background image

w w w . i n n o v a i r . c o m

 

Technical Information

SERVICE MANUAL

Outdoor

Unit

Cross-sectional Area of Power Cable Conductor

sq in

0.0062 

0.0062 

 

3

 

3

N

)

e

r

o

C

(

e

l

b

a

C

 r

e

w

o

P

 

d

e

d

n

e

m

m

o

c

e

R

n

o

it

c

e

n

n

o

C

 

e

r

a

l

F

n

o

it

c

e

n

n

o

C

 

e

r

a

l

F

-

d

o

h

t

e

M

 

n

o

it

c

e

n

n

o

C

 

e

p

i

P

 

n

o

it

c

e

n

n

o

C

Not Additional Gas Connection Pipe Length

ft

131.2 

131.2 

 

2

.

0

 

2

.

0

.t

f/

z

o

e

g

r

a

h

C

 l

a

n

o

it

i

d

d

A

 

s

a

G

 

e

p

i

P

 

n

o

it

c

e

n

n

o

C

Outer Diameter of  Liquid Pipe

 

1

4

/

1

4

/

1

h

c

n

i

Outer Diameter of  Liquid Pipe

 

2

4

/

1

4

/

1

h

c

n

i

Outer Diameter of  Liquid Pipe

 

3

4

/

1

4

/

1

h

c

n

i

Outer Diameter of  Liquid Pipe

 

4

4

/

1

4

/

1

h

c

n

i

Outer Diameter of  Liquid Pipe

 

4

4

/

1

4

/

1

h

c

n

i

Outer Diameter of  Gas Pipe

 

1

8

/

3

8

/

3

h

c

n

i

Outer Diameter of  Gas Pipe

 

2

8

/

3

8

/

3

h

c

n

i

Outer Diameter of  Gas Pipe

 

3

8

/

3

8

/

3

h

c

n

i

Outer Diameter of  Gas Pipe

 

4

8

/

3

8

/

3

h

c

n

i

Outer Diameter of  Gas Pipe

 

4

8

/

3

8

/

3

h

c

n

i

Connection Pipe Max. Height Distance(indoor and 
indoor)

 

6

.

4

2

 

6

.

4

2

tf

Connection Pipe Max. Height Distance(indoor and 
outdoor and indoor up)

 

2

.

9

4

 

2

.

9

4

tf

Connection Pipe Max. Height Distance(indoor and 
outdoor and outdoor up)

 

2

.

9

4

 

2

.

9

4

tf

Max. equivalent connection pipe length(outdoor to 
last indoor)

 

0

.

2

8

 

0

.

2

8

tf

Connection Pipe Max. Length Distance(total lenght)

ft

246.1 

246.1 

The above data is subject to change without notice; please refer to the nameplate of the unit.

8

Summary of Contents for MULTI-MAX VOM0847H7RE605

Page 1: ...rvice technician familiar with safety procedures and equipped with the proper tools and test instruments Installation or repairs made by unqualified persons can result in hazards to you and others Failure to carefully read and follow all instructions in this manual can result in equipment malfunction property damage personal injury and or death This manual is only for licensed technicians only WAR...

Page 2: ...reparation before Installation 26 8 2 Installation Instruction 28 9 Troubleshooting 38 9 1 Malfunction Indicator 38 9 2 Malfunction Checking and Elimination 39 9 3 Maintenance Method for Normal Malfunction 45 10 Exploded View and Parts List 47 11 Removal Procedure 53 Appendix 71 Appendix 1 Reference Sheet of Celsius and Fahrenheit 71 Appendix 2 Pipe Expanding Method 71 Appendix 3 List of Resistanc...

Page 3: ...Technical Information SERVICE MANUAL 1 Summary Part I Technical Information Outdoor Unit VOM0522H7RE602 VOM0733H7RE603 VOM0833H7RE604 1 ...

Page 4: ...w w w i n n o v a i r c o m Technical Information SERVICE MANUAL VOM0836H7RE605 VOM0847H7RE605 2 ...

