46
3) Set the main maintenance switch or static switch from “UPS” to
“BPS”, switch off the main output breaker, and the UPSs would
shut down.
4) Ensure the UPSs shut down totally, set the UPS own
maintenance switch from “BPS” to “UPS” and screw the
maintenance cover plate back again. Remove the wanted UPS
and reinstall the new UPS parallel system by following step 1)
to 12) of last chapter - “install a new parallel UPS system”.
5) If the removed UPS or the remained UPS will be used in a
stand-alone mode, then JP1 and JP2 on the terminal block
should be connected with a short connection wire.
6) Set the main maintenance switch or static switch from “BPS” to
“UPS”, Press the
button of one UPS, each UPS would start
to turn on, after turning on, the UPSs should work parallel in the
Line mode.