9.3.2.8 P2(Low pressure protection) error diagnosis and solution. (Only for VOM42H2RE104)
Error Code
P2
Malfunction decision
conditions
If the sampling voltage is not 5V, the LED will display the
failure.
Supposed causes
●
Wiring mistake
●
Over load protector faulty
●
System block
●
Outdoor PCB faulty
Trouble shooting:
Low pressure protection
Judge 1: Whether the
wiring between the low
pressure protector and main
control board is connected
well or correctly
Method: Short connect the
low pressure protector
socket, check whether the
system can run normally
Yes
No
Connect it well
Replace outdoor main board
No
Replace low pressure protector
Yes
Judge 2: Whether
the low pressure
protector is broken
Check whether
the refrigerant
system is ok
Judge 3: Check whether the
outdoor ambient
temperature is too low
No
Stop the unit
Yes
Method: Connect the pressure
gauge to the gauge joint of the
system, check whether the
pressure is lower than
0.14MPa
No
Leak hunting: Charge nitrogen or refrigerant
to the system, if the leakage is serious, there
will be distinct gas leakage “cici” sound; if the
leakage is slight, use the suds (mixture of
water and abluent is also ok if it can make
bubble) or electronic leak detector.
Yes
Judge 5: The refrigerant
pipe is blocked
No
Let the refrigerant out, then use the high
pressure nitrogen or refrigerant to blow pipe,
vacuumize and charge the refrigerant again
Yes
Judge 4: The
refrigerant of the
system is leakage