background image

D100-68-00 

I56-1684-007R

DH100ACDCI Ionization
Air Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630-377-6495

www.systemsensor.com

Before Installing

Please thoroughly read the System Sensor 

Guide for Proper Use 

of  Smoke  Detectors  in  Duct  Applications

  (A05-1004),  which 

provides  detailed  information  on  detector  spacing,  placement, 
zoning, wiring, and special applications. Copies of this manual 
are  available  online  at  www.systemsensor.com  or  via  System 
Sensor’s  toll  free  fax-back  service,  Documents  on  Demand  at 
800/736-7672. NFPA Standards 72 and 90A should also be refer-
enced for detailed information. 

NOTICE:

  This  manual  shall  be  left  with  the  owner/user  of 

this equipment.

IMPORTANT:

  This  detector  must  be  tested  and  maintained  reg-

ularly  following  NFPA  72  requirements.  The  detector  should  be 
cleaned at least once a year.

Table of Contents 

Page

[1] General Description  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] Limitations of Duct Smoke Detectors . . . . . . . . . . . . . . . . . 1
[3] Contents of the Duct Smoke Detector Kit . . . . . . . . . . . . . . 1
[4] Exploded View of Duct Smoke Detector Components . . . . . 2
[5] Installation Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Duct Smoke Detector Maintenance and Test Procedures . . . 4
[7] Detector Cleaning Procedures . . . . . . . . . . . . . . . . . . . . . . 5
[8] Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[9] Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Warranty   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

[1] General Description

An HVAC system supplies conditioned air to virtually every area 
of a building. Smoke introduced into this air duct system will be 
distributed  to  the  entire  building.  Smoke  detectors  designed  for 
use in air duct systems are used to sense the presence of smoke 
in the duct. 
Model  DH100ACDCI  Air  Duct  Smoke  Detectors  utilizes  ioniza-
tion technology for the detection of smoke. This smoke detection 
method, when combined with an efficient housing design, sam-
ples  air  passing  through  the  duct  and  allows  detection  of  a  de-
veloping hazardous condition. When sufficient smoke is sensed, 
an alarm signal is initiated and appropriate action can be taken 
to shut off fans, blowers, change over air handling systems, etc. 
These actions can facilitate the management of toxic smoke and 
fire gases throughout the areas served by the duct system.
The DH100ACDCI detector is designed to operate on 24 VDC/VAC, 
120 VAC, or 240 VAC. Alarm and supervisory relay contacts are 
available for control panel interface (alarm initiation), HVAC con-
trol, and other auxiliary functions. Auxiliary relays are also pro-
vided for fan shut down or signaling of up to 9 other detectors 
in the loop for multiple fan shut down. These detectors are not 
designed for 2-wire applications.
For testing, the alarm can be enabled by a magnet activated test 
switch or by the optional remote test station. The duct smoke 
detector latches into alarm state when an alarm occurs. A green 
LED  flashes  to  indicate  power,  a  red  LED  signals  local  alarm 
indication, and optional accessories offer a variety of annuncia-
tion capabilities.

The DH100ACDCI can be reset by a momentary power interrup-
tion,  the  reset  button  on  the  front  cover,  the  control  panel,  or 
remote reset accessory. 

The DH100ACDCI incorporates a cover 

tamper feature that provides a trouble signal after 7 minutes if 
the cover is removed or improperly installed.

 Proper installation 

of the cover removes the trouble condition.

[2] Limitations Of Duct Smoke Detectors 

WARNING

The  National  Fire  Protection  Association  has  established  that 
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR 
OPEN AREA DETECTOR PROTECTION as a means of providing 
life safety. Nor are they a substitute for early warning in a build-
ing’s regular fire detection system.

System  Sensor  supports  this  position  and  strongly  recom-
mends that the user read NFPA Standards 90A, 72, and 101. The 
DH100ACDCI Air Duct Smoke Detectors are listed per UL 268A.

This device will not operate without electrical power. Fire situa-
tions may cause an interruption of power. The system safeguards 
should be discussed with your local fire protection specialist.

This device will not sense smoke unless the ventilation system is 
operating and the cover is installed.

For this detector to function properly, it MUST be installed accord-
ing to the instructions in this manual. Furthermore, the detector 
MUST be protected from the elements and operated within ALL 
electrical and environmental specifications listed in this manual. 
Failure to comply with these requirements may prevent the detec-
tor from activating when smoke is present in the air duct.

[3] Contents Of The Duct Smoke Detector Kit

1.  Complete housing base and cover assembly
2.  Two #10 x 1

1

/

4

˝ sheet metal screws for mounting

3.  Two sampling tube filters
4.  One test magnet
5.  Drilling template
6.  Two foam gaskets
7.   Four #6-self tapping mounting screws for the metal sampling 

tube and optional exhaust tube extension

8.  One sampling tube end cap
9.  One plastic sampling tube
10.  One #8 self-tapping screw for the plastic sampling tube

NOTE:

  For  ducts  over  1

1

2

  feet,  longer  sampling  tubes  must  be 

ordered  to  complete  the  installation.  They  must  be  the  correct 
length for the width of the duct where they will be installed. See 
Table 1 on page 3 to determine the sampling tube required for dif-
ferent duct widths.

I56-1684-00

7R

Summary of Contents for DH100ACDCI

Page 1: ...hut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashes to indicate power a red LED signals local alarm indication and optional accessories offer a variety of annuncia tion capabilities The ...

Page 2: ...les as indi cated in Figure 4 D100 68 00 2 I56 1684 007R 4 Figure 1 Exploded View Of Duct Smoke Detector Components FOAM GASKETS PLASTIC SAMPLING TUBE CONDUIT HOLES DETECTOR HOUSING TERMINAL STRIP DETECTOR COVER SAMPLING TUBE FILTERS PLASTIC SAMPLING TUBE SELF TAPPING SCREW POWER BOARD DETECTOR BOARD COVER MOUNTING SCREWS H0401 00 H0110 00 5 Installation Sequence 5 1 Verify Duct Air Flow Direction...

Page 3: ...t the end opposite the duct smoke detector Figure 5 Tube mounting configurations with varying air flow direction AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONT...

Page 4: ... between interconnected detectors or from detectors to auxiliary devices it is usually recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in t...

Page 5: ... RTS451KEY is not required when these accessories are used with the DH100ACDCI detectors The functionality of the magnetic coil has been designed into the circuitry of the new In novair duct smoke detectors 6 2 2 3 SSK451 Multi Signaling Accessory The System Sensor SSK451 Multi Signaling accessory combines a sounder feature with a key activated test and reset function Green amber and red LEDs prov...

Page 6: ...S ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM 5 VDC 1 4 HP 240 VAC 1 8 HP 120 VAC NOT INTENDED FOR CONNECTION TO CONTROL PANELS TROUBLE CONTACT RATING 2 0 A 30 VDC resistive 2 0 A 125 VAC resistive 120 VAC CAUTION Do not loop wire under termin...

Page 7: ...ination of accessories may be used such that the given accessory loads are 60 mA or less in the standby state 110 mA or less in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1684 007R Figure 11 Wiring diagrams for optional accessories H0402 01 15 ALARM SIGNAL 3 14 2 RESET 11 TEST 20 AUX POWER 19 AUX POWER SSK451 FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SUPERVISORY CONTACT NO ...

Page 8: ...60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2 0A 125 VAC resistive Note Alarm auxiliary c...

Reviews: