Doc
#
E159708
13-2
13: Shark® 270 Meter Logging
Electro
Industries/GaugeTech
™
Powered by Innovation™
• Changes in relay state in the event of an alarm condition
• Changes in the state of digital inputs
• V-switch
TM
key: V2 and above
• Power Quality log
• Storage Size: User programmable; Maximum 2 MB.
• Parameter Logged: It logs all PQ events
• V-switch
TM
key: V5 and above
*
Because the memory is flash-based rather than NVRAM (non-volatile random-access
memory), some sectors are reserved for overhead, erase procedures, and spare sec-
tors for long-term wear reduction.
V-Switch
TM
Key
Memory*
Log size
Available Logs
1
NA
NA
NA
2
2 MB
2 MB
1. 3 Historical Logs
2. Alarm Log
3. Control output log
4. Input status change log
3
4 MB
2 MB
1. 3 Historical Logs
2. Alarm Log
3. Control output log
4. Input status change log
4
10 MB
2 MB
1. 6 Historical Logs
2. Alarm Log
3. Control output log
4. Input status change log
5. Waveform Log
5
128 MB
1. Max 6 MB per Historical log
2. Max 8 MB for Waveform Log
3. Max 2 MB for PQ log
1. 6 Historical Logs
2. Alarm Log
3. Control output log
4. Input status change log
5. Waveform Log
6. PQ log