Page 5: ... o r h T Cooling Operation Ambient Temperature Range O 8 1 1 0 8 1 1 0 F Heating Operation Ambient Temperature Range O 6 8 4 2 5 7 1 3 F e b u T r e p p o c n i F m u n i m u l A e b u T r e p p o c n i F m u n i m u l A l a i r e t a M r e s n e d n o C Condenser Pipe Diameter inch 6 1 5 Φ 6 1 5 Φ 6 1 1 2 6 1 1 2 h c n i m m p a G n i F s w o R Coil length l X height H X coil width L inch 38 21 3...

Page 6: ...r of Liquid Pipe 2 4 1 4 1 h c n i Outer Diameter of Liquid Pipe 3 h c n i Outer Diameter of Liquid Pipe 4 h c n i Outer Diameter of Gas Pipe 1 8 3 8 3 h c n i Outer Diameter of Gas Pipe 2 8 3 8 3 h c n i Outer Diameter of Gas Pipe 3 h c n i Outer Diameter of Gas Pipe 4 h c n i Connection Pipe Max Height Distance indoor and indoor 2 6 2 2 6 2 t f Connection Pipe Max Height Distance indoor and outd...

Page 7: ... n i l t t o r h T Cooling Operation Ambient Temperature Range O 8 1 1 0 F Heating Operation Ambient Temperature Range O 6 8 4 F e b u T r e p p o c n i F m u n i m u l A l a i r e t a M r e s n e d n o C Condenser Pipe Diameter inch Φ5 16 6 1 1 2 h c n i m m p a G n i F s w o R Coil length l X height H X coil width L 4 6 3 1 2 1 X 6 1 7 9 2 X 6 1 7 7 2 h c n i 0 3 6 m p r L M H m p r d e e p S r ...

Page 8: ...pe 2 4 1 h c n i Outer Diameter of Liquid Pipe 3 4 1 h c n i Outer Diameter of Liquid Pipe 4 4 1 h c n i Outer Diameter of Gas Pipe 1 8 3 h c n i Outer Diameter of Gas Pipe 2 8 3 h c n i Outer Diameter of Gas Pipe 3 8 3 h c n i Outer Diameter of Gas Pipe 4 8 3 h c n i Connection Pipe Max Height Distance indoor and indoor 6 4 2 t f Connection Pipe Max Height Distance indoor and outdoor and indoor u...

Page 9: ...t t o r h T Cooling Operation Ambient Temperature Range O 8 1 1 0 8 1 1 0 F Heating Operation Ambient Temperature Range O 6 8 4 6 8 4 F e b u T r e p p o c n i F m u n i m u l A e b u T r e p p o c n i F m u n i m u l A l a i r e t a M r e s n e d n o C h c n i r e t e m a i D e p i P r e s n e d n o C 6 1 5 Φ 6 1 5 Φ 6 1 1 2 6 1 1 2 h c n i m m p a G n i F s w o R Coil length l X height H X coil ...

Page 10: ...n i Outer Diameter of Liquid Pipe 4 4 1 4 1 h c n i Outer Diameter of Liquid Pipe 4 4 1 4 1 h c n i Outer Diameter of Gas Pipe 1 8 3 8 3 h c n i Outer Diameter of Gas Pipe 2 8 3 8 3 h c n i Outer Diameter of Gas Pipe 3 8 3 8 3 h c n i Outer Diameter of Gas Pipe 4 8 3 8 3 h c n i Outer Diameter of Gas Pipe 4 8 3 8 3 h c n i Connection Pipe Max Height Distance indoor and indoor 6 4 2 6 4 2 t f Conne...

Page 11: ...apacity W 6400 6380 7950 8550 10650 11080 Total power input W 3150 2500 3130 3200 3400 2930 Sensitive capacity W Total capacity W 100 100 100 100 100 100 Cooling Heatling 2 2 Cooling Capacity Tables ROOM MODEL 18 24 30K CONNECTIVE INDOOR UNIT 9K High Wall 2 12K High Wall 1 OUTDOORTEMPERATURE DRY INDOOR TEMPERATURE 20O C 68O F 25O C 77O F 30O C 86O F 35O C 95O F 40O C 104O F 45O C 113O F 21O C 70O ...

