Doc
#
E159708
C-28
C: Shark® 270 Meter DNP Mapping
Electro
Industries/GaugeTech
™
Powered by Innovation™
• For Default Variation, the following rules apply:
• If the value type is int16 (signed or unsigned) the default variation shall be
shown as 4.
• If the value type is float, the default variation shall be shown as 5.
• For any other type, the variation shall be 3.
• For scaling, the following rules apply:
• If the reading is a float type, the scaling shall be float also.
22
0x1004
30
1
0
Angle Phase
IB
2
23
0x1005
30
1
0
Angle Phase
IC
2
24
0x1006
30
1
0
Angle Phase
VAB
2
25
0x1007
30
1
0
Angle Phase
VBC
2
26
0x1008
30
1
0
Angle Phase
VCA
2
27
0x7530
30
1
0
CT Num
2
28
0x752F
30
1
0
CT Den
2
29
0x7532
30
1
0
PT Num
2
30
0x7531
30
1
0
PT Den
2
31
0x0417
30
1
0
PF A
5
32
0x0419
30
1
0
PF B
5
33
0x041B
30
1
0
PF C
5
34
0x0405
30
1
0
W Phase A
5
35
0x0407
30
1
0
W Phase B
5
36
0x0409
30
1
0
W Phase C
5
Analog Inputs - Objects 30, 32, 34
Default
Variation
DNP
Point
Modbus
Register
DNP
Object
Value
Scaling
Class 0
Object 34
Object 32
Class
Deadband
%
3, 2, 1
Description