background image

[6.1.3] Filter Replacement

The  filters  do  not  substantially  affect  smoke  performance  even 
when up to 90% of the filter is clogged. Quarterly visual inspec-
tion  usually  suffices  to  determine  whether  the  filters  should  be 
replaced because only a high percentage of contamination affects 
performance.  If  further  testing  is  required,  compare  differential 
pressure  readings  with  and  without  the  filters  installed.  If  the 
difference exceeds 10% replace the filters. In no case should the 
pressure differential fall below 0.03 inches of water.

[6.2] Standby, Alarm, And Sensitivity Tests
[6.2.1] Standby And Trouble

Standby — 

 Look for the presence of the flashing green LED 
through the transparent housing cover. The LED 
should flash approximately every 10 seconds.

Trouble — 

 If  the  detector  LED  does  not  flash,  then  the 
detector  lacks  power  (check  wiring,  panel,  or 
power  supply),  the  detector  board  is  missing 
(replace), the cover has been missing or not se-
cured properly for more than 7 minutes (secure 
cover properly), or the unit is defective (return 
for repair).

Test —   

 The trouble condition can be caused intentionally 
to verify correct operation of the system. Remove 
the detector board to cause a trouble condition 
locally and at the system control panel.

Cover Tamper —   If the cover is removed or not properly secured 

for a period longer than 7 minutes, a trouble sig-
nal is generated to indicate the cover is missing.

[6.2.2] Alarm Tests
[6.2.2.1] M02-04-00 Magnet Test

1.   Place the painted surface of the magnet onto the TEST locator 

on the bottom of the housing (

Figure 13

). 

2.   The red alarm LED on the detector should latch on, as should 

any accessories (i.e. RA400Z, RTS451). Verify system control 
panel alarm status and control panel execution of all intended 
auxiliary functions (i.e. fan shutdown, damper control, etc.).

3.   The  detector  must  be  reset  by  system  control  panel,  front 

cover reset button, or remote accessory.[6.2.2.2] RTS451/RTS-
451KEY Remote Test Station

The RTS451/RTS451KEY Remote Test Station facilitates test of the 
alarm  capability  of  the  duct  smoke  detector  as  indicated  in  the 
RTS451/RTS451KEY manual. The DH100ACDCI duct smoke detec-
tor  can  be  reset  by  the  RTS451/RTS451KEY.  If  a  system  control 
panel is used, the panel itself may also require testing.
To install the RTS451/RTS451KEY, connect the device as shown in 

Figure 9

; wire runs must be limited to 25 ohms or less per inter-

connecting wire. 

Please  note  that  the  magnetic  coil  supplied  with  the  RTS451 
and  RTS451KEY  is  not  required  when  these  accessories  are 
used with the DH100ACDCI detectors.

 The functionality of the 

magnetic coil has been designed into the circuitry of the new In-
novair™ duct smoke detectors.

[6.2.2.3] SSK451 Multi-Signaling Accessory

The  System  Sensor  SSK451  Multi-Signaling  accessory  combines 
a  sounder  feature  with  a  key  activated  test  and  reset  function. 
Green, amber, and red LEDs provide a visual indication of power, 
trouble, and alarm respectively. An optional strobe (PS24LO) with 
a  smoke  lens  can  be  added  to  conform  to  the  codes  of  certain 
jurisdictions.
To install the SSK451, connect the device as shown in 

Figure 12

.

[6.2.3] Sensitivity Tests
[6.2.3.1] MOD400 or MOD400R Test 

After verification of alarm capability, use the MOD400R test mod-
ule with a voltmeter to check detector sensitivity as indicated in 
the test module’s manual. The housing cover must be removed to 
perform this test.
If test module readings indicate that the detector head is outside of 
the acceptable range that is printed on the label of the detector, the 
detector chamber requires cleaning per Section [7] of this manual.

[7] Detector Cleaning Procedures

Notify  the  proper  authorities  that  the  smoke  detector  system  is 
undergoing maintenance, and that the system will temporarily be 
out  of  service.  Disable  the  zone  or  system  undergoing  mainte-
nance to prevent unwanted alarms and possible dispatch of the 
fire department.

[7.1] Air Filters

1.  Turn off power to the system.
2.  Remove and inspect sampling tube filters.
3.   If  filters  are  heavily  coated  with  dirt,  replace  them  with  new 

filters. If they are not heavily coated, use a vacuum cleaner or 
compressed air nozzle to remove dust, then reinstall the filters. 

[7.2] Ion Detector Boards 

1.   Brush or vacuum inside area of cover. Chamber may then be 

blown out using clean, compressed air. 

2.   Vacuum sensing chamber before using clean, compressed air 

to loosen and blow out any remaining debris. 

[8.0] Board Replacement
[8.1] Detector Board Replacement (part no. A5052)

1.  Remove the two detector board mounting screws.
2.  Pull gently on the board to remove it. 
3.   To replace the board, align the board mounting features, holes, 

and the interconnect terminals. Push the board into place.

4.  Secure board with the two mounting screws.

[8.2] Power Board replacement (part no. A5064)

1.  Disconnect wiring from the terminal block.
2.  Remove the two power board mounting screws.
3.  Pull gently on the board to remove it. 
4.   To replace the board, align the board mounting features, holes, 

and the interconnect terminals. Push the board into place.

5.  Secure board with the two mounting screws.
6.  Re-connect wiring to terminal block.

D100-68-00 

I56-1684-007R

Summary of Contents for DH100ACDCI

Page 1: ...hut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashes to indicate power a red LED signals local alarm indication and optional accessories offer a variety of annuncia tion capabilities The ...

Page 2: ...les as indi cated in Figure 4 D100 68 00 2 I56 1684 007R 4 Figure 1 Exploded View Of Duct Smoke Detector Components FOAM GASKETS PLASTIC SAMPLING TUBE CONDUIT HOLES DETECTOR HOUSING TERMINAL STRIP DETECTOR COVER SAMPLING TUBE FILTERS PLASTIC SAMPLING TUBE SELF TAPPING SCREW POWER BOARD DETECTOR BOARD COVER MOUNTING SCREWS H0401 00 H0110 00 5 Installation Sequence 5 1 Verify Duct Air Flow Direction...

Page 3: ...t the end opposite the duct smoke detector Figure 5 Tube mounting configurations with varying air flow direction AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONT...

Page 4: ... between interconnected detectors or from detectors to auxiliary devices it is usually recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in t...

Page 5: ... RTS451KEY is not required when these accessories are used with the DH100ACDCI detectors The functionality of the magnetic coil has been designed into the circuitry of the new In novair duct smoke detectors 6 2 2 3 SSK451 Multi Signaling Accessory The System Sensor SSK451 Multi Signaling accessory combines a sounder feature with a key activated test and reset function Green amber and red LEDs prov...

Page 6: ...S ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM 5 VDC 1 4 HP 240 VAC 1 8 HP 120 VAC NOT INTENDED FOR CONNECTION TO CONTROL PANELS TROUBLE CONTACT RATING 2 0 A 30 VDC resistive 2 0 A 125 VAC resistive 120 VAC CAUTION Do not loop wire under termin...

Page 7: ...ination of accessories may be used such that the given accessory loads are 60 mA or less in the standby state 110 mA or less in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1684 007R Figure 11 Wiring diagrams for optional accessories H0402 01 15 ALARM SIGNAL 3 14 2 RESET 11 TEST 20 AUX POWER 19 AUX POWER SSK451 FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SUPERVISORY CONTACT NO ...

Page 8: ...60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2 0A 125 VAC resistive Note Alarm auxiliary c...

Reviews: