12: Using the INP300S IEC 61850 Protocol Card
Electro
Industries/GaugeTech
™
Powered by Innovation™
</Communication>
The node <P type="IP" xsi:type="tP_IP"> (bolded in the example above) defines the
meter’s IP address. This IP address
must
be the same as the IP address configured in
the meter’s Device Profile (see
12.3.3.1: Configuring the Device Profile IEC 61850
Protocol Ethernet Network Card Settings, on page 12-17
) for each IEC 61850 Protocol
Ethernet Network card in the meter.
Also, make sure that the iedName field in the ConnectedAp section (underlined in the
example) is the same as the name field defined in the IED section.
This is how the unit is assigned its name and IP address.
1. The Shark® 270 meter’s .icd file can be downloaded directly from the Shark® 270
unit. To do this, use a web browser and enter:
http://aa.bb.cc.dd/
, where aa.bb.cc.dd is the IP address assigned to the IEC 61850 Protocol Ethernet
Network card (see
12.5: Upgrading the IEC 61850 Protocol Ethernet Network
Card’s Firmware, on page 12-29
).
The Information webpage is displayed.
NOTE:
The firmware runtime version which is displayed in the Run Ver field of this
webpage determines the default password for Network card upgrading, uploading
the .cid file, and resetting the Network card.
Firmware
Runtime
Version