2. INSTALLATION
2.1
GENERAL
INFORMATION
The unit must be installed according to national and local rules governing the use of electrical devices and according to the following
guidelines:
-install the unit within residential buildings with ambient temperature between 0 °C and 45 °C;
-avoid areas in close proximity to sources of heat, steam, flammable and / or explosive and particularly dusty areas;
-the consistency of the wall where the unit is to be installed must be adequate and not cause vibrations.
In the environment chosen for the installation must be present:
-coring for connection of the air duct;
-Electrical connection responding to current regulations
The unit is an integral part of a balanced ventilation system, attention to the coupling unit and a natural draft boiler (ex. Open
fireplace) which may cause a depression in the environment, due to which there may be a reflux gas discharge into the environment.
2.2
POSITIONING
AND
ASSEMBLY
UNIT
To mount the drive, you must:
•
Realize, for the whole thickness of the wall, a
minimum diameter of hole:
162mm (HRC05S VERSION)
102mm (HRC02S VERSION)
with an inclination of 1 ° to the outside
environment.
•
The hole may be positioned at any height.
It is recommended on a height of 1.8 meters
and distant from the lateral walls and ceilings
at least 100mm.
Ensuring sufficient space for the performance of
maintenance tasks: it must be guaranteed the
opening of the cover of the unit (from the bottom).
Do not mount the unit with the hips in direct
contact with the walls to avoid possible noises from
contact, insert strips of rubber or neoprene in this
case.
Fig.1A Recommended positioning
If you use two units on the same wall of 1,2mt
maintain this minimum distance between a core
and another.
If instead you use two adiancent walls at an angle,
keep up with the minimum distance of the coring
1,2mt from the angle common to the two walls.
Fig.1B positioning two units