EAGLE
mGuard
240
Innominate Security Technologies
I15007_en_02
13.3
Installation of EAGLE
mGuard
Connecting the voltage supply and signal contact
Terminal block
The connection of the supply voltage and the signal contact is established via a 6-pos. ter-
minal block.
Figure
13-3
Terminal block base
The EAGLE
mGuard can be operated at a DC voltage of 9.6
...
60
V
DC,
max.
1
A
optionally
at an AC voltage of 18
...
30
V AC, max. 1
A. Use the +24 V and 0 V pins to connect the AC
voltage.
Operating voltage
–
NEC Class 2 power source 12
V
DC or 24
V
DC, -25% +33%
–
Safety Extra Low Voltage (SELV/PELV, redundant inputs isolated)
–
Max. 5
A. Buffer time min. 10
ms at 24
V
DC.
Redundant power supply
A redundant supply voltage can be connected. Both inputs are isolated. The load is not dis-
tributed. With a redundant supply, the power supply unit with the higher output voltage sup-
plies the EAGLE
mGuard
alone.
The supply voltage is electrically isolated from the housing.
Startup
•
Start up the EAGLE
mGuard with the connection of the supply voltage via the 6-pos.
terminal block.
•
Lock the terminal block with the lateral locking screw.
WARNING:
The housing must not be opened.
WARNING:
This is a Class A item of equipment. This equipment can cause radio interfer-
ence in residential areas; in this case, the operator may be required to implement appro-
priate measures. When installed in residential or office areas, the EAGLE
mGuard
may
only be operated in control cabinets with fire protection properties according to
EN
60950-1.
NOTE:
The shielding ground of the connected industrial twisted pair cables is electrically
connected to the front plate.
WARNING:
The EAGLE
mGuard is designed for SELV operation. Therefore, only PELV
circuits or optionally SELV circuits with voltage limitations according to EN 60950-1 may
be connected to the supply voltage connections and the signal contact.
Signal contact
0 V
0 V
+24 V (P1)
+24 V (P2)
Summary of Contents for mGuard
Page 6: ...Innominate Security Technologies...
Page 32: ...mGuard rs4000 rs2000 32 Innominate Security Technologies I15007_en_02...
Page 74: ...mGuard rs4000 rs2000 3G 74 Innominate Security Technologies I15007_en_02...
Page 108: ...mGuard pci SD 108 Innominate Security Technologies I15007_en_02...
Page 142: ...mGuard centerport 142 Innominate Security Technologies I15007_en_02...
Page 156: ...mGuard delta 156 Innominate Security Technologies I15007_en_02...
Page 180: ...mGuard pci 180 Innominate Security Technologies I15007_en_02...
Page 196: ...mGuard blade 196 Innominate Security Technologies I15007_en_02...
Page 236: ...mGuard industrial rs 236 Innominate Security Technologies I15007_en_02...
Page 254: ...EAGLE mGuard 254 Innominate Security Technologies I15007_en_02...