Page 12: ...0580 11300 Sensitive capacity W 8460 8800 9360 10690 10580 11300 Total power input W 3785 3600 3410 3580 2780 2420 Sensitive capacity W Total capacity W 100 100 100 100 100 100 Heatling ROOM MODEL 36K CONNECTIVE INDOOR UNIT 9K High Wall 4 OUTDOOR TEMPERATURE DRY INDOOR TEMPERATURE 20O C 68O F 25O C 77O F 30O C 86O F 35O C 95O F 40O C 104O F 45O C 113O F 21O C 70O F D 15O C 59O F W Total capacity W...

Page 13: ...820 11400 Total power input W 3760 3690 3400 3910 2820 2420 Sensitive capacity W Total capacity W 100 0 100 0 100 0 100 0 100 0 100 0 ROOM MODEL 42K CONNECTIVE INDOOR UNIT 9K High Wall 2 12K High Wall 2 OUTDOOR TEMPERATURE DRY INDOOR TEMPERATURE 20O C 68O F 25O C 77O F 30O C 86O F 35O C 95O F 40O C 104O F 45O C 113O F 21O C 70O F D 15O C 59O F W 0 0 8 6 0 4 6 8 0 0 9 9 0 0 7 0 1 0 2 3 0 1 5 7 6 9 ...

Page 14: ...cal Information SERVICE MANUAL 3 Outline Dimension Diagram VOM0836H7RE605 VOM0847H7RE605 VOM0833H7RE604 Unit inch 40 42 1 2 24 13 16 17 21 64 14 1 4 14 51 64 43 27 64 38 27 64 36 7 32 16 21 64 14 37 64 31 13 64 24 15 23 32 Unit inch 12 ...

Page 15: ...Technical Information SERVICE MANUAL VOM0522H7RE605 VOM0733H7RE603 Unit inch 39 9 16 36 7 32 16 21 64 14 37 64 31 13 64 24 15 23 32 13 ...

Page 16: ...3 Electronic expansion valve A Flash vaporizer Unloading valve Outdoor evaporator 4 way valve Solenoid valve high pressure Solenoid valve low pressure Air injection Compressor Variable volume Gas liquid separator Gas liquid separator COOLING HEATING Heat Exchanger Heat Exchanger Heat Exchanger Heat Exchanger Heat Exchanger Indoor Uint Electronic Expansion Valve Outdoor Uin 14 ...

Page 17: ...oor air and then is turned into refrigerant liquid After passing through the throttling device the temperature and pressure of the refrigerant liquid will further decrease and then go the main valve After that it will be divided and go to the heat exchanger of each indoor unit to exchange heat with the air which needs to be conditioned Consequently the refrigerant liquid become low temperature low...

Page 18: ...lectrical Part 5 1 Wiring Diagram Symbol Symbol Color Symbol Symbol Color Symbol Name WH White GN GREEN COMP Compressor YE Yellow BN Brown Grouding wire RD Red BU Blue YEGN Yellow Green BK Black VT Violet OG Orange Outdoor Unit Instruction VOM0833H7RE604 63624100019 16 ...

Page 19: ...Technical Information SERVICE MANUAL VOM0733H7RE603 600007060491 60000706049101 VOM0522H7RE602 17 ...

Page 20: ... n n o v a i r c o m Technical Information SERVICE MANUAL VOM0836H7RE605 VOM0847H7RE605 These circuit diagrams are subject to change without notice please refer to the one supplied with the unit 63624100020 18 ...

Page 21: ...ressure switch 8 EVA EVE terminals of EXV electronic expansion valve 9 CN802 CN803 terminals of temperature sensor 10 COMU terminals of communication 11 OFAN terminals of fan 12 4WAY terminals of 4 way valve 13 HEAT terminals of compressor band heater 14 HEAT1 terminals of bottom band heater 15 K101 Main relay 16 L4 L5 choke 1 2 4 3 5 6 7 8 9 0 1 11 2 1 4 1 3 1 15 16 5 2 PCB Printed Diagram All mo...

Page 22: ...rface of temperature sensor 7 Terminal of electronic expansion valve 8 Interface of fan 9 Interface of electric heating for chassis 10 Interface of electric heating for compressor 11 Terminal of low pressure 2 way valve 12 Terminal of 2 way valve 13 Terminal of 4 way valve 14 Terminal of high pressure 2 way valve 15 Terminal of communication wire 16 Terminal of neutral wire 17 Terminal of live wir...

