode. PV shows the current
temperature setting value and flashes, and short press “ ” or
“ ” button to increase or decrease the setting value, long
press “ ” or “ ”button to quickly increase or decrease the
setting value, Short press the “
SET
” button again
,
SV shows
the current humidity setting value and flashes, and short press
“ ” or “ ” button to increase or decrease the setting value,
long press “ ” or “ ”button to quickly increase or decrease
the setting value and lastly press the "
SET
" button again to
confirm and exit. If there is no operation, it will automatically
exit after 10 seconds and save the setting value.
2.4 Button Function in Setting Mode
When the controller is working normally, press the “
SET
” button
for 2 seconds to enter the setting mode
,
the PV shows the first
menu code“
”, SV shows the corresponding setting value.
Press “
SET
” button to scroll down the menu item and save the
parameters of the previous menu item. Press“ ” or
“ ”button to change the current setting value. Selected T to
enter the temperature parameter modification mode; selected H
to enter the humidity parameter modification mode. If in the
setting state, there is no operation within 30 seconds or long
press "
SET
" button for 2 seconds, it will exit and save the
setting state and return to normal operation mode.
Summary of Contents for ITC-608T
Page 1: ...ITC 608T Manual...
Page 7: ...5 86 8f 96 0f WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Page 15: ...13 86 8f 96 0f WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Page 28: ...26 DUAL TEMPERATURE PROBES Controller Manual ITC 608T Part 4...
Page 29: ...27 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller 88 6f 98 6f...
Page 38: ...36 HUMIDITY Controller Manual Equivalent to IHC 200 Humidity Controller Manual ITC 608T Part 5...
Page 39: ...37 56 8 66 0 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Page 46: ...44 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller 88 6f 56 8...