Battery DC Over Voltage Battery voltage is
higher than normal
value
Check if the battery quantity is
right.
Over Charge
Battery is over
charged
The UPS would transfer to
battery mode automatically, and
after the Battery voltage is
normal and the mains is normal,
the UPS would retransfer to
Line mode automatically again.
Model Pin Error
UPS internal fault
Consult dealer.
Ambient Over
Temperature
The ambient
temperature is too
high
Check the environment
ventilation.
Heatsink Over
Temperature Warning
Inside temperature of
UPS is too high
Check the ventilation of UPS
and the ambient temperature.
NTC abnormal
UPS internal fault
Consult dealer.
Communication cable
male disconnected
The parallel cable is
disconnected
Check the parallel cable.
Communication
cable
female disconnected
The parallel cable is
disconnected
Check the parallel cable.
Parallel Battery
Connection Different
The battery packs of
some UPSs are
disconnected
Check if all the battery pack is
connected.
Parallel input different
The mains input of
some UPSs is
disconnected
Check the building wiring and
input cable.
Check if the input breaker is
closed.
Ensure the UPSs are
connected to same input
source.
Parallel Power strategy
setting different
There are different
power strategy setting
in parallel system
The UPSs with different power
strategy setting (Ex. one Line
mode and one Converter mode)
are forbidden to parallel.
Parallel rated power
capacity setting different
There are different
UPSs in parallel
system
The UPSs with different
capacity (Ex. one 6KVA and
one 10KVA) are forbidden to
parallel.