7
Outstanding adaptability to the worst mains input condition.
Extra wide input voltage, frequency range and waveform, avoid
excessive dissipating limited battery energy.
Internal charger could be up to 4Amps to decrease recharging
time of battery. Optional external large charging current charger
which is up to 12Amps could be supplied.
N+X parallel redundancy to increase the reliability and flexibility.
Number of parallel operating UPS is up to 4.
HE mode with high efficiency >0.96, save power expense for
user.
Input or output ISO transformer compatibility.
Start-able without battery.
3.2 Electrical specifications
INPUT
Model No.
6K(S)
10K(S)
Phase
Single
Voltage
176~276VAC
Frequency
(45~55)/(54~66) Hz
Current(A)
THDI
< 5% @ full load
Power Factor
> 0.99 @ full load
OUTPUT
Model No.
6K(S)
10K(S)
Power rating
6kVA/5.4kW
10kVA/9kW
Voltage
208*/220/230/240×
(
1
士
1%
)
VAC
Frequency
50/60×
(
1±0.1
)
Hz (Battery mode)
Wave form
sinusoidal