Page 23: ...is mode is the same as cooling mode 3 Heating mode a Turning on the unit for heating operation If any one of the indoor unit satisfy the heating condition the system will start to run in heating mode b If all the indoor units satisfy the stop condition the compressor stops and the outdoor fan stops after 1min c If only part of the indoor units satisfy the stop condition the compressor decrease the...

Page 24: ...er than limit then the high pressure switch cuts off the system will stop to run b If high pressure protection is detected for one time only by cutting off the power and then reenergize that the compressor can restart 6 Compressor overload protection No matter the compressor is on or off when the compressor overload switch is detected activated the system will stop and indoor unit will display H3 ...

Page 25: ...d part to prevent the water leakage electric shock and fire accidents Wire size of power cord should be large enough The damaged power cord and connection wire should be replaced by exclusive cable Never fail to comply with the nitrigen charge requirements Charge nitrogen when welding pipes Please firstly connect the wired controller before energization otherwise wired controller can not be used I...

Page 26: ...eter measuring tape 4 Electroprobe 7 Electronic leakage detector 10 Pipe pliers pipe cutter 2 Screw driver 5 Universal meter 8 Vacuum pump 11 Pipe expander pipe bender 3 Impact drill drill head electric drill 6 Torque wrench open end wrench inner hexagon spanner 9 Pressure meter 12 Soldering appliance refrigerant container 24 ...

Page 27: ...the bound pipes pass through the wall hole and then connect outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installation Note this flow is only for reference please find the more detailed installation steps in this section Select outdoor unit installation location Install the support of outdoor unit select it according to the ac...

Page 28: ...jury or property damage Install the unit at a place where is adequa to withstand the weight of the unit and make sure the unit would not shake or fall off Try to keep the unit away from corrosive gas or exhaust gas Leave some space for heat exchanging and servicing so as to guarantee unit normal operation Never allow children to approach to the unit and take measures to prevent children touching t...

Page 29: ... of pipe 0 5 1 0 mm bearing pressure 3 0MPa The longer the connection pipe is the more cooling and heating capacity will decrease 19 2 3 39 3 8 78 3 4 19 2 3 19 2 3 19 2 3 78 3 4 unit inch M odel Connecting Pipe inch M ax Pipe length ft M ax Height Difference betw een Indoor Unit and Outdoor Unit ft Liquid Gas Ф 1 4 3 8 3 8 3 8 1 4 1 4 Φ 229 6 Ф 1 4 3 8 Φ 164 24 30K 18K 36K 42K Ф Ф 246 1 246 1 Ф Ф...

Page 30: ...h clean the air conditioner cabinet Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube OUTDOOR UNIT No Description 1 Air outlet grille 2 Valve diagram of the appliance and may not correspond to the appearance...

Page 31: ... if the piping and wiring are correct to avoid water leakage Safety Precautions Please read this manual carefully before using and operating correctly as instructed in this manual Please especially take notice of the following two symbols Warning It indicates improper operation which will lead to human casualty or severe injury Caution It indicates improper operation which will lead to injury or p...

Page 32: ...then wet the household wares in the room Under the occurrence of an error like burning smell etc please cut off the main power supply of the unit Please take notice of the supporting frame of the unit to see if it is damaged over the long time period of use or relocation of the unit Non professional personnel are prohibited to dismantle the electric box owing to the high voltage of the outdoor uni...

Page 33: ...isconnection switch having a contact separation of at least 3mm in all poles should be Caution nameplate and also check its security Before using the unit please check if the piping and wiring are correct to avoid water leakage Safety Precautions Please read this manual carefully before using and operating correctly as instructed in this manual Please especially take notice of the following two sy...

Page 34: ...3H7RE604 Outline dimension and Mounting holes VOM0836H7RE605 VOM0847H7RE605 Outline dimension and Mounting holes 31 7 64 13 25 32 3 21 64 14 39 64 15 23 32 16 51 64 11 3 4 24 38 27 64 6 7 64 43 27 64 17 23 32 3 37 64 11 7 64 17 21 64 14 13 64 42 1 2 24 53 64 7 1 2 Fig 2 Fig 3 32 ...

Page 35: ...refrigerant pipe never pull any joints of the indoor unit by force otherwise the capillary pipe or other pipe may crack which then would result in leakage The refrigerant pipe should be supported by brackets that is don t let the unit withstand the weight of it If the piping connection size of outdoor unit does not match the piping connection size of indoor unit use the piping connection dimension...

Page 36: ...ght a b c d e 131 2ft 131 2ft 131 2ft Allowable Value Fitting pipe Total length actual length of fitting pipe length of farthest fitting pipe ft VOM0833H7RE604 Outdoor unit at upper Outdoor unit at lower Height difference between indoor units ft Height difference between outdoor unit and indoor unit b a e d c L4 L3 L2 L5 L1 Outdoor uni t Height difference between indoor unit and outdoor unit H1 He...

Page 37: ...ainage meanwhile it should be insulated to prevent condensing otherwise the improper installation would cause water leakage and then wet the household wares in the room Under the occurrence of an error like burning smell etc please cut off the main power supply of the unit Please take notice of the supporting frame of the unit to see if it is damaged over the long time period of use or relocation ...

Page 38: ...he electric installation should be carried out by the technician as instructed by the loc al laws regulations and also this manual The diameter of the power cord should be large enough and once it is damaged it must be replaced by the dedicated one The earthing should be reliable and the earth wire should be connected to the dedicated device of the building by the technician Besides the air switch...

Page 39: ...hould connect well according to the instruction The electric installation should be carried out by the technician as instructed by the local laws regulations and also this manual The installation location should be dry and can t be expose in direct sunlight or strong breeze Have to install a breaker in the circuit that can shut off the main power supply of the system Besides the air switch coupled...

Page 40: ...nction Flash 5 times F4 Exhaust sensor malfunction Flash 7 times F5 Attain the temperature of switch on Flash 8 times Frequency limit power Flash 13 times Outdoor fan malfunction Flash 14 times Frequency limit PFC module temperature Flash 15 times PFC module sensor malfunction Flash 16 times oE Liquid pipe temperature sensor malfunction of A Flash 17 times Gas pipe temperature sensor malfunction o...

Page 41: ...Reconnect according to the wiring diagram Y N Y De energize change the communication wire of the well communicated indoor unit and malfunction indoor unit then energize the unit and wait for 3min The malfunction indoor unit resumes normal Replace outdoor mainboard Replace the mainboard of the malfunction indoor unit Malfunction display E6 Communication malfunction 9 2 Malfunction Checking and Elim...

Page 42: ...x is connected correctly Connected correctly Reconnect according to the wiring diagram Connected correctly Reconnect according to the wiring diagram De energize check if the connection wire between the outdoor mainboard and the filter board according to the wiring diagram The connection wire is broken Replace the connection wire Check if there is power input bewtweenthenetrualwireandlive wire of t...

Page 43: ...the outdoor unit mainboard Replace pressure switch Check if operation mode of indoor unit is properly set N N Y Y Y Y Check if gas valve and liquid valve are completely open Refer to Instruction Manual of indoor unit Check if the panel of outdoor unit is firmly closed N N Completely open the valve Close the panel Check if the air return and supply from heat exchanger of indoor unit and outdoor uni...

Page 44: ... Replace relevant discharge temperature sensor Discharge temperature protection Malfunction display E5 Compressor Overheat N Y Y Y Y Y N N N Check if compressor s connection line is properly connected Adjust compressor s connection line Check if current value is higher than the protector s setting Replace overcurrent protector If unit s high pressure is normal l Refer to high pressure protection I...

Page 45: ...heck if the plug of the temperature sensor is correctly connected with socket on the mainboard N Removethe sensor to check if the resistance value is ok N Y Y Y Replace mainboard of the indoor uint Check the direction of the plug and socket Replace temperature sensor Failure of condenser Temp sensor 43 ...

Page 46: ...k if the resistance value is ok Replace mainboard of the indoor uint Replace temperature sensor Check the direction of the plug and socket Malfunction display F5 Failure of Exhaust Temp Sensor N N Y Y Y Failure of Exhaust Temp sensor Check if the plug of the temperature sensor is correctly connected with socket on the mainboard Remove the sensor to check if the resistance value is ok Replace mainb...

Page 47: ...or details Malfunction of compressor Compressor can t operate Refer to point 5 of maintenance method for details 9 3 Maintenance Method for Normal Malfunction 1 Air Conditioner Can t be Started Up 2 Poor Cooling Heating for Air Conditioner 3 Horizontal Louver Can t Swing Possible Causes Discriminating Method Air conditioner Status Troubleshooting No power supply or poor connection for power plug A...

Page 48: ...drain pipe Drain pipe is broken Water leaking from drain pipe Replace drain pipe Wrapping is not tight Water leaking from the pipe connection place of indoor unit Wrap it again and bundle it tightly 5 Compressor Can t Operate Possible causes Discriminating method air conditioner status Troubleshooting Wrong wire connection or poor connection Check the wiring status according to circuit diagram Con...

Page 49: ... 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 10 Exploded View and Parts List The component picture is only for reference please refer to the actual product 47 ...

Page 50: ...b assy 01264100034 1 23 Handle Assy 02204100008 1 24 Right Side Plate 0131410000901P 1 25 Electric Expand Valve Fitting 4304413234 1 26 Electric Expand Valve Fitting 4304413235 1 27 Wiring Clamp 26115004 1 28 Electric Expand Valve Fitting 4304413237 1 29 Bidirection Strainer 07220016 1 30 Gas liquid Separator Assy 07225017 1 31 Reactor 43130186 1 32 Rear Grill 01574100003 1 33 Clapboard 0124410000...

Page 51: ...605 VOM0847H7RE605 55 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 4 5 49 50 51 52 53 The component picture is only for reference please refer to the actual product 49 ...

Page 52: ...e Fitting 4300876704 4304413234 1 25 Right Side Plate 0131410002701P 0131410002701P 1 26 Wiring Cover Sub assy 01264100034 01264100034 1 27 Handle Assy 02204100008 02204100008 1 28 Wiring Clamp 26115004 26115004 1 29 Cut off Valve 07130239 071302391 1 30 Electric Expand Valve Fitting 4300876717 4304413235 1 31 Rear Grill 01574100007 01574100007 1 32 Condenser Assy 01124100116 01124100116 1 33 Cond...

Page 53: ... Installation and Maintenance VOM0522H7RE602 VOM0733H7RE603 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 The component picture is only for reference please refer to the actual product 51 ...

Page 54: ...e Assy 030152060055 030152060055 1 11 Valve Support Assy 030163060001 030163060003 1 12 Right Side Plate 0131410000902P 0131410000902P 1 13 Handle 26233053 26233053 1 14 Valve Cover 200087000006 200087000006 1 15 Rear Grill 01574100003 01574100003 1 16 Condenser Assy 011002060151 011002060151 1 17 Clapboard Sub Assy 017021060037 017021060037 1 18 Motor Support Sub Assy 017012000017 017012000017 1 ...

Page 55: ...ve front side plate front side plate Remove the screws connecting the front side plate with chassis and middle isolation sheet and then remove the front side plate Note Take VOM0833H7RE604 handle Remove the screws connicting the handle with right side plate and then remove the handle 11 Removal Procedure Warning Be sure to wait for a minimum of 20 minutes after turning off all power supplies and d...

Page 56: ...and left side plate and then remove the rear guard grille Remove the screws connecting the right side plate with electric box assy valve support chassis and condenser side plate and then remove the right side plate Remove the 4 screws connecting the grille and outer case and then remove the panel grille 4 Remove rear guard grille 5 Remove right side plate 6 Remove grille and cabinet cabinet 54 ...

Page 57: ...g terminals of reactor compressor high and low pressure switch compressor overload protector temperature sensor Note keep pressing the circlip when disconnecting the wiring terminal of reactor keep pressing the retainer when disconnecting other wiring terminals 3 Remove the wire inside the wiring groove 7 Remove outer case 8 Remove electric box assy 9 Remove blade motor motor support reactor 2 Rem...

