9.3.1.2 Indoor / outdoor unit communication error
Indoor / outdoor units communication error
Start: Power off , then Power on
the A/C by the Breaker. (reconnect
the power wire). Is it still displaying
the error code?
Yes
No
Change outdoor unit PCB
assembly(include wiring) totally
Check wiring on the outdoor and
indoor terminal follow the wiring
diagram. Is all connecting correctly?
Yes
No
Measure Vs, is it moving
alternately between positive
value and negative value? (Vs
is the voltage between S and
L2). Refer PIC 1
Turn on all indoor unit by
remote controller. Is all indoor
unit display
Turn off the all indoor
units. Is IPM power LED
lamp On? Refer PIC 3
Yes
Is PFC power LED lamp
off? Refer PIC 3.
Yes
A
:
Is all the wiring
between terminal and
Indoor PCB connect ok?
No
Yes
A
No
Reconnect the wiring
Is indoor units number correct?
Check on the outdoor check point
(18). (2 for dual zone, 3 for tri zone,
4 for qua zone). Refer PIC 5.
Is Main board
”
"
lamp on? Refer PIC 4.
Yes
No first time
Yes
Yes
Change the Indoor PCB
Power on by remote
controller, I
Is it still
displaying the error code
after 3 minutes?
Trouble is solved
No second time
No
Yes
Reconnect the wiring
No
change IPM
No
change PFC
No
Is the reactor connecting
well
?
No
Reconnect the wiring
Change Outdoor Main PCB
Yes
No