Physical and chemical properties of 'water
not compatible chemical and physical characteristics could affect the integrity of the hydraulic part of the the unit.
Check water quality;
DESCRIPTION
Limit value
Hardness
<10 ° F
PH value
7.5 / 9
Oxygen
<2 mg / l
Conductivity
<500 uS / cm
Iron
<2 mg / l
Manganese
<1 mg / l
Nitrate
<70 mg / l
Sulphate
<70 mg / l
Chlorine Compounds
<300 mg / l
Carbon dioxide free radical
<10 mg / l
Ammonium
<20 mg / l