background image

[5.3] Secure The Detector Housing To The Duct

Slide the foam gaskets over the tube bushings as shown in 

Figure 3

Use the two 1

1

/

4

˝ long sheet metal screws to screw the detector hous-

ing to the duct. 

CAUTION: Do not overtighten the screws.

Figure 3. Installation of foam gaskets over sampling 
tube bushings:

SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.

H0107-00

[5.4] Sampling Tube Installation for Ducts Greater 
Than 1

1

2

 Feet Wide

The sampling tube is identified by a series of air inlet holes on 
the tube. A plastic tube is included for ducts up to 18 in width. 
All  other  lengths  must  be  purchased  separately.  Order  the  cor-
rect length, as specified in Table 1, for width of the duct where it 
will be installed. It is recommended that the sampling tube length 
extend at least two-thirds across the duct width for optimal per-
formance. The exhaust tube is molded onto the base of the duct 
housing, and the A2440-00 Exhaust Tube Extension is available as 
an accessory in those cases where the molded exhaust port does 
not extend at least 2 inches into the duct. 
The  sampling  tube  is  always  installed  with  the  air  inlet  holes 
facing  into  the  air  flow.  To  assist  proper  installation,  the  tube’s 
mounting  flange  is  marked  with  an  arrow.  Make  sure  the  sam-
pling tube is mounted so that the arrow points into the air flow 
(see 

Figure 4

). 

Figure 5

 shows the various combinations of tube 

mounting  configurations  with  respect  to  air  flow.  Mounting  the 
detector housing in a vertical orientation is acceptable, provided 
that  the  air  flows  directly  into  the  sampling  tube  holes  as  indi-
cated in 

Figure 4

.

D100-68-00 

I56-1684-007R

[4] Figure 1: Exploded View Of Duct Smoke Detector Components

FOAM

GASKETS

PLASTIC

SAMPLING TUBE

CONDUIT HOLES

DETECTOR

HOUSING

TERMINAL STRIP

DETECTOR

COVER

SAMPLING TUBE

FILTERS

PLASTIC SAMPLING TUBE

SELF-TAPPING SCREW

POWER BOARD

DETECTOR BOARD

COVER MOUNTING

SCREWS

H0401-00

H0110-00

[5] Installation Sequence
[5.1] Verify Duct Air Flow Direction And Velocity

Model DH100ACDCI detectors are designed to be used in air han-
dling systems having air velocities of 500 to 4000 feet per minute. 
Be sure to check engineering specifications to ensure that the air 
velocity in the duct falls within these parameters. If necessary, use 
a velocity meter to check the air velocity in the duct.

[5.2] Drill The Mounting Holes

Remove the paper backing from the mounting template supplied. 
Affix the template to the duct at the desired mounting location. 
Make sure the template lies flat and smooth on the duct. Center 
punch holes A and B. Drill the holes as indicated on the template. 

[5.2.1] Sampling Tube Installation for Ducts Less 
Than 1

1

2

 Feet Wide (see Figure 2)

1.  Remove the front cover.
2.  Slide the plastic sampling tube into the housing bushing.
3.   Align the holes in the bushing with the holes in the sampling 

tube. Make sure there are 6 exposed holes on the plastic sam-
pling tube. Secure with the #8 self-tapping screw into the bot-
tom of the permanent tube (shown in 

Figure 1

).

NOTE:

 The sampling tube end cap is critical to the proper opera-

tion of the duct smoke detector. The end cap is needed to create 
the proper air flow to the sensor of the duct smoke detector.

NOTE:

 For ducts greater than 1

1

2

 feet in width, refer to sections 

[5.4.1] and [5.4.2].

Figure 2. Plastic sampling tube
connected to duct smoke detector:

Summary of Contents for DH100ACDCI

Page 1: ...hut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashes to indicate power a red LED signals local alarm indication and optional accessories offer a variety of annuncia tion capabilities The ...

Page 2: ...les as indi cated in Figure 4 D100 68 00 2 I56 1684 007R 4 Figure 1 Exploded View Of Duct Smoke Detector Components FOAM GASKETS PLASTIC SAMPLING TUBE CONDUIT HOLES DETECTOR HOUSING TERMINAL STRIP DETECTOR COVER SAMPLING TUBE FILTERS PLASTIC SAMPLING TUBE SELF TAPPING SCREW POWER BOARD DETECTOR BOARD COVER MOUNTING SCREWS H0401 00 H0110 00 5 Installation Sequence 5 1 Verify Duct Air Flow Direction...

Page 3: ...t the end opposite the duct smoke detector Figure 5 Tube mounting configurations with varying air flow direction AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONT...

Page 4: ... between interconnected detectors or from detectors to auxiliary devices it is usually recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in t...

Page 5: ... RTS451KEY is not required when these accessories are used with the DH100ACDCI detectors The functionality of the magnetic coil has been designed into the circuitry of the new In novair duct smoke detectors 6 2 2 3 SSK451 Multi Signaling Accessory The System Sensor SSK451 Multi Signaling accessory combines a sounder feature with a key activated test and reset function Green amber and red LEDs prov...

Page 6: ...S ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM 5 VDC 1 4 HP 240 VAC 1 8 HP 120 VAC NOT INTENDED FOR CONNECTION TO CONTROL PANELS TROUBLE CONTACT RATING 2 0 A 30 VDC resistive 2 0 A 125 VAC resistive 120 VAC CAUTION Do not loop wire under termin...

Page 7: ...ination of accessories may be used such that the given accessory loads are 60 mA or less in the standby state 110 mA or less in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1684 007R Figure 11 Wiring diagrams for optional accessories H0402 01 15 ALARM SIGNAL 3 14 2 RESET 11 TEST 20 AUX POWER 19 AUX POWER SSK451 FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SUPERVISORY CONTACT NO ...

Page 8: ...60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2 0A 125 VAC resistive Note Alarm auxiliary c...

Reviews: