SERVICE MANUAL
5.1.3 IPM Continuity Check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital
tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance
value
Digital tester
Normal resistance
value
(+)Red
(-)Black
∞
(Several M
Ω
)
(+)Red
(-)Black
∞
(Several M
Ω
)
P
N
U
N
U
V
V
W
W
(+)Red
5.1.4 Fan Motor
Measure the resistance value of each winding by using the tester.
Model
YKT-32-6-202L
YKT-32-6-3L
YKT-48-6-206
YKT-63-6-200L
Brand
Tongde
Welling
Welling
Welling
Black – Red Main
Ω
86
213
152
88.5
Blue –Black AUX
Ω
64
156
142
138
5.1.5 Normal voltage of P and N
Normal voltage of P and N
208-240V(1-phase,3-phase)
380-420V(3-phase)
In standby
around 310VDC
around 530VDC
In operation
With passive PFC module
With partial active PFC module
With fully active PFC module
/
>200VDC
>310VDC
>370VDC
>450VDC