Page 58: ...ot weld wrap the 4 way valve with wet cloth completely to avoid damage to valve due to high temperature Unsolder all spot welds connected with valve support and then remove the valve support Note When unsoldering the spot weld wrap the gas valve and liquid valve with wet cloth completely to avoid damage to valve due to high temperature Remove all spot welds connected with connection pipe and then ...

Page 59: ...of condenser chassis and then remove the middle isolation sheet 13 Remove compressor compressor the compressor upwards to remove the compressor and damping cushion Note Keep the ports of discharge pipe and suction pipe from foreign objects support and then remove the reactor sub assy 14 Remove the reactor reactor 1 5 Remove middle isolation sheet 57 ...

Page 60: ...and chassis and then remove the condenser Remove 2 screws connecting support plate of condenser and condenser and then remove the support plate of condenser 16 Remove left side plate 17 Remove condenser Remove screws connecting left side plate and support plate of condenser chassis and then remove the left side plate left side plate support plate of condenser 58 ...

Page 61: ...le and valve cover 2 Remove top cover 3 Remove front side plate front side plate Remove the screws connecting the front side plate with chassis and middle isolation sheet and then remove the front side plate VOM0522H7RE602 VOM0733H7RE603 handle valve cover Remove the screws connicting the handle with right side plate and then remove the handle Remove the screws connicting the valve cover and then ...

Page 62: ...de plate and blade 4 Remove grille and cabinet cabinet Remove nuts fixing axial flow blade with wrench blade electric box assy 1 Remove the grounding wire screw on the electric box assy and then remove the grounding wire 2 Disconnect the wiring terminals of reactor compressor high and low pressure switch compressor overload protector temperature sensor Note keep pressing the circlip when disconnec...

Page 63: ...motor motor Remove 2 screws connecting motor support and chassis loosen damper block and then remove the motor support 4 way valve Unsolder the spot weld between 4 way valve and vapour liquid separator compressor cut off valve sub assy and condenser and then remove the 4 way valve Note When unsoldering the spot weld wrap the 4 way valve with wet cloth completely to avoid damage to valve due to hig...

Page 64: ...welds inhalation tube sub assy and then remove the inhalation tube sub assy 11 Remove electromagnetic valve sub assy and inhalation tube sub assy Unsolder all spot welds cflash vaporizer assy and valve support Unsolder all spot welds connected with valve support and then remove the valve support Note When unsoldering the spot weld wrap the gas valve and liquid valve with wet cloth completely to av...

Page 65: ... upwards to remove the compressor and damping cushion Note Keep the ports of discharge pipe and suction pipe from foreign objects 15 Remove middle isolation sheet 14 Remove vapour liquid separator Unsolder spot welds connected with vapour liquid separator remove 2 foot nuts fixing vapour liquid separator and compressor mounting plate sub assy and then remove the vapour liquid separator vapour liqu...

Page 66: ...pport plate of condenser chassis and then remove the left side plate left side plate support plate of condenser 17 Remove compressor mounting plate sub assy plate sub assy and chassis to remove the compressor mounting plate sub assy compressor mounting plate sub assy condenser chassis Pull it upwards to separate the chassis and condenser 18 Remove condenser 64 ...

Page 67: ...the top cover upwards to remove it 1 Remove the handle 2 Remove top cover 3 Remove front side plate front side plate Remove the screws connecting the front side plate with chassis and middle isolation sheet and then remove the front side plate VOM0836H7RE605 VOM0847H7RE605 handle Remove the screws connicting the handle with right side plate and then remove the handle 65 ...

Page 68: ... remove the right side plate Remove the 4 screws connecting the grille and outer case and then remove the panel grille 5 Remove right side plate 6 Remove grille and cabinet cabinet outer case Remove screws connecting outer case and motor support middle isolation sheet and chassis pull the outer case upwards slightly loosen clasps between outer case and right side plate left side plate and then rem...

Page 69: ...ve the wire inside the wiring groove 8 Remove electric box assy 9 Remove blade motor motor support reactor 2 Remove 2 screws connecting motor support and chassis loosen damper block and then remove the motor support 3 Remove 4 screws fixing motor and then remove the motor 4 Remove 4 screws fixing reactor sub assy and motor support and then remove the reactor sub assy Unsolder the spot weld between...

