Auto fan action in heating mode.
6.4.3.3 Outdoor fan running rules:
6.4.3.3 High evaporator coil temp.T2 protection:
If T2>63
℃
, the indoor unit has no capacity demand and resume till 48
℃
.
6.4.3.4
Defrosting mode
:
Condition of defrosting:
T3
≦
TCDIN and lasts for 40 minutes. TCDIN=
-
2
℃
.
Defrosting action
:
T1-Ts
+2.5
Low
+2.0
Medium
+1.5
+1.0
High
16