Page 70: ...ld wrap the gas valve and liquid valve with wet cloth completely to avoid damage to valve due to high temperature Remove all spot welds connected with connection pipe and then remove the connection pipe sub assy 11 Remove valve support 12 Remove connection pipe sub assy compressor 13 Remove compressor the compressor upwards to remove the compressor and damping cushion Note Keep the ports of discha...

Page 71: ...nsolder spot welds connected with vapour liquid separator remove 2 foot nuts fixing vapour liquid separator and compressor mounting plate sub assy and then remove the vapour liquid separator 15 Remove compressor mounting plate sub assy Remove the 4 foot nuts fixing compressor mounting plate sub assy and chassis to remove the compressor mounting plate sub assy vapour liquid separator compressor mou...

Page 72: ...er and condenser and then remove the support plate of condenser 18 Remove left side plate 19 Remove condenser Remove screws connecting left side plate and support plate of condenser chassis and then remove the left side plate left side plate support plate of condenser middle isolation sheet Remove screws connecting middle isolation sheet and support plate of condenser chassis and then remove the m...

Page 73: ...51 8 11 75 76 75 2 24 99 98 6 37 54 53 6 12 77 78 77 25 Fahrenheit display temperature Fahrenheit Celsius Fahrenheit display temperature Fahrenheit Celsius Fahrenheit display temperature Fahrenheit Celsius 61 60 8 16 69 70 69 8 21 78 79 78 8 26 62 63 62 6 17 71 72 71 6 22 80 81 80 6 27 64 65 64 4 18 73 74 73 4 23 82 83 82 4 28 66 67 66 2 19 75 76 75 2 24 84 85 84 2 29 68 68 20 77 77 25 86 86 30 Do...

Page 74: ... according to the steps above The length is equal Improper expanding leaning damaged surface crack uneven thickness Smooth surface Expander Hard mold Pipe A is different according to the diameter please refer to the sheet below Outer diameter inch A inch Max Min Ф0 23 0 25 1 4 0 051 0 028 Ф9 52 3 8 0 063 0 039 Ф0 37 0 5 1 2 0 071 0 039 Ф0 63 5 8 0 095 0 087 Note 72 ...

Page 75: ... 88 33 10 63 72 2 439 111 0 737 5 63 46 34 10 2 73 2 358 112 0 717 4 60 23 35 9 779 74 2 28 113 0 697 3 57 18 36 9 382 75 2 206 114 0 678 2 54 31 37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 064 116 0 642 0 49 02 39 8 297 78 1 997 117 0 625 1 46 6 40 7 967 79 1 933 118 0 608 2 44 31 41 7 653 80 1 871 119 0 592 3 42 14 42 7 352 81 1 811 120 0 577 4 40 09 43 7 065 82 1 754 121 0 561 5 38 15 44 6...

Page 76: ...2 3 252 111 0 983 5 84 61 34 13 59 73 3 144 112 0 956 4 80 31 35 13 04 74 3 04 113 0 93 3 76 24 36 12 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2 663 117 0 833 1 62 13 40 10 62 79 2 577 118 0 811 2 59 08 41 10 2 80 2 495 119 0 77 3 56 19 42 9 803 81 2 415 120 0 769 4 53 46 43 9 42 82 2 339 121 0 746 5 50 87 44 9 054 83 2 265 122 0 ...

Page 77: ...62 11 32 101 3 22 15 362 9 24 51 41 63 10 93 102 3 13 14 342 8 25 49 19 64 10 54 103 3 04 13 323 9 26 47 08 65 10 18 104 2 96 12 306 2 27 45 07 66 9 83 105 2 87 11 289 6 28 43 16 67 9 49 106 2 79 10 274 29 41 34 68 9 17 107 2 72 9 259 3 30 39 61 69 8 85 108 2 64 8 245 6 31 37 96 70 8 56 109 2 57 7 232 6 32 36 38 71 8 27 110 2 50 6 220 5 33 34 88 72 7 99 111 2 43 5 209 34 33 45 73 7 73 112 2 37 4 1...

Page 78: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details ...

Reviews: